Term
UPS
Describe the power to Y21. |
|
Definition
-Normally from MCC-143. -Emergency from MCC-133. -Power selecter is power seeking. |
|
|
Term
UPS
Describe what happens on a loss of Y20. |
|
Definition
-11/12 MG scoop tube lock. -Loss all 4 ECCS sump pumps. -Feed water heater dumps/spills fail open. -Vacuum breaker lights out. -Lose APRMs. -Recombiner outlet closes so vacuum degrades. -RHR min flows fail open. |
|
|
Term
UPS
Describe power at Y91. |
|
Definition
-Normally powered from LC-108 converted to DC to 17 battery, converted back to AC to computers. -Alternate is from LC-107. -Backup is from 17 battery. -Static switch is make before break. -Static switch is normal seeking. |
|
|
Term
UPS
Describe what causes the Y91 static switch to transfer load. |
|
Definition
-Y91 O/P overvoltage > 537V. -Y91 O/P undervoltage < 423 for 10 secs. -Y91 overload > 103% O/P current. -Faults. -Static switch energizes, power breaker opens, new power breaker shuts, static switch deenergizes. |
|
|
Term
UPS
Describe Y91 load shed. |
|
Definition
-If power is supplied by 17 battery then the 3 process computer loads will be shed after 30 minutes. -Allows other loads to be supplied for additional 60 minutes. |
|
|
Term
UPS
Describe power to Y71 and operation of the static switch. |
|
Definition
-Normally powered by 13 battery. -Alternate source by 15/11EDG/1AR bus through LC-103 to MCC-134. -Then powers Y10 and Y70. -Static switch is a fast break before make. -Normal seeking. -Does not auto transfer back if shifted manually. -Will not shift if not in sync or alternate power not available. |
|
|
Term
UPS
Describe power to Y81 and operation of the static switch. |
|
Definition
-Normally powered by 16 battery. -Alternate source by 156/12EDG/1AR bus through LC-104 to MCC-144. -Then powers Y30 and Y80. -Static switch is a fast break before make. -Normal seeking. -Does not auto transfer back if shifted manually. -Will not shift if not in sync or alternate power not available. |
|
|
Term
UPS
Describe faults causing Y71/81 to auto shift. |
|
Definition
-Inverter DC I/P blown fuse. -Inverter low I/P voltage < or equal to 210VDC (alarm at 220, shutdown at 200). -Inverter O/P undervoltage <108VAC. -Inverter O/P overvoltage >132VAC. -Inverter overload: O/P > 343 amps or O/P undervoltage <108VAC. |
|
|
Term
|
Definition
-For Y81/71. -If overload condition and alternate power not available starts zip mode. -Inverter rapid s/d. -Powers up to 312amps (150%) FOR 30 SECONDS. -If fault clears then return to normal. -If doesn't clear then inverter lowers to 260amps (125%) and 114 volts. |
|
|
Term
UPS
Describe what happens on a loss of Y10. |
|
Definition
-No full core display. -No rod select matrix. -RWCU trip (HI temp / MO-2399 closes). -No A side IRM/APRMs. -Cannot move rods. -Have to bypass OG storage. -SJAE rad monitors. -Fire panel C-300. -Loss of HWC system. -1 power supply DFCS. -1 power supply lo lo set. |
|
|
Term
UPS
Describe what happens on a losss of Y70. |
|
Definition
-Lose inboard MSIC AC light. -A spotmos lost/ alarm. -RCIC flow controller out. -RWCU inboard and recirc Sx inboard close. -Steam chase temp goes up. -No Group 2 reset. -RWM lost / rod block. -Need to take manual control of RHRSW. -Secondary containment isolation. -EFT high rad mode. |
|
|
Term
UPS
Describe what happens on a loss of Y80. |
|
Definition
-Lose outboard MSIV AC light. -B spotmos lost / alarm. -HPCI flow controller out. -RWCU-2398 closes. -SBGT starts (gr II iso). -ASDS panel power. |
|
|
Term
UPS
Describe what happens on a loss of Y30. |
|
Definition
-EPR lost must use MPR. -Rx pressure increase. -FRVs lock. -CRD flow control fail open. -Lose vacuum indication. -SJAE supplies fail open. -RWCU hi temp trip inop. |
|
|