Term
|
Definition
occurs when the body is able to dissipate the heat and moisture it produces naturally, and maintains normal body temperature. Thermal balance must exist between body and environment. |
|
|
Term
|
Definition
the physical property that determines the direction of heat flow between two objects placed in thermal contact |
|
|
Term
|
Definition
a form of energy, movement at molecular or atomic level. manifested in materials by a rise of temperature, fusion, expansion, or evaporation. |
|
|
Term
Thermal Comfort Variables |
|
Definition
Comfort is controlled by four variables: (dry-bulb) air temperature, (relative) humidity, radiant temperature, and air speed. |
|
|
Term
|
Definition
a temperature representing the combined effect of ambient temperature, relative humidity, and air movement on the sensation of warmth or cold felt by the human body, equivalent to the dry bulb temperature of still air at 50% relative humidity which induces an identical sensation. |
|
|
Term
Psychrometric chart VARIABLES (7) |
|
Definition
Dry-bulb Temperature % relative humidity wet-bulb termperature dew point water vapor content enthalpy specific volume |
|
|
Term
Psychrometric Chart VARIABLES - Dry-bulb temperature |
|
Definition
the air temperature (ºF) indicated by a standard thermometer |
|
|
Term
Psychrometric Chart VARIABLES - % relative humidity |
|
Definition
the amount of water vapor held in the air as a percent of the maximum amount of water vapor the air can hold at a specific temperature (warmer air can hold more water vapor). Air simply acts as a transporter of water vapor, not a holder of it. In fact, water vapor can be present in an airless volume and therefore the relative humidity of this volume can be readily calculated. The misconception that air holds water is likely the result of the use of the word saturation which is often misused in descriptions of relative humidity. In the present context the word saturation refers to the state of water vapor, not the solubility of one material in another |
|
|
Term
Psychrometric Chart VARIABLES - Wet-bulb temperature |
|
Definition
the temperature (ºF) indicated by a thermometer with a wet wick attached to its bulb; the wick is located in a moving air stream to encourage evaporation. The wet-bulb temperature is the minimum temperature which may be achieved by purely evaporative cooling of a water-wetted ventilated surface. For a given parcel air at a known pressure and dry-bulb temperature, wet-bulb temperature corresponds to unique values of relative humidity, dew point temperature, and other properties. For air that is less than saturated (100 percent relative humidity), the wet-bulb temperature is lower than the dry-bulb temperature; and the dew point temperature is less than the wet-bulb temperature. Cooling of the human body through perspiration is inhibited as the wet-bulb temperature (and relative humidity) of the surrounding air increases in summer. Other mechanisms may be at work in winter if there is validity to the notion of a "humid cold." Lower wet-bulb temperatures in summer can translate to energy savings in air-conditioned buildings due to: Reduced dehumidification load for ventilation air Increased efficiency of cooling towers |
|
|
Term
Psychrometric Chart VARIABLES - Dew point |
|
Definition
the air temperature at which condensation begins. (DPT) is that temperature at which a moist air sample at the same pressure would reach water vapor saturation. At this saturation point, water vapor would begin to condense into liquid water fog or if below freezing, solid frost, as heat is removed. The dew point temperature is measured easily and provides useful information, but is normally not considered an independent property. It duplicates information available via other humidity properties and the saturation curve. |
|
|
Term
Psychrometric Chart VARIABLES - Enthalpy |
|
Definition
the total heat contained in an air/water vapor mixture (BTU per pound of air). Enthalpy is the sum of sensible plus latent heat: heat content per unit mass. Lines of enthalpy are parallel to lines of constant wet bulb temperature. |
|
|
Term
Psychrometric Chart VARIABLES - Specific volume |
|
Definition
the number of cubic feet that 1 pound of air occupies (at 70 °F & 14.7 psi). It is also called Inverse Density, is the volume per unit mass of the air sample. The units are cubic feet per pound of dry air. |
|
|
Term
Psychrometric Chart VARIABLES - Water vapor content |
