Term
WHAT REFERENCED PUBLICATION ARE REFERENCE IN NFPA 17 FOR DRY CHEMICAL EXTINGUISHING SYSTEMS? |
|
Definition
- NFPA NATIONAL FIRE PROTECTION ASSOCIATION
- ANSI AMERICAN NATIONAL STANDARDS
- ASME AMERICAN SOCIETY OF ENGINEERS
- ASTM
- UL UNDERWRITERS LABORATORIES INC
|
|
|
Term
| WHAT DOES THE WORD "SHALL" INDICATE OR MEAN ACCORDING TO THE NFPA 17 |
|
Definition
| INDICATES A MANDATORY REQUIREMENT |
|
|
Term
| WHAT DOES THE WORKD "SHOULD" INDICATE OR MEAN ACCORDING TO THE NFPA 17 |
|
Definition
| A RECOMMENDATION OR THAT WHICH IS ADVISED BUT NOT REQUIRED |
|
|
Term
| WHAT DOES THE NFPA 17 DEFINE AS AN INSPECTION |
|
Definition
| A VISUAL EXAMINATION OF A SYSTEM THEREOF TO VERIFY THAT IT APPEARS TO BE IN OPERATING CONDITION AND IS FREE OF PHYSICAL DAMAGE |
|
|
Term
WHAT DOES THE NFPA 17 DEFINE AS "MAINTENANCE"?
|
|
Definition
| WORK, INCLUDING, BUT NOT LIMITED TO REPAIR, REPLACEMENT, AND SERVICE, PERFORMED TO ENSURE THAT EQUIPMENT OPERATES PROPERLY |
|
|
Term
| WHAT DOES THE NFPA 17 CONSIDER "SERVICING" |
|
Definition
| PERFORMING MAINTENANCE, RECHARGING, OR HYDROSTATIC TESTING |
|
|
Term
| WHAT IS A "TRAINED" PERSON ACCORDING TO THE NFPA 17? |
|
Definition
| A PERSON WHO HAS UNDERGONE THE INSTRUCTIONS NECESSARY TO SAFELY DESIGN, INSTALL, AND RELIABLY PERFORM THE MAINTENANCE AND RECHARGE SERVICE IN ACCORDANCE WITH THE MANUFACTURERS DESIGN, INSTALLATION, AND MAINTENANCE MANUAL |
|
|
Term
| DEFINE TC- TRANSPORT CANADA |
|
Definition
| THE DEPARTMENT THAT HAS JURISDICTION OVER DESIGN AND TRANSPORTATION OF COMPRESSED GAS CYLINDERS AND CARTRIDGES IN CANADA |
|
|
Term
| WHAT DOES THE DEPARTMENT OF TRANSPORTATION (DOT) HAVE JURISDICTION IN ACCORDANCE WITH THE NFPA 17 |
|
Definition
| THE DEPARTMENT OF DOT HAS JURISDICTION OVER THE DESIGN AND TRANSPORTATION OF COMPRESSED GAS CYLINDERS AND CARTRIDGES IN THE UNITED STATES OF AMERICA |
|
|
Term
| ALL OPERATING DEVICES SHALL BE DESIGNED FOR THE SERVICE THEY WILL ENCOUNTER, SHALL NOT BE RENDERED INOPERATIVE OR SUSCEPTIBLE TO ACCIDENTAL OPERATION AND SHALL OPERATE IN AT LEAST WHAT TEMPERATURE RANGE FAHRENHEIT? |
|
Definition
| FROM 320 TO 1200 FAHRENHEIT |
|
|
Term
| WHAT SHALL BE MARKED ON OPERATING DEVICES CONCERNING TEMPERATURE ACCORDING TO THE NFPA 17 |
|
Definition
SHALL BE MARKED TO INDICATE THEIR LISTEM MINIMUM AND MAXIMUM TEMPERATURE LIMITATIONS
32-120 DEGREES |
|
|
Term
| WHAT FORCE MANUAL ACTUATORS SHALL NOT REQUIRE? |
|
Definition
| A FORCE OF MORE THAN 40LBS |
|
|
Term
| WHAT MOVEMENT MANUAL ACTUATORS SHALL NOT REQUIRE TO SECURE OPERATION? |
|
Definition
| SHALL NOT REQUIRE MOVEMENT OF MORE THAN 14 INCHES TO SECURE OPERATION |
|
|
Term
| THE INTERNAL PRESSURE USED FOR THE CALCULATION FOR PIPE AND FITTINGS SHALL NOT BE LESS THAN THE GREATER OF WHAT TWO VALUES |
|
Definition
- THE NORMAL CHARGING PRESSURE IN THE AGENT CONTAINER AT 700
