Term
on projects where the interior designer is the primary design consultant, who is responsible for coordination |
|
Definition
|
|
Term
who is responsible for reviewing all the drawings are correct and ready for bidding |
|
Definition
|
|
Term
who is responsible for submitting the drawings to the building official or AHJ |
|
Definition
|
|
Term
who is responsible of gathering all the drawings from the consultants in order to have a complete drawing set |
|
Definition
|
|
Term
The project manual contains the |
|
Definition
|
|
Term
performance specifications |
|
Definition
tell what results the final construction assembly must achieve, but give the contract some choice in how they will be achieves |
|
|
Term
tell exactly what product or material the contractor must use by using brand name |
|
Definition
prescriptive specifications |
|
|
Term
public projcts usually require ______ specifications in order to encourage competitive bidding |
|
Definition
|
|
Term
what does a closed specification ensure? |
|
Definition
that only one particular product is used. no substitution |
|
|
Term
proprietary speacifications |
|
Definition
most restrictive specification b/c they call out a specific manufacturer's product - complete control |
|
|
Term
which specification does not allow for competitive bidding? |
|
Definition
propreitary specifications |
|
|
Term
|
Definition
also refered to as equal specification, calls out a proprietary material or product but allows the substitution of other products that the contractor thinks are equal to the one stated |
|
|
Term
what are the two variations of a base-bid specification that gives the designer more control? |
|
Definition
the first lists several approved manufacturers of a product (burden on designer) and the other is a "approved equal" which states that the one product or approved equal must be used. meaning contractor can present substitution but it needs to be reviewed by designer and approved before its incorporated into bid. |
|
|
Term
who has the resposiblity for fairly and accurately evaluating the proposed alternatives of the specs |
|
Definition
|
|
Term
descriptive specifications |
|
Definition
(open) specification giving written details for the material or product and teh workmanship required for its fabrication and installation. no mention of trade names |
|
|
Term
reference standard specification |
|
Definition
describes a material, product or process based on requirements set by an accepted authority or test method. a test requirement set by ASTM for example |
|
|
Term
pure performance specification |
|
Definition
setting the criteria and results required of the item being specified. what is expected as an end result from the product |
|
|
Term
which specification is usually used mostly for construction components |
|
Definition
pure performance specification |
|
|
Term
the two specifications most difficult to write are |
|
Definition
descriptive and pure performance specifications |
|
|
Term
what are master specifications? |
|
Definition
they are prewritten specifications that cover nearly all types of products, methods or installation and variable that relate to a specific product or construction activity |
|
|
Term
what is the difference between master specifications and guide specifications? |
|
Definition
guide specifications are not as complete. they simply assist the specifier. |
|
|
Term
what does BIFMA stand for |
|
Definition
Business & Institutional Furniture Manufacturer's Association |
|
|
Term
where would we find the standards for office furniture and general purpose office chairs |
|
Definition
|
|
Term
wehre would we find the standards for office furniture concerning "lateral files" |
|
Definition
|
|
Term
where would we find that standards for office furniture concerning "vertical files" |
|
Definition
|
|
Term
where would we find that standards for office furniture concerning "lounge chairs" |
|
Definition
|
|
Term
where would we find that standards for office furniture concerning "desk products" |
|
Definition
|
|
Term
where would we find that standards for office furniture concerning "panel systems" |
|
Definition
|
|
Term
where would we find that standards for office furniture concerning "STORAGE UNITS" |
|
Definition
|
|
Term
where would we find that standards for office furniture concerning "small office/ home office" |
|
Definition
|
|
Term
where would we find the guidelines for SDT visual display terminal) used in office work spaces |
|
Definition
|
|
Term
two of the most common steel structural system are ______ and ______ |
|
Definition
the beam and girder system and the open-web steel joist system |
|
|
Term
There are many variations of concrete structural systems, but two are primary: |
|
Definition
|
|
Term
name the three types of major loads |
|
Definition
gravity, dynamic and lateral |
|
|
Term
|
Definition
|
|
Term
|
Definition
wind and earthquake loads |
|
|
Term
|
Definition
When a force is only applied suddenly it is impact load when load applied suddenly or changes rapidlyled dynamic load examples: cars in garages elevators traveling in a shaft helicopter landing on roof |
|
|
Term
what do slip joints do in commerical construction |
|
Definition
perimater walls of the building as well as interior partitions that attached to the structural floors should be designed with slip joints to allow the building to move slightly without adding additional pressure to the partition |
|
|
Term
what is used for large movements in the structure |
|
Definition
|
|
Term
|
Definition
a 2" to 4" round hold drilled thorugh the concrete with a special hollow drill bit |
|
|
Term
which cast-in-place concrete structural system is easiest to penetrate with small core drilling for pipes and poke-through electrical outlets? and why? |
|
Definition
beam and girder system and one-way pan joist system because there is less reinforcing in these systems - this is for small holes!!!! large holes its easier on the flat slab & flat plates but then you need additional structure support around opening |
|
|
Term
for larger openings which type of cast-in-place concrete floor is best? |
|
Definition
flat plated and flat slabs |
|
|
Term
which type of cast-in-place concrete can be cut for a staircase opening even though very expensive and who should be contacted? |
|
Definition
waffle and an engineer and will require additional support |
|
|
Term
One of the most common types of floor and roof construction is |
|
Definition
concrete on metal decking |
|
|
Term
what material does most residential construction and small commercial costruction use |
|
Definition
|
|
Term
the space between joist is spanned with _______ or ________ on which underlayment is placed in preparation for finish flooring |
|
Definition
|
|
Term
|
Definition
small repetitive elements that compose loadbearing and nonloadbearing walls most common size 2x4 16 on center for residential - wood 24 on center for commercial - metal |
|
|
Term
|
Definition
horizontal repetitive members used to support the floor |
|
|
Term
when openings for doors and small windows are required, the are framed at the top with __________ |
|
Definition
|
|
Term
|
Definition
used for two-story construction |
|
|
Term
glued-laminated wood members (glulams) |
|
Definition
built from a number of lumber pieces, glued together and finished under factory conditions for use as beams, columns, purlins and other structural elements. used where larger wood members are required & unusual structure shapes |
|
|
Term
|
Definition
high rise buildings, the wall generally used as part of the structure of the buildng and surrounding the common buidling services such as elevator & stairway shafts, toilet rooms, mechanical rooms and such |
