Term
PCIS
Describe Class "A" valves. |
|
Definition
-Penetrate primary containment. -Communicate directly w/reactor vessel. -2 valves (1 inside, 1 outside drywell). -Inboard valves are AC, outboard are DC. -Rx supply lines use 2 check valves in series. |
|
|
Term
PCIS
Describe Class "B" valves. |
|
Definition
-Penetrate primary containment. -Do not communicate directly w/reactor vessel. -Communicate w/primary containment free space. -2 valves, both outside drywell. |
|
|
Term
PCIS
Describe Class "C" valves. |
|
Definition
-Penetrate primary containment. -Do not communicate directly w/reactor vessel or primary containment free space. -1 valve outside of drywell. -Not part of PCIS. |
|
|
Term
PCIS
Describe what isolates on a group I signal. |
|
Definition
-MSIVs. -Main steam line drain valves. -Recirc sample isolation. |
|
|
Term
PCIS
Describe the group I signals. |
|
Definition
-Rx low-low water level: -47". -Main steam line low pressure: < or equal to 840psig when in RUN. -Steam tunnel high temperature: 195-200F. (1 of 2/twice). -Steam line high flow 135-140% of rated (1 of 2/twice). |
|
|
Term
PCIS
Describe the steam chase temperature alarm setpoint. |
|
Definition
|
|
Term
PCIS
Describe the group II isolations. |
|
Definition
-Containment vent/purge valves. -TIP system. -Atmosphere sampling & analyzer isolation. -Drywell sump isolation. -RHR / shutdown cooling. -RHR discharge to radwaste. |
|
|
Term
PCIS
Describe the group II signals. |
|
Definition
-Reactor low water level: +9". -Drywell high pressure: 1.84psig. |
|
|
Term
PCIS
Describe partial group II isolations. |
|
Definition
-Containment vent/purge valves. -Atmosphere sampling & analyzer isolation. |
|
|
Term
PCIS
Describe the partial group II signals. |
|
Definition
-Rx water level low-low: -47". -Drywell high pressure: 1.84psig. -Rx building vent exhaust high: 26mrem/hr. -Fuel pool high radiation: 50mrem/hr. -1 highscale or 2 downscale (.1mrem/hr). |
|
|
Term
PCIS
Describe the group III isolations. |
|
Definition
-RWCU (suctions and discharge). -Recirec sample isolations (CV-2790/2 791). |
|
|
Term
PCIS
Describe the group III isolation signals. |
|
Definition
-Rx low-low water level: -47". -Drywell high pressure: 1.84psig. -RWCU system high flow: 462gpm w/10 second delay or -200gpm w/10 second delay. -RWCU room high temperature: 170F. |
|
|
Term
PCIS
Describe the group IV isolation valves. |
|
Definition
|
|
Term
PCIS
Describe the group IV isolation signals. |
|
Definition
-HPCI high steam flow: 300,000 lbm/hr for 4 seconds. -HPCI steam line area temperature: 187.5F. -HPCI steam supply line low pressure: 100psig. |
|
|
Term
PCIS
Describe the group V isolations. |
|
Definition
|
|
Term
PCIS
Describe the group V isolation signals. |
|
Definition
-RCIC high steam flow: 44,434 lbm/hr for 5 seconds. -RCIC steam line area temperature: 187.5F. -RCIC steam supply line low pressure: 60psig. |
|
|
Term
PCIS
Describe the function of the main steam line high flow signal. |
|
Definition
-Ensures fuel peak cladding temperature remains below limit and offsite doses do not exceed limit. |
|
|
Term
PCIS
Describe the group I isolation reset. |
|
Definition
-Signal must be cleared. -All MSIV switches in CLOSE. -Reset pushbuttons on C-03. |
|
|
Term
PCIS
Describe the group II and III isolations resets. |
|
Definition
-Signals must be cleared. -All non-MOVs switches must be in CLOSE. -Reset switches on C-04. -Switch must be reset in both directions (inboard/outboard). |
|
|
Term
PCIS
Describe the group IV and V isolation resets. |
|
Definition
-Signals must be cleared. -Use HPCI or RCIC steam line isolation reset pushbutton on C-03 or C-04. |
|
|
Term
PCIS
Describe the PCIS channel power supplies. |
|
Definition
-Channel A: RPS MG set A. -Channel B: RPS MG set B and Y-80. |
|
|