|
Definition
he weight of water vapor held in 1 pound of air (weight is measured in grains, 1 grain = 1/7,000 of a pound) |
|
|
Term
Study finding characteristics of air/water vapor using psychometric chart (MEEB 282-283) |
|
Definition
|
|
Term
|
Definition
a subjective experience, lack of heat |
|
|
Term
|
Definition
energy is transmitted between two bodies by a third medium: circulation of a fluid. Primarily dependent on air motion, air temperature, humidity. |
|
|
Term
|
Definition
energy is transmitted between two bodies by direct contact. Primarily dependent on surface temperature. |
|
|
Term
|
Definition
energy is transmitted between two bodies by energy waves. Primarily dependent on orientation of the body, surface temperature. Radiation uses photons to transmit electromagnetic waves through a vacuum, or translucent medium. |
|
|
Term
|
Definition
energy is transmitted between two bodies by vapor. Primarily dependent on humidity, air motion, air temperature. |
|
|
Term
|
Definition
time rate of heat flow through a unit area of a given material of unit thickness when the temperature difference across the thickness is one unit of temperature. |
|
|
Term
|
Definition
time rate of heat flow through a unit area of a given material of a given thickness when the temperature difference across the thickness is one unit of temperature. |
|
|
Term
|
Definition
reciprocal of thermal conductance, expressed as the temperature difference required to cause heat to flow through a unit area of material of a given thickness at the rate of one heat unit at a time. |
|
|
Term
|
Definition
R-value: a measure of the thermal resistance of a given material, used to specify the performance of thermal insulation. U-value: measure of the thermal transmittance of a building component or assembly, equal to the reciprocal of the total R-value of the component or assembly. |
|
|
Term
Thermal transmittance or Coefficient of heat transfer |
|
Definition
Time rate of heat flow through a unit area of building component or assembly when the difference between the air temperatures on the two sides is one unit of temperature. |
|
|
Term
|
Definition
Batt insulation, rigid board insulation, foamed in-place, loose-fill, reflective insulation, dead air space. |
|
|
Term
|
Definition
How much heat can be absorbed or store in a material , compared to the storage capacity of water. More heat energy is required to increase the temperature of a substance with high specific heat capacity than one with low specific heat capacity. For instance, eight times the heat energy is required to increase the temperature of an ingot of magnesium as is required for a lead ingot of the same mass. The specific heat of virtually any substance can be measured, including chemical elements, compounds, alloys, solutions, and composites. |
|
|
Term
|
Definition
British Thermal Unit Amount of heat needed to raise the temperature in a pound of water by one degree ºF. |
|
|
Term
Specific Heat of brick, soft wood and trombe wall |
|
Definition
Brick 0.22 Soft wood 0.39 Trombe wall |
|
|
Term
|
Definition
the ability of a surface to emit heat by radiation |
|
|
Term
|
Definition
the extent to which it diffusely reflects light from the sun. It is therefore a more specific form of the term reflectivity. Albedo is defined as the ratio of diffusely reflected to incident electromagnetic radiation. It is a unit-less measure indicative of a surface's or body's diffuse reflectivity |
|
|
Term
Know how to calculate U-Value |
|
Definition
Kaplan 49-53 MEEB: 185-187. Sdd R-value of all materials and then set the sum under 1. Eg. Total R-value = 18.3 (sum of material r-values): U-value = 1/18.3 |
|
|
Term
|
Definition
|
|
Term
R-value of dry earth, 8" concrete block, Polyurethane insulation, and air spaceAluminum foil facing air space |
|
Definition
dry earth - 0.2, 8" concrete block - 2.0, Polyurethane insulation - 6.0, air space where Aluminum foil facing air space - 3.0 |
|
|
Term
Outdoor air - code and cost |
|
Definition
Outdoor air must be provided in buildings for health reasons as mandated by code. Outdoor air is expensive because it costs a lot to heat it in winter and cool it in summer. |
|
|
Term
|
Definition
air brought into a building by fans or openings. In large buildings with few operable windows, ventilation is necessary to assure healthy and odor free conditions. The quantity of ventilation air brought into a building is determined by building codes according to the number of occupants and their activities. |