|
|
Term
|
Definition
stud above a door opening or below a windowsill |
|
|
Term
|
Definition
light-gage sheets of steel that are ribbed, fluted or otherwise stiffened by shape for use in construcing a floor or roof |
|
|
Term
|
Definition
framing member that crosses and supports the end of joists, transferring the wieght of the joist to parallel joists. used to form openings in wood-framed floors |
|
|
Term
|
Definition
horizontal structural member over an opending that carries the wieght of the wall above it |
|
|
Term
|
Definition
piece of timber laid horizontally |
|
|
Term
|
Definition
the plywood or particleboard covering placed over exterior studding or rafters of a building that provide strength and a base for the application of wall or roof cladding |
|
|
Term
|
Definition
horizontal wood member that serves as a base for the studs in a stud partition |
|
|
Term
|
Definition
wood member in a floor or roof used to support a header |
|
|
Term
|
Definition
structural beam of steel having a shape whose cross sectin resembles the letter H. used for beams and columns because of their shape |
|
|
Term
define mixing boxes and where are they located |
|
Definition
adjusts the quantity or temperature of air going into a space from the main air supply line, reduces the velocity of air and attenuate noise. plenums |
|
|
Term
commercial construction uses _______ ________ which is a false floor of individual panels raised above the structural floor with pedestals |
|
Definition
|
|
Term
what runs through an access floor |
|
Definition
to run electrical, communication and computer wiring and some types of HVAC ductwork that serves individual workstations |
|
|
Term
|
Definition
consists of two runs of studs separted by several inches which is determined by the largest plumbing pipe or duct taht has to be concealed commonly used between back-to-back commerical toilet rooms where extensive plumbing work and toilet carriers are required |
|
|
Term
|
Definition
steel framework that is bolted to the floor inside a pipe chase and carries weight of wall-hung toilets |
|
|
Term
in commerical construction when the plenum is used as a return air space, building code prohibits |
|
Definition
use of combustible material such as wood, exposed wire within the space |
|
|
Term
in plenums ________ ________ ________ must be installed to limit the spread of fire and smoke horizontally. normally the extension of a fire-rated partition serves the purpose |
|
Definition
|
|
Term
plumbing consists of two major components: |
|
Definition
|
|
Term
traps are connected to the actual _____ _______ but they also have to be connected to ______ |
|
Definition
|
|
Term
|
Definition
pipes connected to drainage system at varoius locations, open to the outside air, and designed to serve two purposes 1-allow built-up sewage gases to escape 2-allow pressure in the system to equalize so not to drain the water out of the traps |
|
|
Term
|
Definition
|
|
Term
|
Definition
carries wastes other than human wastes |
|
|
Term
|
Definition
|
|
Term
|
Definition
only used in multi-story buildings and used only for venting. also extends through the roof or connects to the stack vent |
|
|
Term
____ ___ is one of the most important aspects of fire protection |
|
Definition
|
|
Term
|
Definition
is a change in elevation having two or more risers |
|
|
Term
by code the landing should be |
|
Definition
A landing must be as wide as the stairway step |
|
|
Term
|
Definition
is that portion of the egress achieving a change in elevation |
|
|
Term
|
Definition
device placed in a duct that is designed to automatically close when subjected to a certain increase in temperature or with detection of smoke. ***used when fire wall has been penetrated*** |
|
|
Term
|
Definition
enclosed vertical area for pipes or ductwork that runs from one floor to another |
|
|
Term
|
Definition
is a series of two or more risers between one floor or landing and the next |
|
|
Term
|
Definition
unit or device taht radiates heat form water to the surrounding air, usually through closely spaced find. usually placed again a wall under a window |
|
|
Term
what does VCP stand for? and does it do? |
|
Definition
visual comfort probability evaluate direct glare |
|
|
Term
|
Definition
materials that will ignite and burn, either as a flame or glow |
|
|
Term
|
Definition
an assembly of fire door, fire window, or fire damper, including all required anchorage, frames, sills, and hardware |
|
|
Term
|
Definition
new term meaning a fire-resistive vertical or horizontal assembly of materials designed to restrict the spread of fire in which openings are protected |
|
|
Term
|
Definition
a fire-resistive component used to separate dwelling units in R-2 and R-1 construction and tenant spaces in covered mall buildings 1-hour rating partition 45-minute door |
|
|
Term
what are fire partitions required to have |
|
Definition
1-hour fire protection-rated partition & 45-minute door |
|
|
Term
|
Definition
peroid of time an opening assembly (door or window) can confine a fire or maintain its integrity |
|
|
Term
|
Definition
NFPA 252 (aka UL 10B ) NFPA 80 UL 1784 |
|
|
Term
|
Definition
NFPA 257 (ASSEMBLY) ASTEM E163 (ENDURANCE) NFPA 80 (INSTALLATION) |
|
|
Term
|
Definition
property of a material or assembly to withstand or resist the spread of fire or give protection from it |
|
|
Term
difference between fire protection ratings and fire-resistance rating |
|
Definition
fire-protection involves opening assemblies |
|
|
Term
|
Definition
should not be used as a noun. it is an adjective, only used as a modifier with defined compound terms such as fire-retarded treated wood |
|
|
Term
|
Definition
ability to withstand flame impingement or give protection from it |
|
|
Term
|
Definition
numerical value assigned to a material tested in accordance to ASTM E84 |
|
|
Term
|
Definition
WYSENBECK - RESISTANCE TO ABRAISION WITH WOVEN FABRICS |
|
|
Term
|
Definition
TABER - MOSLY CARPETS, SAMPLE PLACED ON A PLATFORM THAT IS 4" IN DIAMETER & THE PLATFORM SPINS WITH TWO ROTATING WHEELS |
|
|
Term
|
Definition
MARTINDALE - FLAT FABRICS TESTS ABRASION RESISTANCE WITH FABRICS WITH FABRICS THAT HAVE A PILE DEPTH OF LESS THAN 0.08" |
|
|
Term
|
Definition
FADE-OMETER - TESTS COLOR FASTNESS UNDER LIGHT EXPOSURE, USING 6 DIFFERENT TEST OPTIONS |
|
|
Term
|
Definition
CROCKING - TEST IF THE FABRIC HAS RESISTANCE TO TRANSFER ITS COLOR IF RUBBED. TESTED WITH A WHITE CLOTH |
|
|
Term
|
Definition
BACTERIAL RESISTANCE TEST - TESTS BATRIOSTATIC ACTIVITY ON TEXTILE MATERIALS |
|
|
Term
|
Definition
TEARING STRENGTH TEST - DETERMINES TEARING RESISTANCE & LOAD NECESSSARY FOR IT TO TEAR |
|
|
Term
|
Definition
TEST FOR WINDOW TREATMENTS |
|
|
Term
|
Definition
ALL THREE DIMENSIONS ARE AT THE SAME SCALE. VIEW OF AN OJECT WHERE THE OBJECT IS TILTED IN RELATIONSHIP TO THE PICTURE PLAN |
|
|
Term
|
Definition
ONE PLANE OF AN OBJECT IS IN TRUE SHAPE WHILE THE THIRD DIMENSION IS DRAWN AS LINES FIXED TO THE TRUE PLANE |
|
|
Term
ADVANTAGE TO THE ISOMETRIC & AT WHAT ANGLE IS IT DRAWN |
|
Definition
ADVANTAGE IS QUICK, EASY & ALL THREE AXES ARE DRAWN TO SCALE 30 DEGREES |
|
|
Term
ADVANTAGE TO THE OBLIQUE & AT WHAT ANGLE IS IT DRAWN |
|
Definition
ADVANTAGE IS THAT AN EXISTING ORTHOGRAPHIC FLOOR PLAN CAN BE USED AS A STARTING POINT CAN BE TILTED AT ANY DEGREE (30,60, 45) AS LONG AS THE WALLS ARE 90 DEGREES TO EACH OTHER |
|
|
Term
WHICH DRAWING IS IN TRUE RELATIONSHIP WITH OTHER PIECES |
|
Definition
|
|
Term
|
Definition
MOST ACCURATE 2-D REPRESENTATION OF WHAT THE 3-D WORLD WILL/ DOES LOOK LIKE |