- 80% OF THE MAXIMUM PRESSURE IN THE AGENT CONTAINER AT A MAXIMUM STORAGE TEMPERATURE OF NOT LESS THAN 130O
|
|
|
Term
| ACCORDING TO THE NFPA 17 CAN TYPES OF DRY CHEMICAL BE MIXED? |
|
Definition
|
|
Term
| CARBON DIOXIDE USED IN EXPELLANT GAS CARTRIDGES SHALL MEET WHAT 3 SPECIFICATIONS? |
|
Definition
- THE VAPOR PHASE SHALL NOT BE LESS THAN 99.5 % CARBON DIOXIDE
- THE WATER CONTENT OF THE LIQUID PHASE SHALL NOT BE MORE THAN .01% BY WEIGHT (-300 F DEW POINT)
- NITROGEN USED AS AN EXPELLANT GAS SHALL BE STANDARD INDUSTRIAL GRADE WITH A DEW POINT OF -600F
|
|
|
Term
| STORAGE CONTAINERS DESIGN PRESSURE SHALL BE SUITABLE FOR THE MAXIMUM PRESSURE DEVELOPED AT WHAT ___TEMERATURE OR AT WHAT ____CONTROLLED TEMPERATURE LIMIT? |
|
Definition
| DEVELOPED AT 1300F OR AT THE MAXIMUM CONTROLLED TEMPERATURE LIMIT |
|
|
Term
| ALL EXTINGUISHING AGENT STORAGE CONTAINERS SHALL BE EXAMINED TO ENSURE THEY ARE _____ SECURELY TO THEIR _____ ______? |
|
Definition
| THEY ARE FASTENED SECURELY TO THEIR MOUNTING BRACKETS |
|
|
Term
| WHAT 7 TYPES OF HAZARDS AND EQUIPMENT SHALL BE PROTECTED USING DRY CHEMICAL EXTINGUISHING SYSTEMS? |
|
Definition
- FLAMMABLE OR COMBUSTIBLE LIQUIDS
- FLAMMABLE OR COMBUSTIBLE GASES
- COMBUSTIBLE SOLIDS INCLUDING PLASTICS
- ELECTRICAL HAZARDS SUCH AS OIL-FILLED TRANSFORMERS OR CIRCUIT BREAKERS
- TEXTILE OPERATIONS SUBJECT TO FLASH SURFACE FIRES
- ORDINARY COMBUSTIBLES SUCH AS WOOD, PAPER, AND CLOTH
- RESTAURANT AND COMMERCIAL HOODS, DUCTS, AND ASSOCIATED COOKING APPLIANCE HAZARDS SUCH AS DEEP FAT FRYERS
|
|
|
Term
| WHAT 3 LIMITATIONS SHALL DRY CHEMICAL EXTINGUISHING SYSTEMS NOT BE CONSIDERED SATISFACTORY PROTECTION FOR? |
|
Definition
- CHEMICALS CONTAINING THEIR OWN OXYGEN SUPPLY SUCH AS CELLULOSE NITRATE
- COMBUSTIBLE METALS SUCH AS SODIUM, POTASSIUM, MAGNESIUM, TITANIUM, AND ZIRCONIUM
- DEEP SEATED OR BURROWING FIRES IN ORDINARY COMBUSTIBLES WHERE DRY CHEMICAL CANNOT REACH THE POINT OF COMBUSTION
|
|
|
Term
| WHAT ARE EXAMPLES OF COMBUSTIBLE METALS LISTED IN THE NFPA 17? |
|
Definition
- SODIUM
- POTASSIUM
- MAGNESIUM
- TITANIUM
- ZIRCONIUM
|
|
|
Term
| ]ACCORDING TO THE NFPA 17, WHERE THERE ARE 2 OR MORE SYSTEMS USED TO PROTECT A COMMON HAZARD HOW SHOULD THEY BE ARRANGED? |
|
Definition
| SHALL BE ARRANGED FOR SIMULTANEOUS OPERATION |
|
|
Term
| WHEN THERE ARE MULTIPLE SYSTEMS PROTECTING A COMMON HAZARD, WHAT SHALL OCCUR WITH OPERATION OF A SINGLE ACTUATOR? |
|
Definition
| OPERATION OF A SINGLE ACTUATOR SHALL CAUSE ALL SYSTEMS TO OPERATE |
|
|
Term
| ACCORDING TO THE NFPA 17 WHAT 5 SAFETY ITEMS TO BE CONSIDERED SHALL INCLUDE, BUT NOT BE LIMITED TO? |
|
Definition
- PERSONNEL TRAINING
- WARNING SIGNS
- PREDISCHARGE ALARMS
- DISCHARGE ALARMS
- RESPIRATORY PROTECTION
|
|
|
Term
THE DRY CHEMICAL CONTAINER AND EXPELLANT GAS ASSEMBLIES UTILIZING NITROGEN SHALL BE LOCATED WHERE THE AMBIENT TEMPERATURE IS NORMALLY ___- TO ___ DEGREES FAHRENHEIT?