|
|
Term
|
Definition
flow of air from outside to inside via cracks or openings in the building envelope. Kaplan: 54-55 Because it's expensive to heat or cool outdoor air, efficient buildings conserve energy by: Careful control of fresh/outdoor air quantities. Using heat exchangers to temper outdoor air. Using an economizer, instead of refrigeration equipment. |
|
|
Term
|
Definition
equipment that permits the use of outdoor air instead of refrigeration units for building cooling when outdoor temperature conditions are right. Even better is an enthalpy controlled economizer which evaluates both outdoor temperature and humidity, and then mixes appropriate quantities of outdoor and indoor air to achieve comfortable conditions without cooling. |
|
|
Term
|
Definition
ransfer heat from exhaust air to incoming outdoor air. Heat exchangers permit building operators to use outdoor air for odor control without paying the full price of heating or cooling it. |
|
|
Term
Infiltration - value and calculation |
|
Definition
Residences and small buildings often rely on infiltration to provide all necessary outdoor air; unusual requirements like smelly cooking are taken care of by opening doors 15 and windows. Quantifying building infiltration is difficult because of the many variables involved. |
|
|
Term
Heat direction - when cold |
|
Definition
When the weather is cold, heat travels from inside (high) to outside (low). |
|
|
Term
|
Definition
calculated to determine the size of heating equipment. Heat leaves a building by only two routes: the building's skin conducts heat to colder outdoor surroundings, and cold outdoor air replaces heated building air. |
|
|
Term
|
Definition
All parts of a building's skin lose heat to colder surroundings, and the rate of heat loss is determined by the U value of the skin. U is the number of STUH conducted through 1 sqft. of a construction when a 1°F temperature difference drives heat flow. Conducted heat losses are given by the formula: q\c/ = UA x delta T U= Conductance value in BTUh/sqft./°F A= Area in sqft. ΔT= Temperature Difference indoor-outdoor Results in = Rate of heat flow, BTU per Hour. 16 Since peak heat loss is used to size heating equipment the outdoor temperature is selected for a typical cold winter day. |
|
|
Term
A roof covers an area 40 ft wide and 80 fl long. With heavy insulation, the resistance has been l l t d 38 ft2 calculated as ft2-hr-OFlBtu and the design equivalent temperature difference is 44°F. The design temperature is - 5°F and it is desired to maintain a 70 aF indoor temperature. The heal loss through the roof is most nearly |
|
Definition
Solution The design equivalent temperature difference has no bearing on the solution to this problem. First, calculate the U value, which is the reciprocal of the R-value. U= 1/38 ft2-hr- ºF /Btu= 0.026 Btu/ft2-hr- ºF Temperature difference: ΔT=T indoor-Tdesign=70-(-5)= 75 ºF Roof area: 40x80=3,200 f2 Heat loss: q=U A ΔT= (0.026 Btu/ft2-hr- ºF)(3,200 ft2) (75 ºF)=6,240 Btu/hr. |
|
|
Term
|
Definition
a day whose mean temperature is one degree below a reference temperature of 65°F. Two degree days may be a single day with a mean temperature of 63° (two degrees below 65°) or two days at 64°. |
|
|
Term
|
Definition
a day colder than 98% of the days experienced in the area. Is another way to size equipment |
|
|
Term
energy flow rate over a period of time formula |
|
Definition
qc = U (A)24 (DD) This formula allows us to compare alternatives over a period of time MEEB: 254-258 Kaplan: 53-54 |
|
|
Term
three added factors to heat gain |
|
Definition
sun, internal loads, and latent heat |
|
|
Term
|
Definition
can radiate up to 350 BUTH on each square foot it reaches radiant energy passes easily through glass a specific time must be used to estimate solar gain |
|
|
Term
Solar Heat gain through roofs and walls |
|
Definition
can also increase the temperature of roofs and walls above ambient air temperature, and heat flow into the conditioned space is increased as a result. |
|
|
Term
Heat gain - Internal Loads |
|
Definition
people, lights, appliances, motors, and food preparation People and cooking can add both sensible (dry) and latent (wet) heat motors and lights add only sensible heat HVAC equipment must remove internally generated heat to maintain comfortable interior conditions |
|
|
Term
|
Definition