|
|
Term
|
Definition
(PP)IS AN IMAGINARY VERTICAL PLANE ON WHICH ALL POINTS OF THE OBJECT ARE PROJECTED TO CREATE THE 2-D IMAGE. USUALLY APPEARS AS A LINE ON THE DRAWING |
|
|
Term
TO CONSTRUCT A PERSPECTIVE DRAWING THE PLAN IS PLACED |
|
Definition
AT AN ANGLE ON THE TOP OF THE DRAWING BOARD |
|
|
Term
|
Definition
(SP) TWO LINES EXTENDED FROM THIS POINT ON THE DRAWINGS AND THEY DETERMINE THE VANISHING POINTS (LEFT AND RIGHT ON TWO POINT PERSPECTIVES) |
|
|
Term
|
Definition
ONLY LINE TO SCALE ON A PERSPECTIVE DRAWING. WHERE THE PICTURE PLANE TOUCHES THE PLAN DRAWING |
|
|
Term
|
Definition
DETAILED & ACCURATELY REPRESENT THE FURNITURE, DETAIL, COLORS & FINISHES USED FOR FINAL, FORMAL PRESENTATION TO CLIENT - MADE BY PROFESSIONAL MODEL BUILDER |
|
|
Term
|
Definition
(OR WORKING MODELS) TO AID DESIGNER TO UNDERSTANDING THE 3-D ASPECTS OF A SPACE |
|
|
Term
|
Definition
FULL-SIZE REPRESENTATION OF A PORTION OF THE DESIGN. GOOD WAY TO CONVEY TO THE CLIENT WHAT THE FINAL PRODUCT WITH LOOK LIKE |
|
|
Term
|
Definition
CLOSE TO EACH OTHER ON THE WHEEL |
|
|
Term
|
Definition
OPPOSITE SIDE OF THE WHEEL |
|
|
Term
|
Definition
|
|
Term
TONE IS CREATED BY ADDING |
|
Definition
|
|
Term
SHADE IS CREATED BY ADDING |
|
Definition
|
|
Term
MAIN PURPOSE OF AN ARBITRATION CLAUSE IS |
|
Definition
TO SETTLE A SERIUS DISCPUTE OUT OF COURT |
|
|
Term
RADIANT PANEL TEST & WHAT DOES IT TEST |
|
Definition
NFPA 253 (ASTM E 648) FLOOR COVERINGS IN CORRIDORS CLASS I - INSTITUTIONAL OCCUPANCIES CLASS II - RESIDENTIAL OCCUPANCIES |
|
|
Term
|
Definition
|
|
Term
|
Definition
ASTM D 2859 TEST CARPETS & RUGS |
|
|
Term
|
Definition
WALL & FLOOR/ CEILING ASSEMBLY TEST FIRE RATING OF WALLS, STRUCTURE & FLOOR ASSEMBLIES |
|
|
Term
FLAME-SPREAD RATING ON FINISHES TEST TAHT ALSO RATES CEILINGS |
|
Definition
STEINER TUNNEL ASTM E84 TEST FLAME SPREAD |
|
|
Term
FIRE TESTS OF DOOR ASSEMBLIES |
|
Definition
|
|
Term
|
Definition
TEST FOR WINDOW & GLASS BLOCK ASSEMBLY |
|
|
Term
|
Definition
FIRE TESTS FOR WINDOW ASSEMBLIES |
|
|
Term
NAME THREE TESTS FOR WINDOWS |
|
Definition
ASTM E163 (ENDURANCE) NFPA 257 (ASSEMBLY) NFPA 80 (INSTALLATION) |
|
|
Term
NAME FOUR TESTS FOR DOORS |
|
Definition
NFPA 252 (UL 10B & C) UBC 7-2 NFPA 80 UL 1784 |
|
|
Term
|
Definition
WALL FINISHES TEST METHOD FOR SPECIFIC OPTICAL DENSITY OF SMOKE GENERATED BY SOLID MATERIAL MEASURES HOW MUCH SMOKE GIVEN OFF BY A FLAMING OR SMOLDERING MATERIAL OR FINISH |
|
|
Term
ASTM E662 ALSO KNOWN AS & WHAT IS UNDER CODE |
|
Definition
NFPA 258 MATERIALS NEED TO HAVE A SMOKE DENSITY OF 450 OR LESS |
|
|
Term
WHICH OF THE CLASSES (A, B, OR C) IS MOST FIRE RESISTANT |
|
Definition
|
|
Term
NAME THE FIRE RATINGS PER CLASS |
|
Definition
CLASS A 0-25 CLASS B 26-75 CLASS C 75-200 |
|
|
Term
|
Definition
ROOM CORNER TEST TESTS THE CONTRIBUTIONS OF INTERIOR WALL & CEILINGS COVERINGS TO FIRE GROWTH |
|
|
Term
IN ADDITION TO THE STEINER TEST WHAT ELSE IS REQUIRED |
|
Definition
NFPA 265 ROOM CORNER TEST |
|
|
Term
WHAT TWO THINGS DOES THE ROOM CORNER TEST TEST FOR |
|
Definition
NFPA 265 TESTS FOR: WHETHER FLAME DOES NOT SPREAD TO THE CEILNG & WHETHER OTHER CONDITIONS ARE MET DURING EXPOSURE OF 150Kw |
|
|
Term
ASIDE FROM NPFA 265 WHAT OTHER TEST TESTS THE CONTRIBUTION OF MATERIALS TO A FLAME |
|
Definition
NFPA 286 TEST MATERIALS THAT DO NOT STAY IN PLACE DURING TESTING |
|
|
Term
LIST THE ORDER OF THE CONSTRUCTION DRAWINGS |
|
Definition
title page index page floor plans reflective ceiling elevations details mechanical drawings electrical drawings (HVAC & plumbing) fire protection drawings |
|
|
Term
an acknowledgement contains |
|
Definition
estimated ship date, designer's po number, quanity, repeats item on po, cost & how it will be shipped |
|
|
Term
client is most typically involved with procurement of furniture through |
|
Definition
sales agreement - which must be signed by client |
|
|
Term
as the merchandise is shipped, carrier transports a ____ ___ _____ that lists contents of shipment |
|
Definition
|
|
Term
|
Definition
detiled list of the nubmer and description of items in teh shipment, will be sealed in an envelope attached to one of the items shipped |
|
|
Term
WHICH STEEL STRUCTURAL SYSTEM IS MOST COMMON FOR HIGH RISE BUILDINGS |
|
Definition
|
|
Term
WHAT STRUCTURAL SYSTEM IS MOST COMMON FOR LOW RISE, ONE STORY BUILDINGS |
|
Definition
OPEN WEB STEEL JOIST SYSTEM |
|
|
Term
PRECAST CONCRETE SHOULD NEVER BE PENETRATED IN WHAT CONDITIONS |
|
Definition
WHEN THE SLAB IS POST-TENSIONED - MEANING THAT THE STEEL CABLES WITHIN THE CONCRETE ARE RIGHTENED AFTER THE CONCRETE SETS, CREATING EXTRA COMPRESSION FORCES IN THE BEAM OR SLAB |
|
|
Term
NAME THE TWO POPULAR FORMS OF PRECAST CONSTRUCTION |
|
Definition
SINGLE AND DOUBLE-TEE MEMBERS DOUBLE-TEES ARE POPULAR IN PARKING GARAGES, INDUSTIRAL BUILDINGS AND ONE-TWO STORY BLDGS |
|
|
Term
SPACING BETWEEN THE BEAM AND GIRDER SYSTEMS RANGE FROM |
|
Definition
|
|
Term
CONCRETE JOISTS SYSTEMS ARE DIFFICULT TO DRILL HOLES BECAUSE |
|
Definition
THEY ARE SO CLOSE TOGETHER THAT IT MAKES IT DIFFICULT TO DRILL HOLES FOR CONDUITS AND SMALL PIPES |
|
|
Term
CONCRETE JOIST SYSTEMS ARE SPACED _____ APART AND RUN IN _____ DIRECTION |
|
Definition
|
|
Term
FLAT PLATE CONSTRUCTION IS DESIGNED FOR WHAT & ARE MOST USED IN WHAT SITUATIONS |
|
Definition
DESGNED AND REINFORCED TO TRANSFER LOADS DIRECTLY TO THE COLUMNS (CANNOT EXCEED 25 FT OF SPACING) & ARE COMMONLY USED WHERE FLOOR TO FLOOR HEIGHT MUST BE KEPT TO A MINIMUM |
|
|
Term
|
Definition
SIMILAR TO FLAT PLATE BUT THE DROP PANELS ARE USED TO INCREASE STRENGTH |
|
|
Term
|
Definition
PROVIDE SUPPORT FOR HEAVIER LOADS AT SLIGHTLY LONGER SPANS THAN FLAT SLABS |
|
|
Term
WHICH STURCTURAL SYSTEM IS USUALLY LEFT EXPOSED WITH LIGHT SYSTEM INTEGRATED INTO IT |
|
Definition
|
|
Term
NAME THREE TYPES OF PRECAST CONCRETE |
|
Definition
SINGLE-TEE DOUBLE-TEE HOLLOW CORE |
|
|
Term
|
Definition
|
|
Term
|
Definition
LIVE LOADS: PEOPLE & FURNITURE DEAD LOADS: WEIGHT OF STRUCTURE ITSELF (COLMNS, FLOOR, BEAMS, WALLS, MECHANICAL EQUIPMENTS) |
|
|
Term
WHERE ARE LOADBEARING WALLS RARELY USED IN COMMERCIAL OR RESIDENTIAL? |
|
Definition
IN COMMERCIAL CONSTRUCTION. MOST STRUCTURES ARE SOME FROM OF COLUMNS & BEAM SYSTEM WITH NONLOADING INFILL |
|
|
Term
NAME THREE MAJOR LOAD TYPES |
|
Definition
|
|
Term
IMPACT LOAD VS DYNAMIC LOAD |
|
Definition
IMPACT - FORCE IS ONLY APPLIED SUDDENLY DYNAMIC - FORCE IS APPLIED SUDDENLY AND CHANGES RAPIDLY (CARS IN GARAGES, ELEVATORS TRAVELING IN SHAFTS & HELICOPTER LANDING ON BUILDING ROOF) |
|
|
Term
WHAT IS USED IN COMMERCIAL CONTRACTUION THAT ATTACHES TO THE STRUCTURAL FLOOR ABOVE & PERIMETER OF BULDING TO ALLOW BUIDLING TO MOVE SLIGHTLY WITHOUT PUTTING PRESSURE ON PARTITIONS |
|
Definition
|
|
Term
MOST COMMON TYPE OF FLOOR AND ROOF CONSTRUCTION IS |
|
Definition
CONCRETE ON METAL DECKING |
|
|
Term
RESIDENTIAL CONSTRUCTION LOAD BEARING WALLS ARE TYPICALLED MADE WITH STUDS. WHAT IS THE MOST COMMON STUD AND WHAT IS THE SPACING ON CENTER |
|
Definition
|
|
Term
WHAT ARE JOISTS & WHAT DETERMINES THEIR DEPTH |
|
Definition
HORIZONTAL REPETITIVE MEMBERS USED TO SUPPORT THE FLOOR. NOMINAL 2" THICK WOOD DISTANCE THE AREA IS REQUIRED TO SPAN DETERMINES THEIR DEPTH |
|
|
Term
LARGE OPENINGS REQUIRE THE USE OF |
|
Definition
LAMINATE VENEER LUMBER (LVL), GLUED LAMINATED BEAMS OR SMALL STEEL BEAMS ARE USED INSTEAD OF HEADERS |
|
|
Term
DESIGNER DESIGN ________ ________ TO ACCOMODATE FOR SEISMIC EVENTS |
|
Definition
|
|
Term
DESIGNER DESIGN ________ ________ TO ACCOMODATE FOR FLOOR DEFLECTIONS |
|
Definition
|
|
Term
DESIGNER DESIGN ________ ________ TO ACCOMODATE FOR WIND SWAY |
|
Definition