|
|
Definition
|
|
Term
| ASSEMBLIES UTILIZING CARBON DIOXIDE SHALL BE LOCATED WHERE THE AMBIENT TEMPERATURE IS NORMALLY ____ TO ___ DEGREES FAHRENHEIT? |
|
Definition
| IS NORMALLY 320 TO 1200 F |
|
|
Term
| PIPE THREAD COMPOUND OR TAPE SHALL OR SHALL NOT BE USED ACCORDING TO THE NFPA 17 STANDARDS? |
|
Definition
|
|
Term
| ACCORDING TO THE NFPA 17 WHEN CAN PIPE THREAD TAPE BE PERMITTED? |
|
Definition
| PIPE THREAD TAPE SHALL BE PERMITTED WHERE INSTALLED IN ACCORDANCE WITH THE MANUFACTURERS DESIGN, INSTALLATION, AND MAINTENANCE MANUAL. |
|
|
Term
| WHEN UNCLOSABLE OPENING EXCEED ____% WHAT PERCENT OF THE ENCLOSURE SURFACE AREA ,A LOCAL APPLICATION SHALL BE USED? |
|
Definition
| WHERE UNCLOSABLE OPENING EXCEED 15% OF THE TOTAL ENCLOSURE SURFACE AREA |
|
|
Term
| WHEN SHALL PRE ENGINEERED TOTAL FLOODING SYSTEMS BE PERMITTED TO PROTECT PERMANENT ENCLOSURES HAVING UNCLOSABLE OPENING GREATER THAN 15%? |
|
Definition
| wHEN PRE-ENGINEERED TOTAL FLOODING SYSTEMS ARE LISTEND FOR SUCH USE |
|
|
Term
| WHERE SIMULTANEOUS USE OF TWO OR MORE HOSE LINES IS POSSIBLE, HOW LONG AT AT WHAT FLOW RATES SHALL A SUFFICIENT QUANTITY OF DRY CHEMICAL BE AVAILABLE TO SUPPLY THE MAXIMUM NUMBER OF NOZZLES? |
|
Definition
| AT LEAST 30 SECONDS AND AT THE APPROPRIATE FLOW RATES |
|
|
Term
| ACCORDING TO THE NFPA 17 PRE-ENGINEERED DRY CHEMICAL SYSTEMS SHALL BE OF WHAT 4 TYPES? |
|
Definition
- LOCAL APPLICATION
- TOTAL FLOODING
- HAND HOSE LINE
- COMBINATION OF LOCAL APPLICATION AND TOTAL FLOODING
|
|
|
Term
| IN ACCORDANCE WITH THE EXTINGUISHING SYSTEM MANUFACTURERS LISTING WHERE SHALL A FUSIBLE LINK OR HEAT DETECTOR BE PROVIDED/PLACED? |
|
Definition
| A FUSIBLE LINK OR HEAT DETECTOR SHALL BE PROVIDED ABOVE EACH PROTECTED COOKING APPLIANCE |
|
|
Term
| FUSIBLE LINKS OR HEAT DETECTORS LOCATED AT OR WITH _____ INCHES INTO THE EXHAUST DUCT OPENING AND AVOE THE PROTECTED APPLIANCE SHALL BE _____ TO MEET THE REQUIREMENTS OF 9.3.2.2 |
|
Definition
12 INCHES
AND
SHALL BE PERMITTED TO MEET |
|
|
Term
| COMMON EXHAUST DUCTS SHALL BE PROTECTED BY ONE OF THE FOLLOWING 2 METHODS? |
|
Definition
- SIMULTANEOUS OPERATION OF ALL INDEPENDENT HOOD, DUCT, AND APPLIANCE PROTECTION SYSTEMS
- SIMULTANEOUS OPERATION OF HOOD, DUCT, AND APPLIANCE PROTECTION SYSTEM AND THE SYSTEM(S) PROTECTING THE ENTIRE COMMON EXHAUST DUCT