exists in the water vapor carried by air as air temperature increases its ability to carry water vapor increases Significant air conditioning capacity is required to dehumidify moist outdoor air but cool dry air is necessary for comfort A ton of air conditioning is equivalent to 12,000 Btu/hr. This is the amount of refrigeration needed to make one ton of ice per day from 32°F water |
|
|
Term
|
Definition
tilt of the earth's axis, |
|
|
Term
Passive Solar Heating - Critical factors |
|
Definition
site and location of the building, climate, design and construction, solar orientation, fenestration and shading elements, and the use of heat sinks. Key word: integration of these principles. |
|
|
Term
|
Definition
a line joining an object and the sun; it becomes the direct normal intensity when it is perpendicular to the object and achieves maximum intensity. |
|
|
Term
|
Definition
radiant heat gain The main source of heat gain into a building Roofs receive the majority of the solar radiation |
|
|
Term
|
Definition
sheets separated by a sealed air/gas space (fused edges or spacer edged) |
|
|
Term
|
Definition
insulating glass that has coatings in one or various sheets of glass and the coating reflects radiation while light can penetrate Coating a glass surface with a low-emittance material reflects a significant amount of the radiant heat, thus lowering the total heat flow through the window. Low-E coatings are transparent to visible light, and opaque to infrared radiation. Different types of Low-E ti coatings have been designed to allow different levels of protection against solar gain. |
|
|
Term
Low-e side for To keep the sun's heat out of the house (for hot climates, east and west-facing windows, and unshaded south-facing windows), |
|
Definition
low-E coating should be applied to the outside pane of glass |
|
|
Term
low-e side if windows are designed to provide heat energy in the winter and keep heat inside the house (typical of cold climates) |
|
Definition
the Low-E coating should be applied to the inside pane of glass |
|
|
Term
borosilicate glass propserties |
|
Definition
|
|
Term
The heat gain for a building has been calculated at 144,000 Btu/hr What size compressive refrigeration machine |
|
Definition
Size = 144000/12000 = 12 tons. A ton of air conditioning is equivalent to 12,000 Btu/hr This is the amount of cooling capacity needed for the facility, and shows the direct application of heat gain calculations. |
|
|
Term
|
Definition
significant contaminant that affects indoor air quality Radon gas from natural sources can accumulate in buildings, especially in confined areas such as the basement can be found in some spring waters and hot springs. Depending on how houses are built and ventilated, radon may accumulate in basements and dwellings |
|
|
Term
|
Definition
Minimum Efficiency Reporting Value: a measurement scale designed in 1987 by ASHRAE to rate the effectiveness of air filters. The scale is designed to represent the worst case performance of a filter when dealing with particles in the range of 0.3 to 10 microns. The MERV rating is from 1 to 16. Higher MERV ratings correspond to a greater percentage of particles captured on each pass |
|
|
Term
Combustion heating - generates: |
|
Definition
carbon monoxide, breathable particulates, at times, nitrogen dioxide |
|
|
Term
Fireplaces v. wood stoves |
|
Definition
Fireplaces = terrible for heating because of heat loss through the chimney Wood stoves are better, but air control is the key factor. Best ones: air comes only from a controlled damper; door is gasketed. Mainly work through radiant heat: Masonry/concrete as heat sinks. Circulating stoves allow convection. Placement in building is critical! Wood storage is a major concern. |
|
|
Term
|
Definition
heats air. A fan is necessary to propel it. (Historic buildings had gravity air heating.) Ductwork is used to guide its path. It uses similar components than HVAC systems, so it is usually combined. Requires; Auto firing of oil/gas Operational / safety controls Blower / fan Filter Dampers and registers Exhaust. |
|
|
Term
|
Definition
heats water. Water is circulated, and it is used to heat the served spaces: it can be done via convection or radiation. |
|
|
Term
|
Definition
gravity air heating systems used by the Romans at public baths and private houses. Spaces were built under the habitable areas supported by short columns or pillars, to house furnaces, and allow hot air to circulate. Chases built in the walls allowing hot air and combustion by-products from furnaces to also heat the walls and escape out of flues in the roof Radiant heating and convection would walls, roof. heat the spaces, without having combustion gases in the spaces. |