|
|
Term
COMMERCIAL BUILDINGS HAVE SEVERAL VARITIONS OF HVAC SYSTEMS, NAME THEM |
|
Definition
VARIABLE AIR VOLUME (VAV) HIGH-VELOCITY DUAL DUCT CONSTANT VOLUME WITH REHEAT MULTI-ZONE SYSTEMS |
|
|
Term
REGISTERS ARE CONNECTED TO THE ____ ____ _______ AND CAN BE ADJUSTED TO CONTROL THE _______ OF AIR FLOW AND VOLUME |
|
Definition
SUPPLY AIR DUCTWORK DIRECTION |
|
|
Term
IF FIRE-RATED PARTITIONS EXEND ABOVE THE SUSPENDED CEILING, THEN WHAT MUST BE PROVIDED |
|
Definition
SUPPLY AIR DUCTS AND OPENINGS FOR RETURN AIR MUST BE PROVIDED AND AT THOSE OPENINGS FIRE DAMPERS ARE REQUIRED |
|
|
Term
WHEN ARE FIRE DAMPERS REQUIRED |
|
Definition
WHEN THE FIRE-RATED WALL IS PENETRATED |
|
|
Term
|
Definition
DEVICE PLACED IN A DUCT THAT IS DESIGNED TO AUTOMATICALLY CLOSE WHEN SUBJECTED TWO A CERTAIN INCREASE IN TEMPERATURE OR DETECTION OF SMOKE |
|
|
Term
CONVECTORS ARE USUALLY PLACED |
|
Definition
AGAINST A WALL UNDER A WINDOW |
|
|
Term
IN RESIDENTIAL CONSTRUCTION WHERE DO SMALL DUCTS AND PLUMBING PIPES TYPICALLY RUN |
|
Definition
WITHIN THE WALLS AND FLOOR JOISTS |
|
|
Term
IN COMMERCIAL CONSTRUCTION WHERE DO HORIZONTAL DUCTS AND VERTICAL DUCTS TYPICALLY RUN |
|
Definition
HORIZONTAL DUCTS IN THE PLENUM VERTICAL DUCTS RUN WITHIN THEIR OWN CHASES |
|
|
Term
BEFORE LOCATING LIGHT FIXTURES & OTHER RECESSED CEILING ITEMS WHAT THREE ITEMS SHOULD BE VERIFIED AND WHERE CAN THEY BE FOUND |
|
Definition
DUCTWORK, MIXING BOXES, AND PIPING FOUND IN THE HVAC PLAN |
|
|
Term
WHERE ARE CHASE WALLS COMMONLY USED |
|
Definition
BETWEEN BACK TO BACK COMMERICAL TOILET ROOMS |
|
|
Term
UNDER WHAT CONDITIONS MAY WIRES BE IN THE PLENUM |
|
Definition
TELEPHONE & COMMUNICATION WIRING ARE PLENUM-RATED (TEFLON COATED) |
|
|
Term
FIRE-RATED DIVIDERS MUST BE INSTALLED IN THE PLENUM TO ........ |
|
Definition
LIMIT SPREAD OF FIRE AND SMOKE HORIZONTALLY |
|
|
Term
THERMOSTATS LOCATIONS ARE NORMALLY DETERMINED BY |
|
Definition
|
|
Term
THERMOSTATS ARE LOCATED ____ ABOVE FLOOR FINISH, BUT ____ IS ADA |
|
Definition
|
|
Term
IN COMMERICAL CONSTRUCTION WINDOW COVERINGS SHOULD BE VERIFIED WITH WHOM AND WHY |
|
Definition
ARCHITECT OR MECHANICAL ENGINEER TO AVOID EXCESSIVE HEAT BUILD-UP WHICH MAY CAUSE GLASS TO CRACK OR BREAK |
|
|
Term
WHAT IS THE MINIMUM DISTANCE THAT THERE SHOULD BE BETWEEN THE GLASS WINDOW AND WINDOW TREATMENT IN A COMMERICIAL CONSTRUCTION |
|
Definition
|
|
Term
WHEN ARE SLOT AIR DIFFUSERS USUALLY USED |
|
Definition
USED WHEN THE APPEARANCE OF THE AIR DISTRIBUTION DEVICE NEEDS TO BE MINIMIZED OR WHEN THE AVAILABLE SPACE DOES NOT ALLOW A SQUARE DIFFUSER SLOT AIR DIFFUSERS ARE 3-8' WIDE EXAMPLE: USUALLY USED WITH GYPSUM WALLBOARD CLG'S |
|
|
Term
LAY-IN AIR DIFFUSERS ARE COMMONLY USED IN |
|
Definition
SUSPENDED CEILINGS RANGE FROM 1'-2' TYPICALLY |
|
|
Term
IN RELATIONS TO DUCT SIZES WHAT DOES THE FIRST NUMBER INDICATE AND WHAT DOES THE SECOND NUMBER INDICATE. EXAMPLE WHAT DOES 18X12 MEAN? |
|
Definition
FIRST NUMBER IS THE WIDTH SECOND NUMBER IS THE HEIGHT 18" WIDE BY 12" HIGH |
|
|
Term
NONMETALLIC SHEATHED CABLES (NM) ARE CONDUTORS THAT SUPPLY POWER & USED |
|
Definition
IN WOOD STUD RESIDENTIAL BUILDINGS NOT MORE THAN 3 FLOORS |
|
|
Term
FLEXIBLE METAL-CLAD OR ALSO CALLED ______ ARE CONDUCTORS THAT ARE USED |
|
Definition
ARMORED CABLE (AC) OR BY THEIR TRADE NAME BX (OR FLEX) REMOLDING WORK |
|
|
Term
OUTLETS MUST BE SPREAD NO MORE THAN |
|
Definition
|
|
Term
TELEPHONE & COMMUNICATION DEVICES ARE USUALLY SHOWN IN WHAT PLAN |
|
Definition
ELECTRICAL PLAN ALONG WITH ALL THE OUTLETS |
|
|
Term
WHO IS RESPONSIBLE FOR SHOWING LOCATIONS OF: TELEPHONES, COMMUNICATIONS DEVICES, SPEAKERS, BUZZERS, COMPUTER TERMINALS? |
|
Definition
|
|
Term
WHO IS RESPONSIBLE FOR ACTUAL CIRCUITING, DETERMINING WIRE SIZES & CONNECTIONS |
|
Definition
|
|
Term
INTERIOR DESIGN LOCATES THE ELECTRICAL, TELEPHONE & COMMUNICATION OULETS IN WHAT PLAN? IN RESIDENTIAL PROJECTS VS COMMERCIAL |
|
Definition
RESIDENTIAL - CONSTRUCTION FLOOR PLAN (OUTLETS CAN BE SHOWN ON FURNITURE PLAN TOO) COMMERCIAL - POWER PLAN |
|
|
Term
POWER PLANS ARE DEVELOPED BY THE _________ AND THEN GIVEN TO THE _________ TO DRAW THE ELECTRIAL PLAN |
|
Definition
INTERIOR DESIGNER ELECTRICAL ENGINEER |
|
|
Term
|
Definition
WIRE SIZE CONDUIT SIZE CIRCUITING PANEL BOXES |
|
|
Term
IN COMMERICAL BULDINGS, MOST OF THE PLUMBING IS CONCENTRATED IN ONE AREA AND LOCATED |
|
Definition
NEAR CORE AND IT SERVES TOILET ROOM, FOUNTAINS & SUCH |
|
|
Term
PLUMBING PLANS ARE DRAFTED BY |
|
Definition
|
|
Term
FIRE PROTECTION AND LIFE SAFETY BULDINGS ADDRESS THREE MAJOR OBJECTIVES |
|
Definition
PROTECTION OF LIFE PROTECTION OF PROPERTY RESTORATION & CONTINUED USE OF BUILDING AFTER FIRE |
|
|
Term
ASIDE FROM FIRES WHAT DOES FIRE PROTECTION ALSO PROTECT AGAINST |
|
Definition
TERRORIST ATTACKS, EARTHQUAKES, FLOODS, ETC |
|
|
Term
FIRE SUPPRESSION IS ACHIEVED THROUGH |
|
Definition
FIRE DETECTIONS & ALARMS FIRE SPRINKLERS STANDPIPES |
|
|
Term
WHAT DOES COMPARTMENTATION MEAN |
|
Definition
TO "CONTAIN" A FIRE AND LIMIT ITS SPREAD IN ORDER TO ALLOW ITS OCCUPANTS TO ESCAPE AND PROTECT PARTS OF THE BUIDLING |
|
|
Term
CODES REQUIRE FIRE SEPARATION IN WHICH AREAS |
|
Definition
BETWEEN DIFFERENT OCCUPANCIES, BETWEEN USE AREAS & EXITS BETWEEN PARTS OF THE BUILDING WHEN MAXIMUM ALLOWABLE AREA IS EXCEEDED |
|
|
Term
FIRE SEPARATION IS BOTH VERTICALLY AND HORIZONTALLY, ELABORATE |
|
Definition
VERTICALLY FLOOR-CEILNG ASSEMBLIES AND HORIZONTALLY WITH FIRE-RATED WALLS |
|
|
Term
WHO IS RESPONSIBLE FOR MAINTAINING COMPARTMENTATION IN DESIGNS OF CORRIDORS & OCCUPANCY SEPARATIONS |
|
Definition
|
|
Term
EXAMPLE OF SMALL SCALE COMPARTMENTATION |
|
Definition
FIRE STOPS IN STUD SPACES BEWTEEN FIRST AND SECOND FLOOR OF A HOUSE |
|
|
Term
MOST IMPORTANT ASPECTS OF FIRE PROTECTION |
|
Definition
|
|
Term
WHO IS RESPONSIBLE FOR DESIGNING THE BASIC ELEMENTS OF A SMOKE CONTROL SYSTEM? |
|
Definition
ARCHITECT & MECHANICAL ENGINEER |
|
|
Term
NAME THE THREE ELEMENTS TO SMOKE CONTROL |
|
Definition
CONTAINMENT, EXHAUST & DILUTION (LESSER DEGREE) |
|
|
Term
BULDING CODES STATES THE REQUIRED TYPES AND LOCATIONS OF FIRE DETECTORS ARE |
|
Definition
NEAR FIRE DOORS IN EXIT CORRIDORS IN INDIVIDUAL HOTEL ROOMS IN BEDROOMS IN PUBLIC ASSEMBLIES MAIN SUPPLY AND RETURN AIR DUCTS |
|
|
Term
|
Definition
RESPONDS TO IONIZED RATHER THAN TO SMOKE CONSIDERED EARLY WARNING |
|
|
Term
|
Definition
RESPONDS TO SMOKE WHICH OBSCURES LIGHT |
|
|
Term
RISE OF TEMPERATURE DETECTORS |
|
Definition
DETECT WHEN TEMPERATURE RISES, NOT SO GOOD BECAUSE FLAMES MUST BE PRESENT IN ORDER TO RISE TEMPERATURE |
|
|
Term
|
Definition
RESPONDS TO ULTRA VIOLET RAYS GIVEN OFF BY FLAMES, DO NOT GIVE ANY EARLY WARNING |
|
|
Term
FIRE DETECTORS CAN BE WIRED TO |
|
Definition
AUDIBLE AND VISUAL ALARMS |
|
|
Term
ASIDE FROM AUDIBLE AND VISUAL ALARMS, DETECTORS ALSO ACTIVATE WHAT ELSE IN COMMERCIAL CONSTRUCTIONS |
|
Definition
FIRE DAMPERS, EXHAUST SYSTEMS, CLOSING OF FIRE DOORS, & OTHERS THAT ARE SIGNALED TO FIRE OFFICIALS |
|
|
Term
MOST COMMON SUPPRESSION SYSTEM |
|
Definition
|
|
Term
STANDPIPLES ARE PIPES THAT |
|
Definition
RUN THE HEIGHT OF THE BULIDNGS AND PROVIDE WATER OUTLETS AT EACH FLOOR TO WHICH FIRE FIGHTERS HOSES CAN BE CONNECTED TO |
|
|
Term
|
Definition
ON EACH FLOOR WITHIN THE STAIRWAY OR VESTIBLES (IN CASE OF PRESSURIZED ENCLOSURES) |
|
|
Term
MOST CODES REFER TO THE NFPA _____ WHICH CLASSIFIES RELATIVE FIRE HAZARDS INTO THREE GROUPS NAME THEM |
|
Definition
13 LIGHT, ORDINARY, EXTRA HAZARD |
|
|
Term
LIGHT HAZARD INCLUDES ......... AND THEY REQUIRE A SPINKLER HEAD FOR EACH |
|
Definition
RESIDENCIES, HOSPITALS, OFFICES, SCHOOLS, RESTURANTS 200 SQ FT OR 225 SQ FT 130SQ FT FOR WOOD JOISTS CEILINGS |
