Shared Flashcard Set

Details

Circulating Water (Circ)
BWR Systems
24
Other
Not Applicable
07/05/2012

Additional Other Flashcards

 


 

Cards

Term
Circ

Describe open cycle operation.
Definition
Flows through discharge structure to an open canal which conveys it to the river downstream the intakes.
Term
Circ

Describe closed cycle operation.
Definition
-River is isolated by control gates.
-Effluent from the cooling towers flows by gravity from the cooling tower basins to the suction chambers of the circ water pumps.
-Blowdown overflows through weirs at the cooling tower basins and is piped from there to the discharge canal.
-
Term
Circ

Describe when open cycle is used.
Definition
-River flow above 860CFS and cooling of circ water effluent not required to keep max daily average discharge canal below the limit.
Term
Circ

Describe when helper cycle is used.
Definition
When upstream temp consistently reaches 68F or when daily average discharge canal approaches the limits.
Term
Circ

Describe helper cycle operation.
Definition
-Taken from intake, through condenser, to discharge structure where some is sent to canal and some is lifted to the cooling towers.
-Cooled effluent collects in basin and overflows the weirs and flows to discharge canal.
Term
Circ

Describe when partial recirculation is used.
Definition
River flows less than 860CFS, 75% of flow may be appropriated.
Term
Circ

Describe partial recirculation operation.
Definition
-Same as helper cycle only some of the cooled effluent is gated back to the intake structure.
-Both intake and discharge gates are full open.
-Discharge canal temp limits may be exceded.
Term
Circ

Describe when closed cycle is used.
Definition
Whenever river flow is equal or greater than 240CFS.
Term
Circ

Describe what takes suction from the service water bay.
Definition
-2 make up pumps.
-3 service water pumps.
-4 RHR service water pumps.
-Screen wash and the fire protection pumps.
Term
Circ

Describe the trash rake alarms and interlock.
Definition
-High D/P alarm.
-Cannot move the trash rake along the rails unless the rake carriage is in the UP position.
Term
Circ

Describe when traveling screens are required to be in operation.
Definition
Whenever river temp is above 50F.
Term
Circ

Describe the traveling screens auto functions.
Definition
-High D/P setpoint the screen wash pump starts and screens start at low speed (2rpm).
-High high D/P screens go to high speed (6rpm).
-If condition exists for 4-5 minutes then an alarm actuates.
Term
Circ

Describe the screen wash and fire protection interlock.
Definition
If fire header pressure lowers to 70psig for 10 seconds, alarm actuates and screen wash/fire pump starts and stops spray to screen wash and stops screens.
Term
Circ

Describe the power supply to the circ water pumps.
Definition
-11 pump from 13 bus.
-12 pump from 14 bus.
-Discharge valves from MCC-123 and MCC-113.
Term
Circ

Describe the pump starting interlocks.
Definition
-CW pump will only start if its discharge valve is shut.
-To start a CW pump if both are secured both discharge valves must be shut.
-If discharge valve is opened when its CWP is secured the valve will auto close after reaching full open.
Term
Circ

Describe the CT pump start interlocks.
Definition
-To start a second pump its discharge must be full shut and the running pumps discharge must be full open.
Term
Circ

Describe the CT pump starting sequence.
Definition
-Pump starts and 10 second timer starts.
-After 10 seconds the valve jogs open for 2 seconds and waits for 8 seconds.
-This continues until full open.
-If after 3-4 minutes and still not full open the jogging is stopped by a second timer.
Term
Circ

Describe the CT pump shutdown sequence.
Definition
-Take switch to Valve Close.
-Valve goes full closed then CT pump trips off.
Term
Circ

Describe the condenser outlet valve interlocks.
Definition
-To secure a CW pump if a condenser outlet is closed, then the open valve must be in AUTO.
-CW pump cannot be started if one of the condenser outlet valves is closed.
Term
Circ

Describe the CW pump start sequence.
Definition
-First pump taken to START.
-Move condenser outlet valves go to intermediate-high.
-Pump starts with its discharge valve shut.
-5 seconds later its discharge valve opens (20 second travel time).
-Second pump to START.
-Pump starts.
-5 seconds and its discharge valve starts to open.
-Simultaneously both condenser outlet valves start going full open.
Term
Circ

Describe the CW pump shutdown sequence.
Definition
-First to SHUTDOWN.
-Both condenser outlet valves go to intermediate-high.
-Then pump discharge valve goes full closed.
-When full closed the pump trips.
-Second pump to SHUTDOWN.
-Both condenser outlets go to intermediate-low position.
-Pump discharge goes full closed.
-When full closed the pump trips.
-Both condenser discharge go to closed.
Term
Circ

Describe how the CW and CT pump trips are interlocked.
Definition
-If CT pump trips then CW pump trips and vice versa when in closed cycle.
Term
Circ Describe the CW and condenser pit flooding interlocks.
Definition
-CW pit level reaches 1' get alarm. -CW pit level 4' alarm and CW pumps trip. -Works same for condenser pit except trip is 2'6".
Term
Circ

Describe the discharge canal temperature limits.
Definition
-April through October: 95F.
-November and March: 85F.
-December through February: 80F.
Supporting users have an ad free experience!