|
|
Term
hourly fuel consumption: coal electricity natural gas #2 fuel oil wood |
|
Definition
coal: 14,600 BTU/lb electricity: 3413 kW/h natural gas: 1050 BTU/cu ft #2 fuel oil: 141,000 BTU/gal wood: 7,000 BTU/lb fuel (gal or lb) h = qc (heat loss -BTU/h)/(BTU per gal or lb) (efficiency) MEEB: 225 |
|
|
Term
heating means: boiler - convection - radiation - furnace - |
|
Definition
boiler - hydronic convection - radiators, baseboards radiation - floor/wall pipes furnace - ducted air |
|
|
Term
|
Definition
Hot water is circulated to fin tube convectors or radiators. These allow cold air to be heated. Typically used in buildings where cooling is not needed, and ventilation can be accomplished through windows or other means. They can be used to supplement other systems. Economical and simple to install and operate. Good comfort during heating season. Space efficient, convectors are available in many shapes. Dampers, thermostatic valves, zone pumps, and valves are some of the means to control the system. Low tech! |
|
|
Term
|
Definition
Water at station 5 will be cooler that 1. |
|
|
Term
central loop with diverts/ branches |
|
Definition
valves can be used at each one to reduce heat or to shut off heating to an area. Water at station 5 will be cooler that 1, but less so, because water is not circulating through the convectors, but accepts water from them |
|
|
Term
|
Definition
It provides the same water temperature to each convector. Equal friction / equal flow is achieved by reversing the return, so each convector has the same pipe run. Uses more pipe than series perimeter loop or central loop with diverts/ branches |
|
|
Term
aqueduct second use and other Roman passive techniques |
|
Definition
Romans circulated aqueduct water through walls to cool their houses. Evaporative cooling was an extended practice around the Mediterranean Sea |
|
|
Term
manually powered rotary fan inventor |
|
Definition
2nd century Chinese inventor Ding Huan of the Han Dynasty |
|
|
Term
|
Definition
In 747, Emperor Xuanzong of the Tang Dynasty built the Cool Hall with water-powered fan wheels for air conditioning as well as rising jet streams of water from fountains. |
|
|
Term
|
Definition
used cisterns and wind towers to cool buildings during the hot season |
|
|
Term
|
Definition
In the 1600s Cornelius Drebbel demonstrated "turning Summer into Winter" for James I of England by adding salt to water |
|
|
Term
Benjamin Franklin and John Hadley |
|
Definition
In 1758, Benjamin Franklin and John Hadley confirmed that evaporation of highly volatile liquids such as alcohol and ether could be used to lower the temperature of an object past the freezing point of water. |
|
|
Term
|
Definition
In 1820 Michael Faraday discovered that compressing and liquefying ammonia could chill air when the liquefied ammonia was allowed to evaporate. |
|
|
Term
|
Definition
In 1842, Florida physician John Gorrie used compressor technology to create ice, which he used to cool air for his patients in his hospital in Apalachicola, Florida |
|
|
Term
commercial applications of air conditioning |
|
Definition
manufactured to cool air for industrial processing rather than personal comfort. |
|
|
Term
first modern electrical air conditioning |
|
Definition
In 1902 the first modern electrical air conditioning was invented by Willis Haviland Carrier in Syracuse, NY. controlled not only temperature but also humidity |
|
|
Term
Larkin Company administration building |
|
Definition
1904 - first entirely air-conditioned modern office building on record.... |
|
|
Term
|
Definition
In 1906, Stuart W. Cramer of Charlotte, NC was exploring ways to add moisture to the air in his textile mill. Cramer coined the term "air conditioning." Willis Carrier adopted the term. |
|
|
Term
|
Definition
created the first chlorofluorocarbon gas, Freon, in 1928 |
|
|
Term
Compressive refrigeration |
|
Definition
based on the change of a gas to a liquid by mechanical method. It is condensed. The gas releases latent heat as it is compressed. This part of the system gets hot. As the liquid expands and vaporizes to a gas, it absorbs latent heat. That part of the system gets cold. |
|
|
Term
Four components of Compressive refrigeration |
|
Definition