|
|
Term
FIRE EXTINGUISHERS HAVE FOUR CLASSIFICATIONS NAME THEM |
|
Definition
1. A- FIRE ORDINARY COMBUSTIBLES OF PAPER, WOOD & CLOTH. EXTINGUISHER CONTAINS WATER BASED SOLVENTS 2. B - FIRE INVOLVE FLAMMABLE LIQUIDS (GAS, PAINT) EXTINGUISHER CONTAINS SMOTHERING TYPES OF CHEMICALS (CO2) 3. C - FIRE INVOLVE ELECTRICAL EQUIPMENT. EXTINGUISHER CONTAINS NON-CONDUCTIVE AGENTS 4. D - FIRE INVOLVES COMBUSTIBLE METALS FOUGHT WITH COMBINATION EXTINGUISHERS |
|
|
Term
|
Definition
CONTAIN NO WATER BUT RATHER GAS (HALON) WHICH PUTS OUT FIRE USED IN AREAS WHERE WATER MAY DO MORE DAMAGE (EX: COMPUTER ROOM) |
|
|
Term
FOAM AS EXTINGUISHERS AGENT |
|
Definition
USED TO SMOOTHER FIRE (EXAMPLE: INDUSTRIAL PLANTS OR AIRCRAFT HANGARS) |
|
|
Term
|
Definition
ANOTHER TYPE OF EXTINGUISHING AGENT FOUND IN SELANTS, CUALKING, PAINT, ETC |
|
|
Term
REGARDING SECURITY: PHOTOELECTRIC BEAMS |
|
Definition
BEAMS THAT WARN OF INTRUSION BY SENDING A PULSED INFRARED BEAM ACROSS SPACE, IF BROKEN AN ALARM IS SENT |
|
|
Term
REGARDING SECURITY: INFRARED DETECTORS |
|
Definition
SENSE SOURCES OF INFRARED RADIATION, SUCH AS THE HUMAN BODY |
|
|
Term
REGARDING SECURITY: AUDIO DETECTOR |
|
Definition
THESE DETECTORS LISTEN FOR UNUSUAL SOUNDS |
|
|
Term
REGARDING SECURITY: ULTRASONIC DETECTORS |
|
Definition
THESE DETECTORS EMIT A VERY HIGH-FREQUENCY SOUND WAVE, WHEN INTRUDER INTERRUPTS WAVE, ALARM IS ACTIVATED |
|
|
Term
REGARDING SECURITY: MICROWAVE DETECTORS |
|
Definition
EMIT A FIELD OF MICROWAVE RADIATION AND SENSE INTERRUPTION IN THAT FIELD LIMITED IN INTERIOR CONSTRUCTION |
|
|
Term
DESCRIBE DIFFERENCE IN CAPACITY PROXIMITY DETECTORS, VIBRATION DETECTORS AND INFRARED MOTION DETECTORS |
|
Definition
CAPACITANCE PROXIMITY DETECTOR - SENSES WHEN METAL OBJECT IS TOUCHED VIBRATION DETECTORS SENSE DISTURBANCE IN OBJECT INFRARED MOTION DETECTORS DETERMINE IF SPACE AROUND OBJECT HAS BEEN DISTURBED |
|
|
Term
WHO IS RESPONSIBLE FOR DESIGNING & INSTALLTING SECURITY SYSTEMS & PROVIDING POWER TO THESE SYSTEMS IN ORDER FOR THEM TO OPERATE |
|
Definition
ELECTRICAL ENGINEER, SECURITY CONSULTANTS & EQUIPMENT VENDOR |
|
|
Term
WHO IS RESPONSIBLE FOR COORDINATING TEAM MEMBERS SO THEIR WORK FITS WITHIN OVERALL DESIGN AND CONSTRUCTION |
|
Definition
|
|
Term
|
Definition
SERIES OF TWO OR MORE RISERS BETWEEN ONE FLOOR OR LANDING & THE NEXT |
|
|
Term
CODES REQUIRE TREADS TO BE ___ AND RISERS TO BE ____ |
|
Definition
|
|
Term
DESIGN OF STAIR IS RESPONSIBLITY OF |
|
Definition
|
|
Term
SPIRAL, WINDING & CURVED STAIRWAYS CAN ONLY BE |
|
Definition
USED AS EXIT STAIR WAYS IN PRIVATE HOMES & CONDOS |
|
|
Term
THE MINIMUM HEIGHT ALLOWANCE ABOVE THE STAIRS IS |
|
Definition
|
|
Term
WHAT IS USED TO CONTROL THE VOLUME OF AIR & DISTRIBUTION IN AN HVAC SYSTEM |
|
Definition
|
|
Term
THERE ARE COMBINATION SYSTEMS THAT USE DUCT WORK FOR SUPPLYING FRESH AIR; BUT USE OF WATER TO HEAT OR COOL THE AIR BEFORE IT IS INTRODUCED TO THE CONDITIONED SPACE, WHAT SYSTEM IS THIS? |
|
Definition
|
|
Term
ALL-WATER HEATING SYSTEMS USE A |
|
Definition
|
|
Term
|
Definition
SUBDIVIDED INTO AS MANY INDIVIDUALLY CONTROLLED AREAS AS NEEDED. |
|
|
Term
NAME THREE HIGH INTENSITY DISCHARGE LAMPS AND WHAT DO THEY ALL HAVE IN COMMON |
|
Definition
METAL-HALIDE MERCURY-VAPOR HPS (HIGH PRESSURE SODIUM) COMMON: PRODUCE LIGHT BY PASSING AN ELECTRIC CURRENT THROUGH A GAS OR VAPOR UNDER HIGH PRESSURE |
|
|
Term
|
Definition
BETTER COLOR RENDITION THAN MERCURY-VAPOR BUT NOT A VERY LONG LIFE. GOOD FOR FURNTIURE WAREHOUSES |
|
|
Term
|
Definition
POOR COLOR RENDITION. LONG LIFE. GOOD FOR OUTDOOR LIGHTING |
|
|
Term
HPS (HIGH PRESSURE SODIUM) LAMPS |
|
Definition
MOST EFFICIENT, BUT PRODUCE YELLOW LIGHT, CRI CAN BE USED IN SOME INTERIORS WITH COLOR CORRECTIONS. ALSO FROM ALL OF THE HID LAMPS ITS TAKES THE SHORTEST TIME TO RESTART |
|
|
Term
|
Definition
BANDS FROM 200-2500 HERTZ RELATED TO THE SAA (SOUND ABSORPTION AVERAGE) WHO IS IN ACCORDANCE WITH THIS TEST |
|
|
Term
WHAT ARE THE MOST IMPORTANT RATINGS FOR EVALUATING TRANSMISSION LOSS THROUGH A FLOOR/CEILING ASSEMBLY |
|
Definition
IIC & STC (IMPACT INSULATION COEFFICIENT & SOUND TRANSMISSION COEFFICIENT) |
|
|
Term
WHAT DOES THE CONTRACT ADMINISTRAION PHASE INVOLVE |
|
Definition
ESTABLISHING CONTRACT BETWEEN OWNER & CONTRACTOR |
|
|
Term
CONTRACTS BETWEEN OWNER AND CONTRACTOR ARE DONE IN ONE OF TWO WAYS: |
|
Definition
NEGOTIATED CONTRACT: OWNER & CONTRACTOR NEGOTIATE A PRICE BID CONTRACT: CONTRACTORS BID ON WORK |
|
|
Term
BIDDERS CAN OBTAIN DOCUMENTS THROUGH _____ OFFICE AND THEY RECEIVE |
|
Definition
INTERIOR DESIGNER'S OFFICE REQUIRED DOCUMENTS (PRINTS), SPECS, BID FORMS, BIDDING DOCUMENTS, & ANY OTHER REQUIRED ITEM |
|
|
Term
________ IS ISSUED BY THE DESIGNER BEFORE THE EXECUTION OF THE CONTRACT THAT MODIFIES OR INTERPRETS THE BIDDING DOCUMENTS BY ADDITIONS, DELETIONS, CLASSIFICATIONS OR CORRECTIONS |
|
Definition
|
|
Term
PUBLIC BIDS ARE CONDUCTED BY |
|
Definition
|
|
Term
IF ALL THE BIDS EXCEED PROJECT BUDGET, OWNER HS FOUR OPTIONS: |
|
Definition
1- REBID 2- AUTHORIZE AN INCREASE IN CONSTRUCTION COST & PROCEED WITH PROJECT 3- WORK WITH DESIGNER IN REVISING SCOPE TO REDUCE PRICE 4- ABANDON PROJECT |
|
|
Term
INSTRUCTIONS TO THE BIDDERS SHOULD INCLUDE: |
|
Definition
CONSIDERATION OF BIDS BIDDERS' REPRESENTATION SUBSTITUTIONS BONDS INTERPRETATION OR CORRECTION OF BIDDING DOCUMENTS ADDENDA MODIFICATION OR WITHDRAWAL OF BID POST-BID INFORMATION |
|
|
Term
WHY ARE BID SECURITIES USED |
|
Definition
TO INSURE BIDDER WILL ENTER INTO CONTRACT WITH OWNER |
|
|
Term
FORM OF A BID SECURITY MAY BE: |
|
Definition
CASHIER'S CHECK CERTIFIED CHECK BID BOND |
|
|
Term
BID SECURITY IS EITHER A FIXED AMOUNT OR |
|
Definition
5% OF ESTIMATED COST FOR WORK OR BID PRICE |
|
|
Term
|
Definition
IS A STATEMENT BY A SURETY COMPANY THAT OBLIGATES THE SURETY COMPNAY TO COMPLETE CONSTRUCTION IF THE CONTRACTOR DEFAULTS ON HIS OR HER OBLIGATIONS |
|
|
Term
IF OWNER HAS A PERFORMANCE BOND AND THE CONTRACTORS BAILS THE JOB WHAT HAPPENS |
|
Definition
SURETY COMPANY WHO WROTE THE STATEMENT (PERFORMANCE BOND) WILL EITHER HIRE ANOTHER CONTRACTOR TO FINISH THE JOB OR SUPPLY ADDITIONAL MONEY TO DEFAULTING CONTRACTOR TO FINISH CONSTRUCTION |
|
|
Term
THE COST OF A PERFORMANCE BOND IS |
|
Definition
3% OF THE ESTIMATED PROJECT & PAID BY OWNER |
|
|
Term
WHAT IS A LABOR & MATERIAL BOND |
|
Definition
PERFORMANCE BOND TO PROTECT OWNER IF CONTRACTOR DOES NOT PAY FOR LABOR AND MATERIALS; THEREFORE, PROTECTING OWNER FORM LIENS AGAINST PROPERTY OR LITIGATION BY SUBCONTRACTORS & MATERIAL SUPPLIERS |
|
|
Term
ONE VARIABLE OVER WHICH DESIGNER & OWNER HAVE CONTROL OVER IS THE |
|
Definition
|
|
Term
ALTERNATES (IN RELATION TO COST CONTROL IN BIDDING) IS A |
|
Definition
REQUEST INCLUDED IN THE BIDDING DOCUMENTS ASKING CONTRACTOR TO SUPPLY A PRICE FOR ANOTHER TYPE OF VARIATION FROM BASE BID. EXAMPLE: BASE BID MAY REQUEST CARPET AS A FLOOR COVERING IN A ROOM, WHITEL AN ALTERNATE MAY BE TO SUBSTITUTE WOOD FLOORING FOR THE CARPET |
|
|
Term
|
Definition
SET AMOUNT OF MONEY ESTIMATED BY DESIGNER TO COVER A PARTICULAR MATERIAL OR EQUIPMENT WHEN THE ACTUAL COST WAS NOT KNOWN AT THE TIME OF BIDDING OR NEGOTIATED PROPOSAL |
|
|
Term
|
Definition
CHANGE ORDER - WRITTEN AMENDMENT TO CONTRACT SIGNED BY BOTH - WRITTEN INTERPRETATION ISSUED BY DESIGNER - OR WIRTTEN ORDER FOR MINOR CHANGES IN WORK |
|
|
Term
CONTRACT DOCUMENTS CONSIST OF |
|
Definition
-THE AGREEMENT -CONDITIONS OF CONTRACT -DRAWINGS -SPECS -ADDENDA -ANY OTHER DOCUMENTS SPECIFICATLLY LISTED IN AGREEMENT -MODIFICATIONS (CHANGE ORDERS) ISSED AFTER EXECUTION OF CONTRACT |
|
|
Term
ARE BIDDING DOCUMENTS PART OF THE CONTRACT? |
