Term
RWCU
Describe teh normal flow path for RWCU. |
|
Definition
-Suction from B recirc line and RPV head drain. -Passes thru 2 PCIVs then thru 3 regen and 2 non-regen HXs. -Thru 1 of 2 pumps. -Thru both demins. -Then back thru the 2 regen HXs. -Thru a non PCIV and out to the A and B FW lines via RCIC and HPCI injection lines. |
|
|
Term
RWCU
Describe the heat reject mode. |
|
Definition
Bypasses tube side for regen HX for max heat removal. |
|
|
Term
RWCU
Describe the Hx bypass mode. |
|
Definition
Bypassess all HXs, conserving NPSH. |
|
|
Term
RWCU
Describe what will give a group 3 isolation. |
|
Definition
-Low low level. -High DW press. -Flow >462/-200 for 10 sec. -Area temp >170F. |
|
|
Term
RWCU
Describe the pumps rated flow and power supplies. |
|
Definition
-Rated at 160gpm. -Powered by MCC-132/122. |
|
|
Term
RWCU
Describe what will cause the pumps to trip. |
|
Definition
-Suctions not full open. -Discharge full closed and <40gpm dump flow. -Loss of indication to suction valve. -High inlet temp to demins >140F. |
|
|
Term
RWCU
Describe resin breakthrough indications. |
|
Definition
-High conductivity in Rx. -Low pH in Rx water. -Increase Rx water sulfates. -Slight decrease in power. -D/P of filter may drop. -D/P of filter strainer may increase. |
|
|
Term
RWCU
Describe the reject/dump flow control isolations. |
|
Definition
-140psig downstream of CV-2403. -5psig upstream of CV-2403. |
|
|
Term
|
Definition
-Goes to hotwell, waste collector or waste surge. -Limit reject flow to 79gmp to protect non-regen. |
|
|
Term
RWCU
Describe the High/High inlet temp setpoint and what happens. |
|
Definition
-140F. -Shuts discharge valves and trips teh pumps. |
|
|
Term
RWCU
Describe the low/high alarm setpoint and what happens. |
|
Definition
|
|
Term
RWCU
Describe when the filter is manually removed. |
|
Definition
-25#dp. -Hi strainer d/p at 5#. -Hi effluent cond .1umho/cm. |
|
|
Term
RWCU
Describe when the filter automatically goes to hold. |
|
Definition
-Low flow 35gpm. -Hi filter d/p 30#. -Hi strainer d/p 10#. -Holding pumps start 35gpm. |
|
|
Term
RWCU
Describe the effects on RWCU on a loss of Y-10. |
|
Definition
-MO-2399 and CV-2404/2405 close on loss of temp monitoring. -Pumps trip. |
|
|
Term
RWCU
Describe the effects on RWCU on a loss of Y-70. |
|
Definition
-MO-2397 (1st suction) closes due to valve control relay in PCIS de-energizing. -Pumps trip. |
|
|
Term
Describe the effects on RWCU on a loss of Y-80. |
|
Definition
-Closes MO-2398,2399 due to valve control relay in PCIS de-energizing. -Pumps trip. |
|
|