|
|
|
Term
| WHO SHALL BE RESPONSIBLE FOR THE PROTECTION OF A COMMON EXHAUST DUCT(S) SERVING HOODS LOCATED WITHIN THE TENANTS SPACE AND UP TO ___ ___ ___ _____TO THE BUILDING OWNERS COMMON EXHAUST DUCT |
|
Definition
THE TENANT SHALL BE RESPONSIBLE
AND UP TO THE POINT OF CONNECTION TO THE BUILDING OWNERS COMMON EXHAUST DUCT |
|
|
Term
| ACCORDING TO THE NFPA 17 THE TENANTS COMMON DUCT SHALL BE CONSIDERED A _____ DUCT TO THE BUILDING OWNER'S COMMON DUCT. |
|
Definition
|
|
Term
| UPON ACTUATION OF ANY COOKING EQUIPMENT FIRE-EXTINGUISHING SYSTEM, WHAT SHALL HAPPEN ACCORDING TO THE NFPA 17 9.3.5 SHUTOFF DEVICES |
|
Definition
| ALL SOURCES OF FUEL AND ELECTRIC POWER THAT PRODUCE HEAT TO ALL EQUIPMENT PROTECTED BY THE SYSTEM SHALL BE SHUT DOWN |
|
|
Term
| ACCORDING TO THE NFPA 17, SHALL STEAM SUPPLIED FROM AN EXTERNAL SOURCE REQUIRE SHUTDOWN? |
|
Definition
| SHALL NOT REQUIRE SHUTDOWN |
|
|
Term
| EXHAUST FANS AND DAMPERS SHALL OR SHALL NOT BE REQUIRED TO BE SHUT DOWN UPON SYSTEM ACTUATION? |
|
Definition
|
|
Term
| ACCORDING TO THE NFPA 17 9.3.5.4 SHUT OFF DEVICES SHALL REQUIRE _____ ______ PRIOR TO FUEL OR POWER BEING RESTORED. |
|
Definition
| SHUT OFF DEVICES SHALL REQUIRE MANUAL RESETTING |
|
|
Term
| WHERE ELECTRICAL POWER IS REQUIRED TO OPERATE THE FIXED AUTOMATIC FIRE- EXTINGUISHING SYSTEM, THE SYSTEM SHALL BE MONITORED BY? |
|
Definition
| SHALL BE MONITORED BY A SUPERVISORY ALARM AND PROVIDED WITH A RESERVE POWER SUPPLY |
|
|
Term
| SYSTEM DRAWING SHALL INCLUDE WHAT 9 ITEMS ACCORDING TO THE NFPA 17 |
|
Definition
- HOODS
- EXHAUST DUCTS
- APPLIANCES
- INTERFACE OF THE FIRE-EXTINGUISHING SYSTEM DETECTORS
- PIPING
- NOZZLES
- FUEL SHUTOFF DEVICES
- AGENT STORAGE CONTAINERS
- MANUAL ACTUATION DEVICE(S)
|
|
|
Term
| EACH HAZARD PROTECTED BY TWO OR MORE SYSTEMS SHALL HAVE THESE SYSTEMS CONNECTED FOR_____ ______? |
|
Definition
| FOR SIMULTANEOUS OPERATION |
|
|
Term
| UPON SYSTEM ACTUATION, EQUIPMENT SHALL BE PROVIDED TO SHUT DOWN WHAT AND HOW? |
|
Definition
| TO SHUT DOWN ALL VEHICLE FUEL DISPENSER SIMULTANEOUSLY |
|
|
Term
IF THE SYSTEM IS PROVIDED WITH A DISCHARGE DELAY DEVICE, BOTH ____ AND ____ ALARMS SHALL BE PROVIDED TO WARN OF THE IMPENDING SYSTEM DISCHARGE.