valve, evaporator coil, compressor, and condenser coil |
|
|
Term
|
Definition
direct expansion (DX) system, where the evaporator is in direct contact with the air stream, so the cooling coil of the airside loop is also the evaporator of the refrigeration loop. The term “direct” refers to the position of the evaporator with respect to the cooling coil. |
|
|
Term
|
Definition
system that uses reversible refrigeration cycle to heat and cool a facility. It “pumps” heat out in summer, and “pumps” heat in during winter. It uses temperature differentials to gain energy savings. The heat pump is a normal compressive cooling mechanism that can be reversed to provide heating. For cooling, the interior heat is moved outdoors. Heating uses higher temperatures, also outdoors, and using the inverse path, transfer that energy inside. Note that the condenser and the evaporator switch roles, and the valve and the compressor work in the opposite direction. Heat pumps are efficient in moderate temperatures, or when there is access to a medium that has a stable temperature or a differential. (Single package, or split, air-to-air, water-air, ground-air) |
|
|
Term
|
Definition
Absorption refrigeration uses the physical property of certain saline solutions to “suck” water vapor or moisture. Creating vapor (evaporation) results in cooling. Remember rubbing alcohol in your arms, and how its evaporation results in a cooling sensation? Salt used: Lithium Bromide. Heat is used to re-generate the saline solution. |
|
|
Term
|
Definition
Vapor is pulled from the evaporator by the “dry saline” (unsaturated) which becomes saturated. The evaporation lowers the temperature which can be used to extract heat from a space. Water is circulated from the system allowing the removal of heat and its release to the exterior. Heat sources can be the sun, gas, or waste heat. Double effect, and triple effect units add other evaporators/ condensers to increase the temperature drop, and increase the efficiency. Not as efficient as a compression unit. Chillers require a lot more space. Three LOOPS or circuits: purple, grey, and red/blue. |
|
|
Term
Local HVAC systems advantages |
|
Definition
Attractive when differences in schedule, function, and placement in the building are significant. Minimizes distribution (water or air) Greatly simplifies controls. Breakdowns only affect part of the building |
|
|
Term
Local HVAC systems disadvantages |
|
Definition
Energy, maintenance, air quality, noise |
|
|
Term
Local HVAC systems definition and types |
|
Definition
Independent, self-contained pieces of equipment are located in different places of the building. wall units roof top/single-package split unit |
|
|
Term
Central systems advantages |
|
Definition
Attractive when similarities in schedule, function, and placement in the building are significant. Saves energy, as the system is more efficient. Ease of centralized maintenance Air quality is easier to control Noise is easier to control Distribution is very important. (Water or air) Large trees. |
|
|
Term
Central systems disadvantages |
|
Definition
Conditioning is provided by large equipment situated in one or more mechanical spaces. |
|
|
Term
Central systems definition and types |
|
Definition
Room / space, complex controls, breakdowns affect part of the building all-air single duct, constant air volume all-air multi-duct, constant air volume (multi-zone) all-air, single duct, variable air volume air and water induction system all-water, fan coil terminals all water, closed loop heat pumps |
|
|
Term
|
Definition
Air occupies a larger volume of space, holds much less heat per unit of volume than water; at high velocities, noise can result. Water uses less space, so the refrigeration components can be separated from the spaces. |
|
|
Term
|
Definition
Q = AV Q - air volume in cfm A - area (section) of duct V - velocity factor: friction loss |
|
|
Term
|
Definition
Air moves because of a pressure differential. Air is a gas, so it is compressible |
|
|
Term
|
Definition
from 300 to 200 feet per minute Water is moved by pumps that also create a pressure delta. Water systems require the use of heat exchangers or coils. |
|
|
Term
|
Definition
inefficiency due to turns, and contact with duct walls |
|
|
Term
all-air, single duct, CAV |
|
Definition
Air is treated (heated or cooled, mixed with fresh air, filtered, de-humidified) at a central source. Supply and return are a simple circuit. A master (single!) thermostat controls the system for all the building. |