|
Definition
NO THEY ARE PART OF THE PROJECT MANUAL |
|
|
Term
|
Definition
FORM OF AGREEMENT B/T OWNER & VENDOR (BASIS OF PAYMENT IS STIPULATED SUM) |
|
|
Term
|
Definition
GENERAL CONDITIONS OF CONTRACT FOR FF&E |
|
|
Term
|
Definition
INVITATION & INSTRUCTIONS FOR QUOTATION FOR FF&E |
|
|
Term
|
Definition
FORM OF AGREEMENT B/T ARCHITECT & OWNER FOR ARCHITECTURAL INTEIROR DESIGN SERVICES |
|
|
Term
|
Definition
AGREEMENT B/T ARCHITECT & OWNER FOR FF&E |
|
|
Term
WHY ARE THERE TWO DIFFERENT CONTRACTS WHEN IT COMES TO CONSTRUCTION & FF&E? |
|
Definition
BECAUSE CONSTRUCTION IS GOVERNED BY COMMON LAW (REGULATES SERVICES) & FF&E IS GOVEREND BY STATUTORY (SALE OF GOODS) |
|
|
Term
THE PERCENTAGE OF THE CONTRACT AMOUNT WITHHELD UNTIL COMPLETION OF PROJECT IS CALLED |
|
Definition
|
|
Term
|
Definition
OWNER-CONTRACTOR AGREEMENT WHERE BASIS OF PAYMENT IS A STIPULATED SUM |
|
|
Term
CLIENT CANNOT TAKE OCCUPANCY OF BUILDINGS OR MOVE ANY FF&E INTO THE BUILDING UNTIL |
|
Definition
SUBSTANTIAL COMPLETION HAS BEEN DOCUMENTED |
|
|
Term
|
Definition
MONEYS PAID BY CONTRACTOR TO OWNER FOR EVERY DAY THE PROJECT IS LATE (B/C OWNER MAY HAVE TO BE PAYING RENT BECAUSE HE/ SHE CANNOT MOVE INTO NEW PROPERTY DUE TO CONTRACTOR NOT MEETING COMPLETION DATE) |
|
|
Term
WHAT CODE GOVERNS SALE OF GOODS |
|
Definition
UCC-UNIFORM COMMERCIAL CODE |
|
|
Term
TRUE OR FALSE: THE UCC MAY TAKE PRESENCE OVER THE CONTRACT |
|
Definition
|
|
Term
|
Definition
|
|
Term
|
Definition
FF&E VENDOR (BUYER) PAYS FOR THE TRANSPORTATION COSTS AND MANUFACTURER IS NOT RESPONSIBLE FOR ANYTHING LOST OR BROKEN DURING SHIPMENT |
|
|
Term
|
Definition
MANUFACTURER RESPONSIBLE FOR SHIPPING & RECOVERING DAMAGES OR LOSS DURING SHIPMENT |
|
|
Term
FOB FACTORY-FREIGHT PREPAID |
|
Definition
FF&E VENDOR (BUYER) OWNS FURNITURE, BUT SUPPLIER PAYS SHIPPING COSTS |
|
|
Term
_______ IS RESPONSIBLE FOR A PRELIMINARY INSPECTION OF THE FURNITURE & OTHER GOODS AT THE JOB SITE |
|
Definition
|
|
Term
|
Definition
DETENTION OF A SHIP AT PORT BY SHIP OWNER (OR RALILROAD CAR OR TRUCK OWNER) BEYOND TIME NORMALLY ALLOWED OR AGREED UPON |
|
|
Term
|
Definition
GENERAL CONDITIONS OF CONTRACT FOR CONSTRUCTION |
|
|
Term
|
Definition
SECURE AGAINST LOSS OR DAMAGE . INTENDED TO PROTECT OWNER & ARCHITECT AGAINST SITUATION WHERE PERSON IS INJURED DUE TO CONTRACTOR'S (OR CONTRACTORS' AGENTS) NEGLIGENCE |
|
|
Term
CONTRACT TIME MAY BE EXTENDED BY A |
|
Definition
CHANGE ORDER IF DELAYS OCCUR BEYOND CONTRACTOR'S CONTROL |
|
|
Term
__________ IS RESPONSIBLE FOR ONSITE SAFETY & PRECAUTIONS AGAINST DAMAGE TO PERSON OR PROPERTY |
|
Definition
|
|
Term
_____ ______ IS BASED ON A WRITTEN AGREEMENT AMONG OWNER, CONTRACTOR & DESIGNER CONCERNING THE EXTENT OF THE CHANGE & ITS COSTS OR SCHEDULE IMPLICATIONS |
|
Definition
CHANGE ORDER NOTE: IT MUST BE SIGNED BY ALL THREE PARTIES(OWNER, CONTRACTOR & DESIGNER) |
|
|
Term
THE RISK FOR FURNITURE BEING DAMAGED DURING SHIPMENT IS ASSIGNED BY THE |
|
Definition
UCC UNIFORM COMMERCIAL CODE |
|
|
Term
DUTIES OF AN INTERIOR DESIGNER ARE ITEMIZED IN |
|
Definition
|
|
Term
|
Definition
SHOP DRAWINGS, SAMPLES, PRODUCT DATA (BROCHURES, CHARTS, CATALOG PAGES) |
|
|
Term
WHO IS RESPONSIBLE FOR APPROVING & REVIEWING SHOP DRAWINGS |
|
Definition
|
|
Term
WHEN ARE THE SHOP DRAWINGS GIVEN TO THE DESIGNER |
|
Definition
AFTER CONTRACTOR HAS REVIEWED THEM AND IF THEY ARE NOT SIGNED BY CONTRACTOR, DESIGNER MUST SEND THEM BACK TO CONTRACTOR |
|
|
Term
WHO IS RESPONSIBLE TO VERIFY FIELD DIMENSIONS WITH SHOP DRAWINGS |
|
Definition
|
|
Term
WHO IS RESPONSIBLE FOR DETERMINING COMPLETENESS OF DETAILS, QUANTITIES, FABRICATION, INSTALLATION PROCEDURES, ACCURACY OF MEASUREMENTS) |
|
Definition
|
|
Term
IF DESIGNER DOES NOT CATCH A MISTAKE ON THE SHOP DRAWINGS AND THEY ARE BUILT AND THE MISTAKE IS NOTED WHOSE FAULT IS IT? |
|
Definition
CONTRACTOR BECAUSE HE/SHE IS RESPONSIBLE FOR BUILDING ACCORDANCE TO THE CONTRACT DOCUMENTS & MAKING SURE SHOP DRAWINGS CONFIRM TO THEM |
|
|
Term
WHO IS RESPONSIBLE OF CHECKING FOR CONFORMANCE WITH INFORMATION PROVIDED & DESIGN INTENT |
|
Definition
|
|
Term
WHAT IS THE AMOUNT OF TIME A DESIGNER HAS TO REVIEW THE SHOP DRAWINGS GIVEN TO HIM/HER BY THE CONTRACTOR? |
|
Definition
THERE IS NO SPECIFIC AMOUNT OF TIME EXCEPT DESIGENR MUST ACT WITH REASONABLE PROMPTNESS |
|
|
Term
CONTRACT ADMINISTRATION CONSISTS OF: |
|
Definition
FIELD ADMINISTRATION CHANGES IN WORK REVIEWING SHOP DRAWINGS PROGRESS PAYMENTS INSTALLATION OF FF&E PROJECT CLOSE OUT (PUNCH LISTS) |
|
|
Term
TRUE OR FALSE: DESIGNER HAS AUTHORITY TO REJECT CONSTRUCTION WORK THAT DOES NOT CONFORM TO THE CONTRACT DOCUMENT |
|
Definition
TRUE THE GENERAL CONDITIONS OF THE CONTRACT FOR CONSTRUCTION STATES THIS |
|
|
Term
A DEMAND OR ASSERTION BY THE CONTRACTOR OR OWNER SEEKING PAYMENT OF MONEY, AN EXTENSION OF TIME, ADJUSTMENT OR INTERPRETATION OF THE CONTRACT TERMS, OR OTHER RELIEF IS CALLED A |
|
Definition
|
|
Term
WHO IS RESPONSIBLE FOR REVIEWING A CLAIM? AND HOW MANY DAYS DOES HE/SHE HAVE TO REACH A DECISION? |
|
Definition
|
|
Term
HOW MANY DAYS DOES THE CLAIMANT HAVE TO FILE A CLAIM? |
|
Definition
|
|
Term
|
Definition
A PROCESS THAT INVOLVES A NEUTRAL THIRD PARTY TO ASSIST IN DISPUTE. IF AGREEMENT CANNOT BE MADE IT MOVES TO ARBITRATION |
|
|
Term
|
Definition
KNOWLEDGEABLE IDUSTRY, LISTENS TO EVIDENCE, HEARS WITNESSES, REVIEWS DOCUMENTS ADVANTAGE OVER LITIGATION |
|
|
Term
DURING BIDDING CHANGES ARE MADE BY ________, DURING CONSTRUCTION CHANGES ARE MADE BY ________, ________, OR ________ |
|
Definition
ADDENDA MINOR CHANGES, CONSTRUCTION CHANGE DIRECTION OR FORMAL CHANGE ORDER |
|
|
Term
|
Definition
CLAIMS FROM SUPPLIERS, VENDORS FOR GOODS AND SERVICES NOT YET PAID |
|
|
Term
|
Definition
MONEY THAT OTHERS OWE DESIGN FIRM |
|
|
Term
|
Definition
ANY TYPE OF TAGIBLE OR INTANGIBLE RESOURCE THAT CAN BE MEASURED IN MONETARY TERMS |
|
|
Term
|
Definition
LIST OF VARIOUS ACCOUNTSA BUSINESS USES TO KEEP TRACK OF MENY ALONG WITH ACCOUNT NUMBERS USED FOR DATA PROCESSING |
|
|
Term
|
Definition
RESOURCES OF THE BUSINESS THAT WILL BE CONVERTED TO CASH WITHIN A YEAR |
|
|
Term
|
Definition
CHARGABLE TO CLIENTS AS THEY RELATE TO PROJECT |
|
|
Term
|
Definition
NOT BILLABLE TO PROJECTS BECAUSE THEY ARE IN HOUSE EXPENSES. GENERAL OFFICE, MARKETING, ETC |
|
|
Term
|
Definition
PAYROLL TAXES, HEALTH INSURANCE |
|
|
Term
DISCRETIONARY DISTRIBUTIONS |
|
Definition
VOLUNTARY DISTRIBUTIONS OF PROFITS TO OWNERS (BONUSES, INCENTIVES, ETC) |
|
|
Term
|
Definition
RESOURCES GENERATED BY A BUSINESS THAT ARE LONG-TERM |
|
|
Term
|
Definition
ALL THE REVENUE GENERATED DURING A PERIOD OF TIME |
|
|
Term
|
Definition
CLAIMS MADE BY PEOPLE OUTSIDE BUSINESS |
|
|
Term
|
Definition
MISCELLANEOUS RESOURCES SUCH AS SECURITIES AND COPYRIGHTS |
|
|
Term
|
Definition
UTILITIES, RENT, POWER, TELEPHONE |
|
|
Term
|
Definition
REVENUE & EXPENSES RECOGNIZED AT THE ACTUAL TIME THE BUSINESS RECEIVES CASH OR PAYS A BILL CANNOT BE USED BY COMPANY THAT KEEPS INVENTORY |
|
|
Term
|
Definition
REVENUE & EXPENSES ARE RECOGNIZED AT TIME THEY ARE EARNED OR INCURRED FIRM SENDS CLIENT BILL FOR 1,000.00 AND FIRM ALREADY HAS IT LISTED AS REVENUE |
|
|
Term
|
Definition
TRANSACTIONS POSTED ON LEDGER AND GROUPED INTO INDIVIDUAL ACCOUNTS |
|
|
Term
WHAT IS ONE OF THE MOST IMPORTANT TYPES OF REPORTS FOR AN INTERIOR DESIGN FIRM? |
|
Definition
|
|
Term
AVERAGE COLLECTION PERIOD FOR INVOICES |
|
Definition
|
|
Term
IF I NEED TO FIND OUT WHICH PROJECT IS HURTING OVERALL PROFITABIITY I WOULD LOOK AT WHICH REPORT? |
|
Definition
|
|
Term
IF I NEEDED TO LOOK UP WHICH CLIENT INVOICES ARE STILL OPEN AND NOT PAID I WOULD LOOK AT THE |
|
Definition
