Shared Flashcard Set

Details

Circulation Water
ILT '09
31
Other
Not Applicable
03/01/2008

Additional Other Flashcards

 


 

Cards

Term
Function of Circ water system
Definition
Remove heat energy from plant cycle in the main condenser and dissipate this energy to the river or to the atmosphere via cooling towers.
Term
Flow, above which open (circ water) cycle is used.
Definition
Open cycle operation is used when river flow is above 860 CFS and cooling of the circ water effluent is not required to keep the max daily average discharge canal temperature below limit.
Term
Flow limit below which power operation is not allowed
Definition
240 CFS
Term
Daily average maximum flow appropriation
Definition
645 cfs provided river flow is at or above 860 cfs. Otherwise, 75% of river flow (when below 860 cfs).
Term
When should traveling screens be set for automatic operation?
Definition

Any time the Circ water or Service Water systems are operating.

 

NOTE: Above 50 degrees F, traveling screens are to be placed in continuous operation when circ pumps are operating.

Term
Whenever upstream river temperature is 50 degrees F or below, what is the limit in temperature change?
Definition
Should not drop more than 5 degrees F in one hour. (fish can sweat, but they can't freeze)
Term
With upstream river temperature at or below 50 degrees F, what conditions require ERAD-Supervisor notification?
Definition
  1. A complete shutdown is anticipated;
  2. A scram occurs;
  3. The 5 degree F per hour drop limit is exceeded.
Term
Whenever upstream river temperature is above 50 degrees, what is the limit in temperature change?
Definition

Discharge canal temperature may rise or drop at any rate (no limitations).

Term
When should de-icing line be open and the EPA Hot Water Pumps placed in service?
Definition

When the river inlet temperature is

below 35 degrees F.

Term
Power supply to 11 Circ Water Pump Motor
Definition
Bus 13
Term
Power supply to 12 Circ Water Pump Motor
Definition
Bus 14
Term
Power supply to 11 Circ Water Pump Motor Exciter
Definition
MCC-112
Term
Power supply to 12 Circ Water Pump Motor Exciter
Definition
MCC-121
Term
Power supply to 11 Circ Pump Discharge Valve
Definition
MCC-123
Term
Power supply to 12 Circ Pump Discharge Valve
Definition
MCC-113
Term
Power supply to Condenser discharge and inlet valves
Definition
All four come off MCC-131
Term
CW pump will start only if…
Definition
Discharge valve is closed. First pump to start requires both discharge valves closed.
Term
Cooling tower pump sequence
Definition

Switch to start:

  1. Pump starts immediately, 10 seconds later discharge valve jogs open (2 seconds jog, 8 second wait);
  2. If valve not full open in 3 to 4 minutes, another timer inhibits valve movement.
Term
First circ pump start sequence
Definition

Upon taking control switch to PUMP START position:

  1. Both condenser outlet valves move to intermediate-high position;
  2. Pump starts (against a closed discharge valve);
  3. Five seconds after pump start, discharge valve opens (designed to open in 20 seconds).
Term
Second circ pump start sequence
Definition

Upon taking control switch to PUMP START position:

  1. Pump starts (against a closed discharge valve);
  2. Five seconds after pump starts the following simultaneously occur:
    • Discharge valve begins to open;
    • Both condenser discharge valves begin to move to their fully open position.
Term
First circ pump shutdown sequence
Definition

Upon taking control switch to SHUTDOWN position:

  1. Both condenser outlet valves move to intermediate-high flow position;
  2. Pump discharge valve starts moving to the fully closed position;
  3. Upon discharge valve full closed, pump trips.
Term
Second circ pump shutdown sequence
Definition

Upon taking control switch to SHUTDOWN position:

  1. Both condenser outlet valves move from intermediate-high flow to intermediate-low position;
  2. Pump discharge valve starts moving to the fully closed position;
  3. When discharge valve is fully closed, pump trips and both condenser outlet valves fully close.
Term
What protects the circ water system from overpressurization on column recovery following an automatic trip of one or two circ water pumps (which may induce column separation)?
Definition
Automatic air admission valves at the condenser water boxes.
Term
How is column separation during manual shutdown of circ water pump avoided?
Definition
Condenser outlet valves automatically moving to intermediate-high flow position.
Term
Describe the circ water pit flooding setpoints
Definition
  • Alarm (only): 1 foot;
  • Alarm and Circ water pump(s) trip: 4 feet.
Term
Describe the condenser pit flooding setpoints
Definition
  • Alarm (only): 1 foot;
  • Alarm and Circ water pump(s) trip: 2 feet, 6 inches.
Term
What is ERAD's interpretation of consistently?
Definition

3 consecutive days.

 

Specifically, "all available cooling water equipment SHALL be placed in the helper mode when the daily average upstream river temp is anticipated to be at or above 68 degrees F for 3 consecutive days."

Term
Daily average temperature at the end of the discharge canal limit during April - October (summer).
Definition
35 degrees C (95 degrees F)
Term
Daily average temperature at the end of the discharge canal limit during November and March
Definition
29.4 degrees C (85 degrees F)
Term
Daily average temperature at the end of the discharge canal limit during December through February (winter)
Definition
26.7 degrees C (80 degrees F)
Term
Halogen discharge concentration limit
Definition
"SHALL NOT at any time exceed 0.2 mg/L measured as total residual Halogen, and the discharge of Halogenated water SHALL NOT exceed a total of 2 hours per day."
Supporting users have an ad free experience!