Term
RBCCW
Describe the power supplies to the RBCCW pumps. |
|
Definition
-11 pump: MCC-133. -12 pump: MCC-142A. |
|
|
Term
RBCCW
Describe the RBCCW loads. |
|
Definition
-RWCU NRHX. -Recirc pump motor and seal water coolers. -RB & TB process system sample coolers and chillers. -Fuel pool cooling water HXs. -RHR pump seal coolers. -DW coolers. -DW equipment drain sump HX. -CRD pump thrust bearing and gear box oil coolers. -PAS system. |
|
|
Term
RBCCW
Describe the flow to recirc pumps and alarms, trips. |
|
Definition
-Normal flow 66.5 gpm. -Low flow alarm at 58 gpm. -Loss of RBCCW must trip recirc pumps after 60 secs. |
|
|
Term
RBCCW
Describe the surge tank alarms. |
|
Definition
-High alarm: 6'4". -Low alarm: 2'6". |
|
|
Term
RBCCW
Describe the system pressure alarms/standby features. |
|
Definition
-Low pressure is 30psig. -Standby pumps starts at 30psig if in auto. |
|
|
Term
RBCCW
Describe the load shed of RBCCW. |
|
Definition
Shed on LOOP with ECCS signal. |
|
|
Term
RBCCW
Describe rad monitoring of the RBCCW system. |
|
Definition
-RM downstream of pumps. -Alarms at 1500cps. |
|
|
Term
RBCCW
Describe primary containment with RBCCW. |
|
Definition
-Supply MO valve and check valve. -2 discharge MO valves. -All on outside of drywell. |
|
|
Term
RBCCW
Describe what cools the RBCCW HXs. |
|
Definition
|
|
Term
RBCCW
Describe the HX operation requirements. |
|
Definition
-During summer ops: all 3 HXs w/SW to all 3. -During winter ops: 2 HX w/SW to 1. -Max dP of SW to heat exhchanger is 20psid. |
|
|
Term
RBCCW
Describe corrosion protection for RBCCW. |
|
Definition
Potassium chromate is added. |
|
|
Term
RBCCW
Describe power supplies to RBCCW MO valves. |
|
Definition
-2 drywell cooler MO isolation valves powered by MCC-143, and 2 others by MCC-133. -Inlet to drywell and second outlet from drywell MO valves powered by MCC-134. -First outlet valve from drywell powered by MCC-143. -NRHX outlet valve is MCC-122 (non "E"). |
|
|