Term
Circ
Describe open cycle operation. |
|
Definition
Flows through discharge structure to an open canal which conveys it to the river downstream the intakes. |
|
|
Term
Circ
Describe closed cycle operation. |
|
Definition
-River is isolated by control gates. -Effluent from the cooling towers flows by gravity from the cooling tower basins to the suction chambers of the circ water pumps. -Blowdown overflows through weirs at the cooling tower basins and is piped from there to the discharge canal. - |
|
|
Term
Circ
Describe when open cycle is used. |
|
Definition
-River flow above 860CFS and cooling of circ water effluent not required to keep max daily average discharge canal below the limit. |
|
|
Term
Circ
Describe when helper cycle is used. |
|
Definition
When upstream temp consistently reaches 68F or when daily average discharge canal approaches the limits. |
|
|
Term
Circ
Describe helper cycle operation. |
|
Definition
-Taken from intake, through condenser, to discharge structure where some is sent to canal and some is lifted to the cooling towers. -Cooled effluent collects in basin and overflows the weirs and flows to discharge canal. |
|
|
Term
Circ
Describe when partial recirculation is used. |
|
Definition
River flows less than 860CFS, 75% of flow may be appropriated. |
|
|
Term
Circ
Describe partial recirculation operation. |
|
Definition
-Same as helper cycle only some of the cooled effluent is gated back to the intake structure. -Both intake and discharge gates are full open. -Discharge canal temp limits may be exceded. |
|
|
Term
Circ
Describe when closed cycle is used. |
|
Definition
Whenever river flow is equal or greater than 240CFS. |
|
|
Term
Circ
Describe what takes suction from the service water bay. |
|
Definition
-2 make up pumps. -3 service water pumps. -4 RHR service water pumps. -Screen wash and the fire protection pumps. |
|
|
Term
Circ
Describe the trash rake alarms and interlock. |
|
Definition
-High D/P alarm. -Cannot move the trash rake along the rails unless the rake carriage is in the UP position. |
|
|
Term
Circ
Describe when traveling screens are required to be in operation. |
|
Definition
Whenever river temp is above 50F. |
|
|
Term
Circ
Describe the traveling screens auto functions. |
|
Definition
-High D/P setpoint the screen wash pump starts and screens start at low speed (2rpm). -High high D/P screens go to high speed (6rpm). -If condition exists for 4-5 minutes then an alarm actuates. |
|
|
Term
Circ
Describe the screen wash and fire protection interlock. |
|
Definition
If fire header pressure lowers to 70psig for 10 seconds, alarm actuates and screen wash/fire pump starts and stops spray to screen wash and stops screens. |
|
|
Term
Circ
Describe the power supply to the circ water pumps. |
|
Definition
-11 pump from 13 bus. -12 pump from 14 bus. -Discharge valves from MCC-123 and MCC-113. |
|
|
Term
Circ
Describe the pump starting interlocks. |
|
Definition
-CW pump will only start if its discharge valve is shut. -To start a CW pump if both are secured both discharge valves must be shut. -If discharge valve is opened when its CWP is secured the valve will auto close after reaching full open. |
|
|
Term
Circ
Describe the CT pump start interlocks. |
|
Definition
-To start a second pump its discharge must be full shut and the running pumps discharge must be full open. |
|
|
Term
Circ
Describe the CT pump starting sequence. |
|
Definition
-Pump starts and 10 second timer starts. -After 10 seconds the valve jogs open for 2 seconds and waits for 8 seconds. -This continues until full open. -If after 3-4 minutes and still not full open the jogging is stopped by a second timer. |
|
|
Term
Circ
Describe the CT pump shutdown sequence. |
|
Definition
-Take switch to Valve Close. -Valve goes full closed then CT pump trips off. |
|
|
Term
Circ
Describe the condenser outlet valve interlocks. |
|
Definition
-To secure a CW pump if a condenser outlet is closed, then the open valve must be in AUTO. -CW pump cannot be started if one of the condenser outlet valves is closed. |
|
|
Term
Circ
Describe the CW pump start sequence. |
|
Definition
-First pump taken to START. -Move condenser outlet valves go to intermediate-high. -Pump starts with its discharge valve shut. -5 seconds later its discharge valve opens (20 second travel time). -Second pump to START. -Pump starts. -5 seconds and its discharge valve starts to open. -Simultaneously both condenser outlet valves start going full open. |
|
|
Term
Circ
Describe the CW pump shutdown sequence. |
|
Definition
-First to SHUTDOWN. -Both condenser outlet valves go to intermediate-high. -Then pump discharge valve goes full closed. -When full closed the pump trips. -Second pump to SHUTDOWN. -Both condenser outlets go to intermediate-low position. -Pump discharge goes full closed. -When full closed the pump trips. -Both condenser discharge go to closed. |
|
|
Term
Circ
Describe how the CW and CT pump trips are interlocked. |
|
Definition
-If CT pump trips then CW pump trips and vice versa when in closed cycle. |
|
|
Term
Circ Describe the CW and condenser pit flooding interlocks. |
|
Definition
-CW pit level reaches 1' get alarm. -CW pit level 4' alarm and CW pumps trip. -Works same for condenser pit except trip is 2'6". |
|
|
Term
Circ
Describe the discharge canal temperature limits. |
|
Definition
-April through October: 95F. -November and March: 85F. -December through February: 80F. |
|
|