Shared Flashcard Set

Details

Rod Control
N/A
8
Engineering
Professional
04/22/2014

Additional Engineering Flashcards

 


 

Cards

Term
What is the normal output voltage of the Rod drive MG sets?
Definition
260 VAC
Term
How fast will rods step in, in auto?
Definition

8-72 steps per minute

 

8 spm from 1.5-3F

40 spm@ 4F

72 spm @ 5F more

 

difference between Hi Tave actioneered and Tref

 

 

Term
Shutdown bank rod speed
Definition
64 spm
Term
Control bank rod speeds?
Definition
48 spm
Term
What does the "startup" switch on MB4 do?
Definition

 Resets the following:

  • P/A converter
  • overlap counter
  • slave cycler
  • step counters
  • urgent failures
  • master cycler
Term
What does the "reset" at MB4 do?
Definition
Resets all logic cabinet and power cabinet urgent alarms
Supporting users have an ad free experience!