RPV Instrumentation and Backfill (RPV Inst)
BWR Systems
15
Other
Not Applicable
05/28/2012

Additional Other Flashcards

 


 

Cards

Term
RPV Inst

Describe reference leg indications for failures.
Definition
-Break: Level fails high.
-Prassure fails: fails low.
Term
RPV Inst

Describe variable leg indications for failures.
Definition
-Break: fails low.
-Pressure: remains unaffected.
Term
RPV Inst

Describe the reference leg location.
Definition
-Outside drywell in Rx building.
Term
RPV Inst

Describe the hot calibrated instruments and indicated levels.
Definition
-Safeguards: -50" to +50".
-Feedwater: 0 to +60".
-Core flood: -335" to +65".
Term
RPV Inst

Describe the cold calibrated instruments and indicated levels.
Definition
Vessel flood: -50" to +350".
Term
RPV Inst

Describe the backfill flow indicator power supply.
Definition
L-38.
Term
RPV Inst

Describe the reason for backfill.
Definition
-Notching: during depressurizing conditions, gasses leave solution and form bubbles causing the density to decrease and cause higher than actual level indications.
Term
RPV Inst

Describe the backfill system and rated flow.
Definition
-8 lbm/hr (.016 gpm).
-Metering valves set to 3lbm/hr (.006 gpm).
-From CRD (pure water and low oxygen).
Term
RPV Inst

Describe the Rx high pressure SCRAM setpoint.
Definition
1056 psig.
Term
RPV Inst

Describe the Rx low pressure setpoint and what happens.
Definition
-420 psig if in coincidence with -47".
-Will start LP ECCS pumps and open associated injection valves.
Term
RPV Inst

Describe the Rx press HI/LO setpoints.
Definition
-1025 psig HI.
-900 psig LO.
Term
RPV Inst

Describe the reactor water level HI/LO setpoints.
Definition
-LO: +30" with 3 second time delay.
-HI: +40"
Term
RPV Inst

Describe the Rx low level scram setpoint and logic.
Definition
-Set at +9".
-1 out of 2 taken twice.
Term
RPV Inst

Describe the Rx low low water level setpoint and what happens.
Definition
-Set at -47".
-Trip recirc drive motor.
-Group 1 and 3 isolation.
-Start HPCI, RCIC, EDGs, and CS.
Term
RPV Inst

Describe the Rx High water level trip and what happens.
Definition
-Set at +48".
-Trips main turbine and RFPs.