|
|
Definition
| AUDIBLE AND VISUAL ALARMS |
|
|
Term
| ACCORDING TO NFPA 17, DRY CHEMICAL HAND HOSE LINE SYSTEM SHALL BE PROVIDED WITH? |
|
Definition
- TURRETS
- SKID-MOUNTED HOSE REELS
- REMOTE HOSE REELS
- OR COMBINATIONS THEREOF
|
|
|
Term
| PRIOR TO TEST REQUIRED BY 10.4.3.1. (A TEST USING NITROGEN OR DRY AIR) WHAT SHALL THE PIPING BE PHYSICALLY CHECKED FOR? |
|
Definition
| SHALL PHYSICALLY CHECKED FOR TIGHTNESS |
|
|
Term
| ACCORDING TO NFPA SHALL PIPING BE HYDROSTATICALLY TESTED? |
|
Definition
|
|
Term
| WHAT DEW POINT AND WHAT STANDARD INDUSTRIAL GRADE EXPELLANT SHALL EXPELLANT GAS FOR STORED PRESSURE CYLINDERS BE AT AND CONTAIN? |
|
Definition
| DEW POINT OF -600F OR LOWER AND SHALL BE STANDARD INDUSTRIAL GRADE NITROGEN |
|
|
Term
| ACCORDING TO THE NFPA 17 THE OWNERS INSPECTION MUST RETAIN WHAT RECORDS UNTILS THE NEXT SEMI-ANNUAL MAINTENANCE? |
|
Definition
| THE MONTHLY DATE THE INSPECTION IS PERFORMED AND THE INITIALS OF THE PERSON PERFORMING THE INSPECTION SHALL BE RECORDED AND SHALL BE RETAINED |
|
|
Term
| DRY CHEMICAL STORED IN PRESSURE SYSTEMS SHALL NOT REQUIRE WHAT? BUT SHALL BE EXAMINED AT LEAST HOW OFTEN? |
|
Definition
SHALL NOT REQUIRE SEMI-ANNUAL EXAMINATION
SHALL BE EXAMINED AT LEAST EVERY 6 YEARS |
|
|
Term
| DRY CHEMICAL CONTAINERS THAT PASS THE APPLICABLE 6 YEAR REQUIREMENT SHALL HAVE THE MAINTENANCE INFORMATION RECORDED ON WHAT KIND OF LABEL AND WHAT SIZE LABEL? |
|
Definition
SHALL BE RECORDED ON A DURABLE WEATHERPROOF LABEL
THAT IS A MINIMIM SIZE OF 2 in. X 3 1/2 in. |
|
|
Term
| DRY CHEMICAL CONTAINERS THAT PASS THE APPLICABLE 6 YEAR REQUIREMENT SHALL INCLUDE WHAT INFORMATION? |
|
Definition
- MONTH AND YEAR THE MAINTENANCE WAS PERFORMED, INDICATED BY A PERFORATION SUCH AS DONE BY A HAND PUNCH
- NAME OR THE INITIALS OF THE PERSON PERFORMING THE MAINTENANCE AND THE NAME OF THE AGENCY PERFORMING THE MAINTENANCE
|
|
|
Term
| ACCORDING TO THE NFPA 19 EACH SYSTEM CONTAINER THAT HAS UNDERGONE MAINTENANCE THAT INCLUDES INTERNAL EXAMINATION OR HAS BEEN RECHARGED SHALL HAVE A __________ COLLAR LOCATED AROUND THE ______ OF THE CONTAINER |
|
Definition
SHALL HAVE A VERIFICATION-OF-SERVICE COLLAR
AROUND THE NECK OF THE CONTAINER |
|
|
Term
ACCORDING TO THE NFPA 17 THE COLLAR SHALL INCLUDE WHAT INFORMATION?
|
|
Definition
- MONTH AND YEAR THE SERVICE WAS PERFORMED, INDICATED BY A PERFORATION SUCH AS DONE BY A HAND PUNCH
- NAME OF THE AGENCY PERFORMING THE MAINTENANCE OR RECHARGE
|
|
|
Term
| HOW LONG SHALL THE OWNER OR OWNER'S REPRESENTATIVE RETAIN ALL MAINTENANCE REPORTS? |
|
Definition
| FOR A PERIOD OF 1 YEAR AFTER THE NEXT MAINTENANCE OF THAT TYPE REQUIRED BY THIS STANDARD |
|
|
Term
| HOW OFTEN SHALL FIXED TEMPERATURE SENSING ELEMENT OF THE FUSIBLE METAL ALLOY TYPE BE REPLACED? |
|
Definition
