Term
SW
Describe the SW pump power supplies. |
|
Definition
-11 pump: LC-107. -12 pump: LC-104. -13 pump: LC-102. |
|
|
Term
|
Definition
-East and West turbine building headers. -Rx building. -ECCS room coolers/motors. -RBCCW HXs. -Recirc MG sets. -Emergency makeup to hotwell. -Admin building, computers, chillers. |
|
|
Term
SW
Describe any SW alarms or interlocks. |
|
Definition
-Low discharge pressure at 45psig. -Standby pump starts at 40psig if set up for standby. |
|
|
Term
|
Definition
Provides keep fill to RHRSW up to pump discharge check valves. |
|
|
Term
SW
Describe the SW strainer. |
|
Definition
-Rotates at 4 rpm. -Powered from MCC-123. -Backwash valve opens at 2.1 psig, shuts at 0.9 psid. |
|
|
Term
|
Definition
-12 and 13 pumps get load shed on a loss of power and an ECCS signal. -11 pump is shed on station loss of power to LC-107 and 10 seconds. |
|
|
Term
SW
Describe the RHRSW pump power supplies. |
|
Definition
-11 & 13 pumps: 15 bus. -12 & 14 pumps: 16 bus. |
|
|
Term
SW
Describe the RHRSW loads. |
|
Definition
-RHR HXs. -RHR HX outlet valves. |
|
|
Term
SW
Describe the RHRSW/RHR HX D/P requirement and how it is controlled. |
|
Definition
-SW > the RHR by 20#. -Controlled by control valve that controls pressure when energized (RHR pump running). |
|
|
Term
SW
Describe the RHRSW strainer alarm. |
|
Definition
Strainer at 5 psid, max D/P at 10 psid. |
|
|
Term
SW
Describe RHRSW pumps on LPCI initiation signal. |
|
Definition
-All 4 pumps auto secure. -Can restart if > -47" Rx level and < 1.84 psig drywell pressure or if override. -Should also secure a RHR pump for EDG loading. |
|
|
Term
SW
Describe the EDGSW pump power supplies. |
|
Definition
-11 pump: MCC-134. -12 pump: MCC-143A. |
|
|
Term
SW
Describe the EDGSW loads. |
|
Definition
|
|
Term
SW
Describe the EDGSW flow and pressure alarms. |
|
Definition
-Low flow: 367gpm. -Low discharge pressure: 30psig. -Low EDG water pressure: 7 psig. |
|
|
Term
SW
Describe EDGSW minimum flow. |
|
Definition
-Min flow is 367gpm (7gpm for error). |
|
|
Term
SW
Describe which EDGSW pump can be operated from ASDS. |
|
Definition
|
|
Term
SW
Describe the ESW pump power supplies. |
|
Definition
-13 pump: MCC-134. -14 pump: MCC-144. |
|
|
Term
SW
Describe the ESW loads. |
|
Definition
-Emergency AC units. -ECCS motor oil coolers. -ECCS room coolers. -11/12 core spray. -13/14 RHR. |
|
|
Term
SW
Describe the ESW strainer alarm. |
|
Definition
Hi Y-strainer dP at 2 psid for 135secs. |
|
|
Term
SW
Describe the ESW SW pressure setpoint. |
|
Definition
|
|
Term
SW
Describe the low EFT condenser dP. |
|
Definition
|
|
Term
SW
Describe the ESW auto start sequence. |
|
Definition
-Supply breaker to 15/16 bus opens and EDG output breakers shut. -1AR breaker shut. |
|
|