|
|
Term
all-air, single duct, CAV applications |
|
Definition
Buildings with large open spaces, uniform loads, few windows, uniform scheduling: theaters, department stores, exhibition halls. |
|
|
Term
all-air, single duct, CAV components |
|
Definition
A packaged system (central or split) could provide all parts, joining boiler, chiller, and air handler. |
|
|
Term
|
Definition
Each zone has a centrally conditioned, different temperature air supply, and these are separated. Chiller and boiler work at the same time, and hot and cool air are mixed before traveling to each zone, or re-heat coils at the fan room (air handler) regulate the temperature to accommodate independent needs. Single return system. Require larger space, specially for ductwork. |
|
|
Term
multi-duct system applications |
|
Definition
Medium sized buildings, or large buidlings with separate mechanical rooms for segments of the facility. |
|
|
Term
single duct, variable air volume |
|
Definition
Similar to single/constant, but with significant differences: Air is treated (heated or cooled, mixed with fresh air, filtered, de-humidified) at a central source. Air volume flow is controlled, instead of air temperature.) Supply and return are a simple circuit, but the building is separated in zones. Each zone has separate controls. |
|
|
Term
single duct, variable air volume - applications |
|
Definition
great system, widely used, and found in all type of buildings. Versatile! |
|
|
Term
single duct, variable air volume - Disadvantages |
|
Definition
limited range of temperatures (heating and cooling simultaneously), scheduling. |
|
|
Term
single duct, variable air volume - Variations |
|
Definition
Combined with a secondary system to provide perimeter supplement, to deal with large differences of temperature. |
|
|
Term
|
Definition
pipe coil or electrical resistance that rises temperature before the air is circulated to the zones, as needed. Allows a wider range of temperatures. |
|
|
Term
Secondary induction system |
|
Definition
smaller high velocity ducts allow treated air to be mixed with existing air at each zone, to reduce the size of the ductwork. |
|
|
Term
|
Definition
heated and cooled air run parallel, and are mixed at each zone |
|
|
Term
air-water induction system |
|
Definition
A high velocity, constant volume fresh air supply is brought to each terminal, where it is forced to circulate through an opening in such a way that the air in the space is induced (forced) to mix with the new flow. Temperature is obtained by the contact of air with hot or cold water in the induction unit. An equivalent amount is exhausted without returning to the air handler. Good circulation results, with only a small amount of treated air. Control is obtained via the water temperature or the circulation of air. |
|
|
Term
air-water induction system - applications |
|
Definition
It is used in spaces next to the exterior, with wide range of loads, and control of humidity is not critical. |
|
|
Term
air-water induction system - disadvantages |
|
Definition
Complicated, noisy, energy in-efficient, humidity control is not possible. |
|
|
Term
air-water induction system - components |
|
Definition
Chiller, boiler, double water tree, induction units, ductwork, exhaust system. |
|
|
Term
Fan coil system with supplementary air |
|
Definition
Fan coil units are familiar units located below windows. At each terminal, a fan mixes existing air with an exterior supply. It goes through a filter, and by water coils that heat or chill the air. A thermostat controls the water supply to the unit. |
|
|
Term
Fan coil system with supplementary air - applications |
|
Definition
Buildings with many zones, with varied schedules, and spaces along perimeter. Hotels, motels, schools, apartments, offices. |
|
|
Term
Fan coil system with supplementary air - advantages |
|
Definition
No fan room or ductwork inside the building. Temperature is individually controlled. |
|
|
Term
Fan coil system with supplementary air - disadvantages |
|
Definition
Maintenance in occupied spaces, humidity control, condensate piping. |
|
|
Term
|
Definition
Heat pumps draw heat from the loop or discharge heat to it, heating or cooling. In large buildings in cold weather, it is possible to obtain heat from the internal parts to heat the perimeter. In hot weather, a cooling tower might be used to discharge excessive heat. This can be considered an all water system. |