| SHALL BE REPLACED AT LEAST SEMIANNUALLY FROM THE DATE OF INSTALLATION. |
|
|
Term
| WHAT PARTS OF DRY CHEMICAL EXTINGUISHING SYSTEMS SHALL BE SUBJECTED TO A HYDROSTATIC PRESSURE TEST AT INTERVALS EXCEEDING 12 YEARS? |
|
Definition
- DRY CHEMICAL CONTAINERS
- AUXILIARY PRESSURE CONTAINERS
- HOSE ASSEMBLIES
|
|
|
Term
| WHAT 3 EXCEPTIONS ARE THERE CONCERNING HYDROSTATIC PRESSURE TEST FOR DRY CHEMICAL EXTINGUISHING SYSTEMS? |
|
Definition
- DRY CHEMICAL CONTAINERS HAVING AN AGENT CAPACITY EXCEEDING 150 LB
- AUXILIARY PRESSURE CONTAINERS NOT EXCEEDING 2 INCHES DIAMETER (OUTSIDE) AND LESS THAN 2 FEET
- AUXILIARY PRESSURE CONTAINERS BEARING THE DOT 3E MARKING
|
|
|
Term
| HOW MANY SECONDS SHALL THE PRESSURE IN A HYDROSTATIC TEST OF A CYLINDER BE MAINTAINED? |
|
Definition
A MINIMUM OF 30 SECONDS
*BUT NO LESS TIME THAT IS REQUIRED FOR COMPLETE EXPANSION OF THE CYLINDER AND TO COMPLETE THE VISUAL EXAMINATION |
|
|
Term
| ACCORDING TO NFPA 17 WHY DO EXHAUST FANS NOT NEED TO BE SHUT DOWN OR TO HAVE DAMPERS CLOSED UPON SYSTEM ACTUATION? |
|
Definition
| BECAUSE THE SYSTEMS HAVE BEEN TESTED UNDER BOTH ZERO AND HIGH-VELOCITY FLOW CONDITIONS. |
|
|
Term
ACCORDING TO THE NFPA 17A DISCHARGE NOZZLES SHALL BE OF WHAT MATERIALS?
|
|
Definition
- BRASS
- STAINLESS STEEL
- OR OTHER CORROSION-RESISTANT MATERIALS
|
|
|
Term
| HOW SHALL DISCHARGE NOZZLES TO BE PROTECTED AND AGAINST WHAT? |
|
Definition
| SHALL BE PROTECTED INSIDE AND OUT AGAINST CORROSION |
|
|
Term
| DISCHARGE NOZZLES SHALL BE ________ _______ FOR IDENTIFICATION. |
|
Definition
| SHALL BE PERMANENTLY MARKED |
|
|
Term
| ACCORDING TO THE NFPA 17A MANUAL ACTUATORS SHALL NOT REQUIRE A FORCE OF MORE THAN? |
|
Definition
| A FORCE OF MORE THAN 40LBS |
|
|
Term
| MANUAL ACTUATORS SHALL NOT REQUIRE MOVEMENT OF MORE THAN HOW MANY INCHES? |
|
Definition
|
|
Term
TRUE OR FALSE
ALL MANUAL ACTUATORS SHALL NOT BE PROVIDED WITH OPERATING INSTRUCTIONS |
|
Definition
|
|
Term
| ACCORDING TO THE NFPA 17A SOLID FUEL COOKING OPERATIONS SHALL OR SHALL NOT BE REQUIRED TO BE SHUT DOWN? |
|
Definition
| SHALL NOT BE REQUIRED TO SHUT DOWN |
|
|
Term
| ACCORDING TO THE NFPA 17A WHEN MANUAL ACTUATION IS USED FOR COOKING RELATED PROTECTION, THE DEVICE SHALL BE INSTALL NOR MORE THAN AND NO LESS THAN FROM THE FLOOR? |
|
Definition
| SHALL BE INSTALLED NO MORE THAN 48 INCHES AND NO LESS THAN 42 INCHES |
|
|
Term
| WHAT SHALL BE DESIGNED AND INSTALLED TO GIVE INDICATION OF TROUBLE WHERE SUPERVISION IS PROVIDED? |
|
Definition
- AUTOMATIC DETECTION SYSTEM
- ELECTRICAL ACTUATION CIRCUIT
- ELECTRICAL POWER SUPPLY
|
|
|
Term
| SYSTEMS PROTECTING TWO OR MORE HOODS OR PLENUMS, OR BOTH SHALL BE INSTALLED TO ENSURE THE SIMULTANEOUS OPERATION OF? |
|
Definition
| ALL SYSTEMS PROTECTING THE HOODS, PLENUMS, AND ASSOCIATED COOKING APPLIANCES LOCATED BELOW THE HOODS |
