Pri Con
Describe the designed pressures, temperatures, and leakage. |
|
Definition
-Internal pressure of 56psig. -External pressure of 2 psig. -Temperature of 281 d-F. -Leakage of 1.2% by weight & .5% by volume in 24 hours. |
|
|
Term
Pri Con
Discuss atmoshpere inerting. |
|
Definition
During power operation the drywell and TORUS inerted to <4% oxygen using nitrogen gas. |
|
|
Term
Pri Con
Describe the torus-to-drywell vacuum breakers. |
|
Definition
-8, 18" check valves. -Air operation for testing. -Full open at .5psid. |
|
|
Term
Pri Con
Describe the torus water temp limits. |
|
Definition
-Normal limit is < or equal to 90F and > or equal to 65F. -Allowed up to 99F for testing but cannot be > 90F >24 hours after testing. ->120F must depress <200psig w/in 12 hours. |
|
|
Term
|
Definition
-2 divisions. -8 RTDs. -Powered by Y-70 and Y-80. |
|
|
Term
Pri Con
Describe drywell atmospheric cooling. |
|
Definition
-4 fans in drywell with 16 dampers. -Cooled by RBCCW. -Maintain <135F for normal equipment ops. -Designed to lower air temp <105F w/in 8-10 minutes post shutdown. |
|
|
Term
Pri Con
Describe the TORUS size basis. |
|
Definition
-Designed to absorb energy from DBA-LOCA without exceeding 170F. -Assumes minimum level and max temp of 125F. |
|
|