Reactor Recirculation Flow Control (Recirc Flow)
BWR Systems
11
Other
Not Applicable
05/28/2012

Additional Other Flashcards

 


 

Cards

Term
Recirc Flow

Describe the drive motor power supply.
Definition
Buss 11/12.
Term
Recirc Flow

Describe the recircflow controller rate limitations.
Definition
-Limits increases to < or equal to 2%/sec.
-Limits decreases to < or equal to 2.5%/sec.
Term
Recirc Flow

Describe the recirc pump speed limits and reason.
Definition
-Equal or < to 30% until FW flow > 20% and discharge valve full open.
-For NPSH.
Term
Recirc Flow

Describe the recirc runbacks.
Definition
-With steam flow > 55.4% and both pumps running and a FW or condensate pump trip runback to 45% resets at 50.7% steam flow.
-FW flow <20% for 15 secs runback to 30%.
-Disch valve <90% at 66secs runback to 30%.
Term
Recirc Flow

Describe the MG set power supplies.
Definition
-11 Recirc MG set - 11 bus.
-12 Recirc MG set - 12 bus.
Term
Recirc Flow

Describe teh AC lube oil pumps power supplies.
Definition
MCC-122/132.
Term
Recirc Flow

Describe the recirc valves power supply.
Definition
MCC-133B/143B.
Term
Recirc Flow

Describe the initial exciter field flash power supply.
Definition
Y-20.
Term
Recirc Flow

Describe the DC lube oil pump power supply.
Definition
D-313.
Term
Recirc Flow

Describe the requirements to restart a recirc pump at power.
Definition
-Running pump <50%.
-Idle loop w/in 50F of coolant temp.
-Bottom head w/in 145F of upper head.
Term
Recirc Flow

Describe the limitations with temp stratification.
Definition
-Recirc flow shall not be increased unless coolant delta T top to bottom is <145F.