|
|
Term
| TO BE COMPLIANT WITH NFPA 17A HOW MANY FUSIBLE LINKS OR HEAT DETECTOR SHALL BE INSTALLED WITH IN EACH EXHAUST DUCT OPENING? |
|
Definition
| AT LEAST ONE AND IN ACCORDANCE WITH THE MANUFACTURERS LISTING |
|
|
Term
| WHAT ITEM SHALL BE PROVIDED ABOVE EACH PROTECTED COOKING APPLIANCE AND IN ACCORDANCE WITH THE EXTINGUISHING SYSTEM MANUFACTURERS DESIGN, INSTALLATION AND MAINTENANCE? |
|
Definition
| A FUSIBLE LINK OR HEAT DETECTOR |
|
|
Term
| FUSIBLE LINKS OR HEAT DETECTORS LOCATED AT OR WITHIN, HOW MANY INCHES, INTO THE EXHAUST DUCT OPENING AND ABOVE THE THE PROTECTED APPLIANCE SHALL BE PERMITTED TO MEET THE REQUIREMENT? |
|
Definition
| LOCATED AT OR WITHIN 12 INCHES |
|
|
Term
| THE NFPA 17A REQUIRES COMMON EXHAUST DUCTS TO BE PROTECTED BY ONE OF TWO METHODS. WHAT ARE THESE METHODS? |
|
Definition
- SIMULTANEOUS OPERATION OF ALL INDEPENDENT HOOD, DUCT, AND APPLIANCE PROTECTION SYSTEMS
- SIMULTANEOUS OPERATION OF ANY HOOD, DUCT, AND APPLIANCE PROTECTION SYSTEM AND THE SYSTEM(S) PROTECTING THE ENTIRE COMMON EXHAUST DUCT
|
|
|
Term
| WHAT SHALL BE LOCATED AT EACH BRANCH DUCT TO COMMON DUCT CONNECTION WHERE ELECTRICAL OPERATION OF THE COMMON DUCT FIRE EXTINGUISHING SYSTEM DOES NOT MEET THE REQUIREMENTS OF SUPERVISION? |
|
Definition
| A FUSIBLE LINK OR OTHER MECHANICALLY OPERATED HEAT DETECTION DEVICE FROM THE COMMON DUCT FIRE EXTINGUISHING SYSTEM |
|
|
Term
| WHAT IS THE NFPA 96 STANDARD FOR? |
|
Definition
| NFPA 96 IS STANDARD FOR VENTILATION CONTROL AND FIRE PROTECTION OF COMMERCIAL COOKING OPERATIONS |
|
|
Term
| WHERE A FUSIBLE LINK OR MECHANICALLY OPERATED HEAT DETECTOR IS LOCATED AT A BRANCH-TO-COMMON DUCT CONNECTION, WHAT SHALL BE INSTALLED? |
|
Definition
| AN ACCESS PANEL SHALL BE INSTALLED IN ACCORDANCE WITH NFPA 96 |
|
|
Term
| WHERE PLANS ARE TO BE REQUIRED THE NFPA 17A STATES INFORMATION SHALL BE SUBMITTED PERTAINING TO WHAT DEVICES AND EQUIPMENT? |
|
Definition
- THE LOCATION AND FUNCTION OF DETECTION DEVICES
- OPERATING DEVICES
- AUXILIARY EQUIPMENT
- ELECTRICAL CIRCUITRY
|
|
|
Term
| A TEST USING ____ OR ____ SHALL BE PERFORMED ON THE PIPING NETWORK AT A PRESSURE NOT TO EXCEED NORMAL OPERATING PRESSURE |
|
Definition
|
|
Term
TRUE OR FALSE
THE TEST USING NITROGEN OR DRY AIR SHALL VERIFY THAT THE NITROGEN OR DRY AIR HAS DISCHARGED OUT OF MOST OF THE NOZZLES IN THE SYSTEM |
|
Definition
FALSE
SHALL TEST THEAT NITROGEN OR DRY AIR HAS DISCHARGED OUT OF EACH NOZZLE IN THE SYSTEM |
|
|
Term
| WHEN PERFORMING A PIPING INTEGRITY TEST WHAT SHAL BE CHECKED PRIOR TO TESTING? |
|
Definition
| PIPING SHALL BE PHYSICALLY CHECKED FOR TIGHTNESS |
|
|
Term
| ACCORDING TO NFPA 17A, HEAT DETECTORS AND ALL ASSOCIATED WIRING THAT SHOW SIGNS OF ___ ____ SHALL BE TESTED IN ACCORDANCE WITH THE MANUFACTURERS INSTRUCTIONS AND ______ IF NECESSARY? |
