Term
RMCS
Describe what Y-10 powers in relation to RMCS. |
|
Definition
-Rod select matrix. -Full core display. -4-rod display. |
|
|
Term
RMCS
Describe what Y-20 powers in relation to RMCS. |
|
Definition
-RMCS relays. -RMCS drive buses. -HCU directional control valves. -Full core display rod selected light. |
|
|
Term
RMCS
Describe what the rod select power switch does. |
|
Definition
-Supplies 28Vdc power to activate rod select matrix. |
|
|
Term
RMCS
Describe the function of the select pushbutton. |
|
Definition
-Energizes the 3A-K32 XX-XX relay. -Which connects directional control valves of selected HCU to the RMCS drive buses. -Also energizes the full core display light for selected control rod. |
|
|
Term
RMCS
Describe the purpose of the timer malfunction. |
|
Definition
-Protection for if timer fails during a withdraw. -If remains energized for 2 sec, and not performing continuous withdraw a withdraw block occurs. |
|
|
Term
RMCS
Describe the function of the timer test switch. |
|
Definition
-TEST-simulates timer malfunction. -White 2 SEC DELAY light illuminuates immediately. -Red BLOCK light illuminates 2 seconds later. |
|
|
Term
RMCS
Describe the Rod movement control switch lights. |
|
Definition
-White-permit. -Amber-Settle. -Red-Rod out. -Green-Rod in. |
|
|
Term
RMCS
Describe the function of the rod out notch override. |
|
Definition
-Interrupts timer during withdraw portion of timing cycle for continuous withdraw. |
|
|
Term
RMCS
Describe the function of the emergency in. |
|
Definition
-Bypasses all rod movement controlls except the RWM insert blocks. -No settle function. |
|
|
Term
RMCS
Describe the function of the rod drift test. |
|
Definition
Hold in test while driving rod to test drift alarm. |
|
|
Term
RMCS
Describe what will cause a drift alarm. |
|
Definition
-Sensed rod motion with no drive signal present (no even reed switch closed or odd reed switch closed and rod not being driven). |
|
|
Term
RMCS
Describe the function of theRefuel Mode One Rod Permissive. |
|
Definition