Term
Gen
Describe the normal H2 gas pressure. |
|
Definition
|
|
Term
Gen
Describe the isophase bus cooling flow path. |
|
Definition
Down the "B" phase and returns on the "A" and "C" phases. |
|
|
Term
Describe what is used to purge the generator. |
|
Definition
CO2 used to purge then followed by air to prevent explosive air H2 mixture. |
|
|
Term
Gen
Describe the exciter reservoir alarm setpoint. |
|
Definition
|
|
Term
Gen
Describe what service water cools in regard to the generator. |
|
Definition
-Stator water cooling. -H2 gas coolers. -Exciter air cooler. -Isophase bus cooler. |
|
|
Term
Gen
Describe isophase bus cooling. |
|
Definition
-Self cooling below 10,500 amps for 10 minutes at EPU rated load of 718MW. |
|
|