|
Definition
SHOW SIGNS OF FIRE DAMAGE
AND REPLACED IF NECESSARY |
|
|
Term
| AFTER ANY DISCHARGE, WHAT SHALL BE PERFORMED IN ACCORDANCE WITH THE PROCEDURES DETAILED IN THE MANUFACTURER'S DESIGN, INSTALLATION AND MAINTENANCE MANUAL? |
|
Definition
| AFTER ANY DISCHARGE THE SYSTEM PIPING SHALL BE FLUSHED AND BLOWN OUT WITH DRY AIR OR NITROGEN IN ACCORDANCE WITH THE MANUFACTURER |
|
|
Term
| WHAT 2 PARTS OF WET CHEMICAL EXTINGUISHING SYSTEMS SHALL BE SUBJECTED TO A HYDROSTATIC PRESSURE TEST AT INTERVALS NOT EXCEEDING 12 YEARS? |
|
Definition
- WET CHEMICAL CONTAINERS
- AUXILIARY PRESSURE CONTAINERS
- HOSE ASSEMBLIES
|
|
|
Term
| WHAT ARE THE TWO EXCEPTIONS CONCERNING WET CHEMICAL EXTINGUISHING SYSTEMS WHICH ARE SUBJECT TO HYDROSTATIC PRESSURE TEST? |
|
Definition
- AUXILIARY PRESSURE CONTAINERS NOT EXCEEDING 2 INCHES OUTSIDE DIAMETER AND LESS THAN 2 FT IN LENGTH
- AUXILIARY PRESSURE CONTAINERS BEARING THE DOT 3E MARKING
|
|
|
Term
| WET CHEMICAL CONTAINERS, AUXILIARY PRESSURE CONTAINERS, AND HOSE ASSEMBLIES SHALL BE SUBJECTED TO A HYDROSTATIC TEST PRESSURE ______ TO THE MARKED FACTORY TEST PRESSURE OR THE TEST PRESSURE SPECIFIED WHERE? |
|
Definition
SHALL BE SUBJECT TO A HYDROSTATIC TEST PRESSURE EQUAL TO
TEST PRESSURE SPECIFIED IN THE MANUFACTURERS DESIGN, INSTALLATION, AND MAINTENANCE MANUAL |
|
|
Term
| PRIOR TO BEING REFILLED OR TRANSPORTED, IN ACCORDANCE WITH DOT OR TC REQUIREMENTS, CONTAINERS BEARING DOT OR TC MARKINSH SHALL? |
|
Definition
| SHALL BE RETESTED OR REPLACED IN ACCORDANCE WITH THE APPROPRIATE DOT OR TC REQUIREMENTS |
|
|
Term
| DOES THE DATE OF MANUFACTURE MARKED ON FUSIBLE METAL ALLOY TEMPERATURE SENSING ELEMENT LIMIT WHEN THEY CAN BE USED? |
|
Definition
| DOES NOT LIMIT WHEN THEY CAN BE USED |
|
|
Term
| WHAT IS THE INTENT OF 7.3.4 IN DETERMINING THE DIFFERENCE BETWEEN SHELF LIFE V. THE DATE OF THE MANUFACTURE MARKING ON FUSIBLE METAL ELEMENTS AND THE REPLACEMENT TEREOF? |
|
Definition
| THE INTENT OF 7.3.4 IS TO REQUIRE REPLACEMENT OF FUSIBLE METAL ALLOY TEMPERATURE SENSING ELEMENTS THAT HAVE BEEN INSTALLED FOR UP TO 6 MONTHS IN ENVIRONMENTS SUBJECTING THEM TO CONTAMINANT LOADING V AND UNLIMITED SHELF LIFE |
|
|
Term
| DOT OR TC MARKED CYLINDERS CAN OR CANNOT BE REQUIRED TO BE SUBJECTED TO MORE FREQUENT TESTING? |
|
Definition
|
|
Term
| IF A DOT OR TC MARKED CONTAINER IS INSTALLED IN A SYSTEM NOT UNDER THE JURISDICTION OF DOT OR TC ARE OR ARE NOT REQUIRED TO DO WHAT? |
|
Definition
| ARE NOT REQUIRED TO FOLLOW DOT OR TC REQUIREMENTS AS LONG AS THEY REMAIN IN OPERATION |
|
|
Term
| ACCORDING TO THE NFPA 17A, SYSTEMS FOR PROTECTION OF MOBILE EQUIPMENT, MANUAL ACTUATIONS SHOULD BE? |
|
Definition
| PERMITTED TO BE PROVIDED ONLY IF ACCEPTABLE TO THE AUTHORITY HAVING JURISDICTION |
|
|