Shared Flashcard Set

Details

Reactor Manual Control System (RMCS)
BWR Systems
12
Other
Not Applicable
05/28/2012

Additional Other Flashcards

 


 

Cards

Term
RMCS

Describe what Y-10 powers in relation to RMCS.
Definition
-Rod select matrix.
-Full core display.
-4-rod display.
Term
RMCS

Describe what Y-20 powers in relation to RMCS.
Definition
-RMCS relays.
-RMCS drive buses.
-HCU directional control valves.
-Full core display rod selected light.
Term
RMCS

Describe what the rod select power switch does.
Definition
-Supplies 28Vdc power to activate rod select matrix.
Term
RMCS

Describe the function of the select pushbutton.
Definition
-Energizes the 3A-K32 XX-XX relay.
-Which connects directional control valves of selected HCU to the RMCS drive buses.
-Also energizes the full core display light for selected control rod.
Term
RMCS

Describe the purpose of the timer malfunction.
Definition
-Protection for if timer fails during a withdraw.
-If remains energized for 2 sec, and not performing continuous withdraw a withdraw block occurs.
Term
RMCS

Describe the function of the timer test switch.
Definition
-TEST-simulates timer malfunction.
-White 2 SEC DELAY light illuminuates immediately.
-Red BLOCK light illuminates 2 seconds later.
Term
RMCS

Describe the Rod movement control switch lights.
Definition
-White-permit.
-Amber-Settle.
-Red-Rod out.
-Green-Rod in.
Term
RMCS

Describe the function of the rod out notch override.
Definition
-Interrupts timer during withdraw portion of timing cycle for continuous withdraw.
Term
RMCS

Describe the function of the emergency in.
Definition
-Bypasses all rod movement controlls except the RWM insert blocks.
-No settle function.
Term
RMCS

Describe the function of the rod drift test.
Definition
Hold in test while driving rod to test drift alarm.
Term
RMCS

Describe what will cause a drift alarm.
Definition
-Sensed rod motion with no drive signal present (no even reed switch closed or odd reed switch closed and rod not being driven).
Term
RMCS

Describe the function of theRefuel Mode One Rod Permissive.
Definition
-Illuminates when:
-Mode switch in REFUEL.
-All rods inserted.
-No rod selected.
Supporting users have an ad free experience!