|
|
Term
closed loop heat pump - locations |
|
Definition
This can be an efficient system that does not occupy a lot of room. It allows for varied scheduling. |
|
|
Term
closed loop heat pump - advantages |
|
Definition
above ceilings, perimeter, or under windows. |
|
|
Term
closed loop heat pump - disadvantages |
|
Definition
It can be an expensive system to install, and requires maintenance in occupied areas. Requires temperate/ stable conditions, or warm water in winter and cool water in summer. |
|
|
Term
|
Definition
Building use Architecture and lay-out Cycles / Diversity of occupancy Control requirements Building scale Energy sources Climatic zone Initial cost Long term/ lifetime costs |
|
|
Term
air handler, chiller, boiler, and cooling tower - exchange loops |
|
Definition
Two heat exchange loops, one refrigeration loop: 1. Air/water to refrigerant (gas) 2. Refrigerant compression cycle. 3. Refrigerant to water-air. |
|
|
Term
air handler, chiller, boiler, and cooling tower - location of the refrigeration loop |
|
Definition
Having it compact and installed inside the chiller minimizes maintenance, but more important, reduces the potential for refrigerant leaks, simplifies refrigerant handling practices, and typically makes it easier to contain a leak if one occurs. |
|
|
Term
|
Definition
An air handler, or air handling unit (AHU), is a device used to condition and circulate air. Usually, an air handler is a large metal box containing a blower, heating and/or cooling elements, filter racks or chambers, sound attenuators, and dampers. Air handlers connect to ductwork that distributes the conditioned air through the building, and returns it to the AHU. Can mix fresh and return air. The cooling coils in the air handler transfer sensible heat and latent heat from the air to the chilled water, thus cooling and usually dehumidifying the air stream. |
|
|
Term
|
Definition
complex refrigeration machine, and a heat exchanger. It removes heat from a liquid using compression or absorption. The water that is chilled may also contain 20% glycol and corrosion inhibitors. The chilled water is used to cool and dehumidify air in the air handler units or equivalent. The heat is extracted via a water loop and a cooling tower, or heat from the water is cooled using air. Most chillers are designed for indoor operation, but some are weather-resistant. Chillers are precision machines that are very expensive to purchase and operate. There are air chillers that do not require a cooling tower. These eliminate the third loop, releasing heat from the refrigerant directly to the air, using a fan. |
|
|
Term
|
Definition
Cooling towers are heat removal devices used to transfer process waste heat to the exterior air. Cooling towers may either use the evaporation of water to remove heat and cool the working fluid to near the wet-bulb air temperature or rely solely on air to cool the working fluid to near the dry-bulb air temperature. Water cascades inside a louvered box that uses a fan to increase air movement and maximize contact of the water with it. There are vertical ones, and cross-flow ones. |
|
|
Term
Cooling towers - disadvantages |
|
Definition
Create a microclimate and are noisy. Fog can occur in cold weather. Corrosion and biological problems are issues. Water needs to be replaced on a regular basis, as it escapes via evaporation. |
|
|
Term
Closed circuit evaporative cooler |
|
Definition
no water, direct refrigerant, enclosed cooling water box. |
|
|
Term
|
Definition
VAV box, is control device that manages flow at the zone-level. It is a calibrated air damper with an automatic actuator. The VAV terminal unit is connected to either a local or a central control system. Historically, pneumatic control was commonplace, but electronic direct digital control systems are popular especially for mid-to-large size applications. Hybrid control, for example having pneumatic actuators with digital data collection, is popular as well. Control of the system's fan capacity (VARIABLE FAN SPEED) is critical in VAV t With systems. Without proper and rapid flow rate control, the system's ductwork, or its sealing, can easily be damaged by over-pressurization. However, the fan capacity control is the primary advantage of VAV systems, especially with modern electronic variable speed drives, because the energy consumed by fans is a substantial part of the total cooling energy requirements of a building |
|
|