AGED ACCOUNTS RECEIVABLE REPORT |
|
|
Term
IS I NEED TO LOOK UP AN EMPLOYEES NUMBER OF HOURS FOR A CERTAIN WEEK I WOULD TURN TO WHICH REPORT? |
|
Definition
|
|
Term
NATIONAL LABOR RELATIONS ACT PROTECTS |
|
Definition
EMPLOYEES (MOSTLY UNION) FROM UNFAIR LABOR PRACTICES BY EMPLOYERS AKA WAGER ACT |
|
|
Term
|
Definition
EMPLOYEE CAN QUIT AT ANY TIME WITHOUT NOTICE |
|
|
Term
NAME THE THREE "DUTIES" ARE ESTABLISHED IN INTERIOR DESIGNS |
|
Definition
TERMS OF CONTRACT DESIGNER'S BEHAVIOR (IMPLIED DUTIES) BUILDING CODES, TITLE LAWS, LICENSING |
|
|
Term
|
Definition
LEGAL RESPONSIBILITY FOR INJURY OR DAMAGE TO ANOTHER PERSON OR PROPERTY |
|
|
Term
|
Definition
FAILURE TO USE DUE TO CARE TO AVOID HARMING ANOTHER PERSON OR PROPERTY |
|
|
Term
PRIVITY PROTECTS THE DESIGNER FORM |
|
Definition
CLAIMS BY PARTIES WITH WHOM THE DESIGNER HAS NO DIRECT CONTRACTUAL RELATIONSHIP |
|
|
Term
|
Definition
LEADERSHIP IN ENERGY & ENVIORNMENTAL DESIGN |
|
|
Term
|
Definition
NONPROFIT ORGANIZATION THAT PROMOTES ENVIRONMENTALLY RESPONSIBLE PRODUCTION, PURCAHSING & PRODUCTS |
|
|
Term
NAME THE FOUR STAGES OF PRODUCTS LIFE CYCLE |
|
Definition
RAW MATERIAL MANUFACTURING USE AND MAINTANENCE DISPOSAL |
|
|
Term
|
Definition
MARKETABLE BY-PRODUCT THAT WAS CONSIDERED TO BE WASTER BUT CAN BE USED AS A RAW MATERIAL IN A DIFFERENT MANUFACTURING PROCESS |
|
|
Term
DEMAND CONTROL VENTILATOIN |
|
Definition
ADJUST AMOUNT OF VENTILATION PRODUCED IN A SPACE. USES CARBON DIOXIDE SENSORS |
|
|
Term
|
Definition
TOTAL ENERGY REQUIRED TO EXTRACT, PRODUCE, FABRICATE, & DELIVERY MATERIAL TO JOBSITE, ENERGY USED TO EXTRACT & PROCESS RAW MATERIAL, ETC |
|
|
Term
|
Definition
REFERRING TO MATERIAL OR PRODUCT THAT HAS SERVED ITS INTENDED USE, RECOVERED FROM WASTE & DESTINED FOR DEPOSAL HAVING COMPLETED ITS LIFE AS A CONSUMER ITEM |
|
|
Term
|
Definition
REFERRING TO MATERIAL GENERATED IN MANUFACTURING PROCESS (TRIMMINGS OR SCAP) THAT HAVE BEEN RECOVERED FROM WASTE |
|
|
Term
|
Definition
WASTE OR BY-PRODUCTS THAT HAVE BEEN RECOVERED FROM WASTE DISPOSAL |
|
|
Term
|
Definition
PRODUCTS THAT CAN BE GROWN, NATURALLY REPLENISHED OR CLEANSED AT RATE THAT EXCEEDS HUMAN DEPLETION |
|
|
Term
|
Definition
CONDITION OF BEING ABLE TO MEET THE NEEDS TO THE PRESENT GENERATION WITHOUT COMPROMISING NEEDS OF FUTURE GENERATIONS |
|
|
Term
HOW MUCH FRESH AIR VENTILATION IS RECCOMENDED BY THE ASHRAE STANDARD 62 PER PERSON? |
|
Definition
|
|
Term
WHO IS RESPONSIBLE FOR MAKING SURE THE DESIGNS MEET ALL THE APPLICABLE CODES & REGULATIONS |
|
Definition
|
|
Term
TURE OR FALSE: ASTM PERFORMS TESTS AS WELL AS HAS ITS PROCESURES & STANDARDS USED BY TESTING AGENCIES |
|
Definition
FALSE UNDERWRITTERS LABORATORY IS A TESTING AGENCY ASTM ONLY HAS ITS PROCESURES & STANDARDS USED BY TESTINGS AGENCIES |
|
|
Term
FIRE DOORS ARE REQUIRED TO BE TESTED IN ACCORDANCE WITH |
|
Definition
|
|
Term
WHICH IS MOST FIRE RESISTANT CLASS A CLASS B CLASS C |
|
Definition
CLASS A UNDER THE ASTM E119 |
|
|
Term
TEST METHOD FOR SMOKE DENSITY? WHAT DOES THE CODE REQUIRE FOR SMOKE DENSITY? |
|
Definition
ASTM E662 OR NFPA 258 450 OR LESS |
|
|
Term
TEST REQUIRED IN ADDITION TO E84 WHICH DETERMINES CONTRIBUTION OF INTERIOR WALL & CEILING COVERINGS TO ROOM FIRE GROWTH. TEST IS A FULL-SCALE MOCKUP |
|
Definition
NFPA 265 ROOM CORNER TEST |
|
|
Term
TESTING METHOD TO ADDRESS CONCERNS WITH INTERIOR FINISHES THAT DO NOT REMAIN IN PLACE DURING TESTING ACCORDING TO E84 |
|
Definition
|
|
Term
TESTING OF DRAPERY, CURTAINS OR OTHER WINDOW TREATMENTS |
|
Definition
|
|
Term
EXIT-ACCESS CORRIDORS ARE REQUIRED TO HAVE |
|
Definition
1-HOUR RATINGS & 20-MINUTE DOOR ASSEMBLY RATINGS |
|
|
Term
IT IS IMPORTANT TO NOTE THAT MANY MATERIALS BY THEMSELVES DO NOT CREATE A FIRE-RATED BEARRIER, IT IS THE |
|
Definition
|
|
Term
NAME THE LOCATIONS WHERE A 1-HOUR FIRE RATED PARTITION IS REQUIRED & WHAT IS THE EXCEPTION |
|
Definition
1-WALLS SEPARATING DWELLING UNITS 2-WALLS SEPARATING R-1 (HOTELS), R-2 (APARTMENTS), I-1 (LIVING FACILITIES) OCCUPANCIES 3-WALL SEPARATING TENANT SPACES IN MALLS 4-CORRIDOR WALLS EXCEPT IF BUILDING IS EQUIPPED WITH AUTOMATIC SPRINKLERS WHICH DEPENDS ON OCCUPANY B/C IT DOES NOT APPLY TO I, H, OR R |
|
|
Term
IN "MOST" CASES FIRE PARTITIONS MUST PROVIDE A |
|
Definition
CONTINUOS BARRIER MEANING IT SHOULD EXTEND FROM FLOOR TO UNDERSIDE FLOOR OR ROOF/CEILING ASSEMBLY |
|
|
Term
DOOR OPENINGS IN A FIRE PARTITION MUST BE A MINIMUM OF _____ EXCEPT IN ________ WHERE THE DOORS ARE ______ FIRE PROTECTED ASSEMBLY |
|
Definition
3/4-HOUR CORRIDOR 20-MINUTES |
|
|
Term
|
Definition
VERTICAL OR HORIZONTAL ASSEMBLY THAT IS FIRE-RESISTANCE RATED AND DESIGNED TO RESTRICT SPREAD OF FIRE, CONFINE FIRE TO AN AREA, AND/OR ALLOW FOR SAFE PASSAGE FOR PROTECTED EGRESS |
|
|
Term
FIRE BARRIER PURPOSES ARE |
|
Definition
-ENCLOSE A VERTICAL EXIT ENCLOSURE (STAIRWAY), EXIT PASSAGE, HORIZONTAL EXITS -SEPARATE DIFFERENT OCCUPANCIES INTO DIFFERENT MIXED OCCUPANCIES -SEPARATE SINGLE OCCUPANICES INTO DIFFERENT FIRE AREAS -PROVIDE FIRE BARRIER WHERE SPECIFICALLY REQUIRED BY CODE |
|
|
Term
UNLIKE FIRE PARTITIONS, FIRE BARRIER "MUST ALWAYS" BE |
|
Definition
CONTINUOUS FROM FLOOR SLAB TO UNDERSIDE SLAB OR ROOF SLAB ABOVE |
|
|
Term
FIRE BARRIERS REQUIRED TO HAVE A FIRE-RESISTANCE RATING OF |
|
Definition
|
|
Term
|
Definition
CONTINUOUS VERTICAL OR HORIZONTAL MEMBRANE WITH MINIMUM FIRE-RATING OF 1 HOUR DESIGN TO RESTRICT MOVEMENT OF SMOKE OPENINGS REQUIRED TO HAVE 20-MINUTE RATING AT LEAST |
|
|
Term
WHAT TEST RATES THE FOLLOWING: PANELING WAISCOTTING HEAVY WALLCOVERING ACCOUSTICAL COVERING |
|
Definition
|
|
Term
WHAT TESTS DOES WALL COVERING NEEDS TO PASS |
|
Definition
1- ASTM E84 TUNNEL TEST 2- NFPA 265 ROOM CORNER TEST (CONTRIBUTION TO FIRE GROWTH) 3- NFPA 258 SMOKE DENSITY (SMOKE DEVELOPED FROM FLAMING & NONFLAMING MATERIALS) |
|
|
Term
WHAT TESTS DOES CEILNG FINISHES NEED TO PASS |
|
Definition
1- ASTM E84 TUNNEL TEST 2- NFPA 258 SMOKE DENSITY |
|
|
Term
WHAT CLASSIFICATION OF OCCUPANCY IS IT WHEN THERE IS 50 OR MORE OCCUPANTS? |
|
Definition
ASSEMBLY A-1 BEING MOST RESTRICTIVE GOES FROM A-1 THRU A-5 A-1 THEATER, FIXED SEATING A-2 PLACE WHERE THERE IS FOOD & ALCOHOL A-3 ASSEMBLY OF WORSHIP & MISC A-4 ASSEMBLY INDOOR SPORTS A-5 ASSEMBLY OUTDOOR SPORTS |
|
|
Term
NAME THE LEVELS OF THE "R" OCCUPANCY |
|
Definition
THERE ARE FOUR LEVELS, R-1 BEING MOST RESTRICTIVE R-1 HOTELS R-2 APARTMENTS R-3 SINGLE FAMILY HOMES, DUPLEXES R-4 RESIDENTIAL CARE OF ASSISTIVE LIVING USES |
|
|
Term
|
Definition
A-ASSEMBLY (A-1 THRU A-4) B-BUSINESS E-EDUCATIONAL F-FACTORY & INDUSTRIAL H-HAZARDOUS I-INSTITUTIONAL (I-1THRU I-4) M-MERCHANTILE R-RESIDENTIAL (R-1 THRU R-4) S-STORAGE U-UTILITY |
|
|
Term
WHEN THE BUILDING IS EQUIPPED WITH AUTOMATIC SPRINKLER SYSTEM, THE REQUIRED HOURLY RATING ARE "GENERALLY" REDUCED BY |
|
Definition
|
|
Term
|
Definition
A SEPARATE SPACE OR ROOM THAT DOES NOT OCCUPY MORE THAN 10% OF THE MAIN OCCUPANCY & IT WOULD DOES NOT REQUIRE A FIRE BARRIER SEPARATION |
|
|
Term
|
Definition
AN AREA THAT IS INCIDENTAL TO THE MAIN OCCUPANCY & HAS SAME CLASSIFICATION AS NEAREST MAIN OCCUPANY BUT IT NEEDS TO BE SEPARATED BY FIRE BARRIER (BY CODE) BUT IF SPRINKLERED CAN BE SEPARATED BY SMOKE BARRIER & SPRINKLERS ONLY NEED TO BE IN THE INCIDENTAL SIDE WITH A SELF-CLOSING (OR AUTOMATIC) DOOR(S) |
|
|
Term
HOW MANY TYPES OF CONTRUSTIONS ARE THERE & WHICH IS THE MOST RESTRICTIVE? |
|
Definition
FIVE TYPES, & TYPE I IS THE MOST RESTRICTIVE |
|
|
Term
IN NONSPRINKLERED BUILDINGS OF OCCUPANICES A,B,E,F,M,S & U THE CORRIDORS MUST HAVE ______ BUT IN A SPRINKLERED BUILDING OF SAME OCCUPANCIES CORRIDORS NEED ______ |
|
Definition
1-HOUR RATING NOT BE RATED |
|
|
Term
