Term
Ves Con
Describe the Delta T limits for H/U and C/D. |
|
Definition
-Reactor vessel flange and shell differential temperature shall be limited to: -H/U: <78F. -C/D: <132F. |
|
|
Term
Ves Con
Describe any precaustions for raising recirculation flow. |
|
Definition
-Flow shall not be raised unless top and bottom head delta T is < 145F. |
|
|
Term
Ves Con
Describe the maximum H/U and C/D limit. |
|
Definition
-Shall not exceed 100F/hr. |
|
|
Term
Ves Con
Describe the operating and design temperature limit. |
|
Definition
-Design: 562F. -Operating: 525F. |
|
|
Term
Ves Con
Describe the operating and design pressure limit. |
|
Definition
-Design: 1250 psig. -Operating: 1025 psig. |
|
|
Term
Ves Con
Describe the amount of core flow. |
|
Definition
|
|
Term
Ves Con
Describe the amount of steam flow. |
|
Definition
|
|
Term
Ves Con
Describe the amount of feed flow. |
|
Definition
|
|
Term
Ves Con
Describe the setpoints for vessel head seal flange leak rate detection. |
|
Definition
|
|
Term
Ves Con
Describe the function of the CRD housing support. |
|
Definition
-CRDs are not ejected due to stub tube failure. . -Limits travel to 3". |
|
|
Term
Ves Con
Describe the function of the control rod tube guide. |
|
Definition
-Houses CR when withdrawn. -Four holes for water flow thru fuel. |
|
|
Term
Ves Con
Describe the function of the velocity limiter. |
|
Definition
-Prevents freefall less than 5' (3'11") / second. -Limits reactivity addition of <280 cal/gram. |
|
|
Term
Ves Con
Describe the jet pump / recirc flow percentages. |
|
Definition
-42% from recirc pumps (driving). -58% from jet pumps (driven). |
|
|
Term
Ves Con
Describe the jet pumps. |
|
Definition
-20 total. -10 per loop0. Eensures 2/3 coverage of core (-174"). |
|
|
Term
Ves Con
Describe the indicated safeguard water level. |
|
Definition
|
|
Term
Ves Con
Describe the indicated core flood water level. |
|
Definition
|
|
Term
Ves Con
Describe the indicated feedwater water level. |
|
Definition
|
|
Term
Ves Con
Describe the indicated vessel flood water level. |
|
Definition
|
|
Term
Ves Con
Describe the limits on starting a recirc pump. |
|
Definition
-Don't start if: -50F difference across recirc pumps (or) -145F Rx difference. |
|
|
Term
Ves Con
Describe the Rx low water level alarm setpoint. |
|
Definition
|
|
Term
Ves Con
Describe the Low/Low water level setpoint and what happens. |
|
Definition
-Set at -47". -Trips recirc pumps. -Initiates groups 1 and 2 -Starts RCIC, HPCI, RHR, CS, EDG's and APRS low level logic. |
|
|
Term
Ves Con
Describe the High water level setpoint and what happens. |
|
Definition
-Set at +48". -Trips RCIC. -Trips HPCI. -Trips FW. -Trips the turbine. |
|
|
Term
Ves Con
Descripe what happens at -156". |
|
Definition
Containment spray permissive reset. |
|
|
Term
Ves Con
Describe the LPCI loop select permissive setpoint. |
|
Definition
|
|
Term
Ves Con
Describe what happens at <600psig Rx pressure. |
|
Definition
-Bypasses MSIV closure and low condenser vacuum inputs to RPS when mode switch in startup, shutdown or refuel. |
|
|
Term
Ves Con
Describe what happens when <420 psig Rx pressure. |
|
Definition
-LPCI valve permissive. -ECCS pump start permissive. |
|
|
Term
Ves Con
Describe the High pressure SCRAM setpoint. |
|
Definition
|
|
Term
Ves Con
Describe the indications for a failure of the shroud support access cover. |
|
Definition
-Sudden drop in Core Plate d/p. -Sudden drop in reactor power. -Rise in indicated core flow. -Drop in all jet pump d/ps. |
|
|
Term
Ves Con
Descripe the indications of a shroud support access cover coming completely off. |
|
Definition
-Core plate d/p, reactor power, indicated core flow, and jet pump d/p will be 15% above normal. |
|
|
Term
Ves Con
Describe the temperatures taken during H/U and C/D. |
|
Definition
-Taken every 15 minutes until 3 consecutive within 5F in each location. -Rx vessel shell adjacent to shell flange. -RX vessel bottom drain. -Recirc loops A and B. -RX vessel bottom head. |
|
|
Term
Ves Con
Describe the function of the biological shield. |
|
Definition
-Provide shielding to protect equipment from radiation and thermal effects. -Provides main protection for areas surrounding Rx. -ALARA. |
|
|
Term
Ves Con
Describe the height of the steam seperator skirt. |
|
Definition
|
|
Term
Ves Con
Describe the jet pumps with multiple taps. |
|
Definition
-A loop 11 and 16. -B loop 1 and 6. |
|
|
Term
Ves Con
Describe core orificing. |
|
Definition
-More power occurs in center of core so more two-phase flow in center. -Larger openings in center of core. |
|
|
Term
Ves Con
Describe a rod when at pos 48. |
|
Definition
-Valve off seat area to allow cooling water flow path. -If it uncouples it will go to position 49 and may get alarm. |
|
|
Term
Ves Con
Describe the fuel bundle and control rod locations. |
|
Definition
-Fuel: odd-even. -Control rod: even-odd. |
|
|
Term
Ves Con
Describe a control rod withdrawl sequence. |
|
Definition
-Limit worth so that core will not be more than 1.3% reactivity supercritical during rod drop accident. |
|
|