RESPONSIBILITY OF DESIGN & LAYOUT OF SPRINKLERS RESTS ON THE |
|
Definition
|
|
Term
|
Definition
USED TO DESCRIBE ANY FIRE ALARM OR FIRE-EXTINGUISHING DEVICE OR SYSTEM THAT IS DESIGNED AND INSTALLED TO DETECT, CONTROL OR EXTINGUISH FIRE OR TO ALERT OCCUPANTS OR FIRE DEPARTMENT THAT FIRE HAS OCCURRED |
|
|
Term
1/4" WIRED GLASS MEETS WHAT RATING |
|
Definition
MEETS REQUIREMENTS FOR 45-MINUTE RATING WITHOUT SPECIFIC TESTING BUT ALL OTHER GLAZING MUST MEET NFPA 252 OR 257 |
|
|
Term
FIRE PROTECTION RATED GLAZING |
|
Definition
1/4" THICK WIRE GLASS IN STEEL FRAMES |
|
|
Term
FIRE RESISTANCE-RATED GLAZING |
|
Definition
GLASS OR OTHER GLAZING MATERIAL THAT HAS BEEN TESTED AS A PART OF FIRE-RESISTANCE-RATED WALL ASSEMBLY ACCORDINGLY ASTM E119 NO LIMITATION |
|
|
Term
|
Definition
COMPONENT WHOSE FUNCTION IS TO PREVENT FALLS FROM AN ELEVATED AREA |
|
|
Term
UBC REQUIRES GUARD (GUARDRAILS) |
|
Definition
ALONG OPEN-SIDED WALKING SURFACES, MEZZANINES, INDUSCTRIAL EQUIPMENT, PLATFORMS, STAIRWAYS, RAMPS, & LANDINGS THAT HAVE MORE THAN 30" ABOVE FLOOR BELOW EXCEPTIONS: STAGES, PLATFORMS |
|
|
Term
SATISFYING PLUMBING REQUIREMENT IS RESPONSIBILITY OF |
|
Definition
MECHANICAL ENGINEER & ARCHITECT |
|
|
Term
IN DWELLINGS UNITS & GUEST ROOMS IBC REQUIRES WALL ASSEMBLIES TO HAVE A MINIMUM SOUND TRANSMISSION OF |
|
Definition
50 FOR WALLS (45 FOR FIELD) |
|
|
Term
WHEN SELECTING A FINISH FOR A WALL PARTITION WHAT ARE THE TWO MOST IMPORTANT THINGS A DESIGNER SHOULD KNOW |
|
Definition
OCCUPANCY & WHETHER THE FINISH WILL GO IN AN EXIT OR NOT |
|
|
Term
THE MAJORITY OF THE BUILDINGS CODES IN THE UNITED STATES ARE GOVERNED BY |
|
Definition
|
|
Term
|
Definition
EXIT ACCESS, EXIT, EXIT DISCHARGE |
|
|
Term
OF THE THREE PARTS OF THE EGRESS SYSTEM WHICH ONE HAS THE LOWEST LEVEL OF PROTECTION |
|
Definition
|
|
Term
EXITS MUST HAVE WHAT TYPE OF RATING |
|
Definition
|
|
Term
WHAT IS THE LIMIT ON TRAVEL DISTANCE FOR AN EXIT DISCHARGE |
|
Definition
|
|
Term
BY CODE WHICH OF THE OCCUPANCIES IS ALLOWED AN EXIT THROUGH A STOCKROOM |
|
Definition
GROUP M OCCUPANCY BUT ONLY WITH CERTAIN RESTRICTION MET: 44" WIDTH IN STOCKROOM SAME HAZARD CLASSIFICATION AS STORE NOT MORE THAN 50% CAN BE OF EXIT ACCESS CANNOT BE SUBJECT TO LOOKING FROM EGRESS SIDE |
|
|
Term
MINIMUM CORRIDOR SIZE IS ______ WITH LESS THAN 50 OCCUPANTS & _______WITH OCCUPANT LOAD OF 50 OR MORE. IF OCCUPANT LOAD IS 100 OR MORE, CORRIDORS NEED TO BE ______ |
|
Definition
|
|
Term
CORRIDOR WALLS & CEILINGS IN A RESIDENTIAL OCCUPANCY SERVING 10 OR MORE MUST BE RATED |
|
Definition
|
|
Term
IN OCCUPANCIES REGARDLESS OF OCCUPANT LOAD MUST HAVE CORRIDOR WALLS/CEILINGS RATED AT |
|
Definition
|
|
Term
BOTH DOOR & FRAME MUST BEAR LABEL OF |
|
Definition
|
|
Term
GLASS MAY BE USED IN A 1-HOUR RATED CORRODR WALLS ONLY IF |
|
Definition
LABELED & LISTED AS A 3/4 HOUR FIRE-RPOTECTION RATING AND THE TOAL AREA DOES NOT EXCEED 25% OF WALL AREA |
|
|
Term
TRUE OR FALSE: FIRE-RESISTANCE-RATED GLAZING, TESTED WITH ASTM E119, IS USED ON A RATED CORRIDOR THERE IS NO LIMITATIONS |
|
Definition
|
|
Term
EGRESS DOORS MUST BE ____ OR ___HINGED AND MUST SWING IN ______ OF TRAVEL WHEN SERVING ANY HAZARDOUS AREA OR WITH OCCUPANT LOAD OF 50 OR MORE |
|
Definition
PIVOTED OR SIDE-HINGED DIRECTION |
|
|
Term
MAXIMUM WIDTH OF EGRESS DOOR OPENING MUST BE SUFFICIENT FOR OCCUPANT LOAD, BUT WITH A CLEAR WIDTH OF AT LEAST ____ |
|
Definition
|
|
Term
|
Definition
AUTOMATIC CLOSERS AND ALL HARDWARE MUST BE TESTED & APPROVED |
|
|
Term
WITH AN OCCUPANT LOAD TO DETERMINE THE WIDTH OF THE CORRIDOR YOU SHOULD MULTIPLY |
|
Definition
.15 SPRINKLERED .2 IF NOT SPRINKLED |
|
|
Term
STAIRS WITH AN OCCUPANT LOAD OF 50 OR MORE SHOULD BE AT LEAST ______ OR DETERMINED BY MULTIPLYING OCCUPANT LOAD BY ______ |
|
Definition
|
|
Term
STAIRWAYS WITH LESS THAN 50 OCCUPANTS SHOULD BE AT LEAST |
|
Definition
|
|
Term
STAIRWAYS WIDER THAN ___ SHOULD HAVE AN INTERMIDIATE HANDRAIL |
|
Definition
|
|
Term
TOP OF THE HANDRAIL MUST BE BETWEEN ______ ABOVE THE NOSING AND MUST EXTEND NOT LESS THAN ____ BEYOND THE TOP RISER & NOT LESS THAN THE DEPTH OF ONE ______ BEYOND THE BOTTOM RISER |
|
Definition
|
|
Term
LANDINGS MUST BE PROVIDED |
|
Definition
AT TOP & BOTTOM OF EVERY STAIRWAY |
|
|
Term
THE GRIPPING PORTION CANNOT BE LESS THAN _____ OR MORE THAN _____. SPACE BETWEEN HANDRAIL & WALL MUST BE AT LEAST _____. GIVING A TOTAL ALLOWABLE DISTANCE OF ______ PROTRUDING ON EACH SIDE OF STAIR |
|
Definition
|
|
Term
WHAT FOUR FACTORS DETERMINE THE NUMBER OF EXITS OR EXIT ACCESS DOORWAYS |
|
Definition
OCCUPANT LOAD OCCUPANCY OF SPACE LIMITATIONS ON COMMON PATH OF EGRESS SPECIFIC REQUIERMENTS WHEN LARGE OCCUPANT LOARDS ARE ENCOUNTERED |
|
|
Term
TRUE OR FALSE: EVEN IF THE OCCUPANT LOADS DOES NOT REQUIRE TWO EXITS, BUT THE COMMON PATH OF EGRESS EXCEEDS THE LIMITED, TWO EXITS ARE STILL REQUIRED |
|
Definition
|
|
Term
TRUE OR FALSE: IN RESIDENTIAL OCCUPANCIES EXITS MAY PASS THROUGH KITCHEN, STOREROOMS AND SIMILIAR SPACES |
|
Definition
|
|
Term
TRUE OR FALUSE: RESIDENTIAL OCCUPANCIES MAY HAVE CORRIDORS AT 44" & DOOR NEEDS TO SWING IN DIRECTION OF TRAVEL |
|
Definition
FALSE CORRIDORS ARE 36" DOORS CAN SWING INTO BEDROOMS |
|
|
Term
TRUE OR FALSE: IN AN OCCUPANCY OF B & F, DEAD END CORRIDORS CAN BE UP TO 50 FT WHEN IN A BULDING WITH AUTOMATIC SPRINKLERS. |
|
Definition
|
|
Term
WHAT IS INCLUDED IN THE RISE OF THE STAIR |
|
Definition
DISTANCE FROM FLOOR SLAB TO FLOOR SLAB |
|
|
Term
WHAT IS INCLUDED INCLUDED IN THE VERTICAL DISTANCE FROM ONE NOSING TO THE NEXT |
|
Definition
|
|
Term
WHAT ARE THE TWO MOST IMPORTANT FACTORS WHEN DETERMINING THE NUMBERS OF EXITS NECESSARY |
|
Definition
OCCUPANCY AND OCCUPANT LOAD!!!!!!! |
|
|
Term
|
Definition
|
|
Term
PASSAGE POINT CANNOT BE MORE THAN (ADA) |
|
Definition
|
|
Term
MINIMUM CLEAR FLOOR SPACE REQUIRED TO ACCOMODATE ONE STATIONARY WHEELCHAIR IS |
|
Definition
|
|
Term
|
Definition
1-1/2" NO SLOPE GREATER THAN 1:2 |
|
|
Term
GRAB BARS MUST BE INSTALLED AT A HEIGHT OF |
|
Definition
|
|
Term
CENTERLINES OF TOILETS (ADA) MUST BE INSTALLED |
|
Definition
|
|
Term
TRUE OR FALSE: IN DESIGNED ADA PUBLIC RESTROOMS YOU ONLY NEED TO INSTALL A GRAB BAR BEHIND THAT TOILET |
|
Definition
FALSE BACK AND SIDE MOUNTED AT 33-36" ABOVE THE FLOOR |
|
|
Term
IN ADA RESTROOMS MIRRORS SHOULD BE INSTALLED WITH THE BOTOOM EDGE OF THE REFLECTING SURFACE NO HIGHER THAN ______ ABOVE THE FLOOR |
|
Definition
|
|
Term
WITH ADA CARPET MUST HAVE A FIRM CUSHION OR BACKING OR NO CUSHION AND A PILE HEIGHT OF NO MORE THAN |
|
Definition
|
|
Term
STAIRS AND RAMPS: ACCORDING TO ADA RULING, SLOPE CANNOT BE GREATER THAN |
|
Definition
1:12 (1" FOR EVERY 12" IN RUN) |
|
|
Term
MAXIMUM RISE FOR EVERY RAMP IS LIMITED TO ____ WITH A CLEAR WIDTH OF ______ |
|
Definition
|
|
Term
ADA, RAMPS MUST HAVE HANDRAILS INSTALLED AT _______ |
|
Definition
|
|
Term
MAXIMUM DISTACE HEIGHT PROTRUDING OBJECT CAN EXTEND |
|
Definition
|
|
Term
ADA, VERTICAL CLEARANCE OF AN AREA |
|
Definition
|
|
Term
MOUNTING FOR THE LOWEST TECTILE CHARACTER MUST BE ______ |
|
Definition
|
|
Term
PERMINANT ROOMS AND SPACES, BY ADA CODE, MUST BE IDENTIFIED WITH SIGNS HAVING LETTERS IN ________, SIZES FROM _______ AND ____ RAISED ABOVE SURFACE OF SIGN |
|
Definition
|
|
Term
SIGNS MUST HAVE A _____ ______ FINISH OR _______ |
|
Definition
|
|
Term
DIRECTIONAL SIGNS MUST HAVE A HEIGH OF __________ |
|
Definition
|
|
Term
EMERGENCY WARNING SYSTEMS PROVIDE BOTH A _______ AND ______ ALARM AS REQUIRED |
|
Definition
VISUAL (1 CYCLE PER SECOND) AUDIABLE (SOUND LEVEL OF 15dB) |
|
|
Term
INSIDE ELEVATOR CAB BUTTONS SHOULD BE ISNTALLED |
|
Definition
54" ABOVE FLOOR, SIDE APPROACH 48" ABOVE FLOOR FRONT APPROACH |
|
|