Term
A low-pressure steam boiler has a maximum allowable working pressure (MAWP) of up to:
15 psi
Exam 1 Steam Boilers |
|
Definition
|
|
Term
In a fire tube boiler, the heat and gases of combustion pass:
through the tubes
Exam 1 Steam Boilers
|
|
Definition
|
|
Term
A fire tube boiler may be used:
in high or low pressure plants
Exam 1 Steam Boilers
|
|
Definition
|
|
Term
Because of the large volume of water, the boiler most likely to cause a boiler explosion is:
a fire tube boiler
Exam 1 Steam Boilers
|
|
Definition
|
|
Term
A horizontal return tubular (HRT) boiler is:
fire tube boiler
Exam 1 Steam Boilers
|
|
Definition
|
|
Term
A sudden drop in boiler steam pressure without a corresponding drop in boiler water temperature could result in:
a boiler explosion
Exam 1 Steam Boilers
|
|
Definition
|
|
Term
The part of a boiler that has the heat and gases of combustion on one side and water on the other side is known as the:
heating surface
Exam 1 Steam Boilers
|
|
Definition
|
|
Term
The comparison, or ratio, of heat supplied in fuel to heat absorbed by water is defined as:
thermal efficiency
Exam 1 Steam Boilers |
|
Definition
|
|
Term
The steam and water drum of water tube boilers is dished (concave) to eliminate the need for:
stays
Exam 1 Steam Boilers
|
|
Definition
|
|
Term
Vertical fire tube boilers require:
high ceilings, less floor space and the use of stay bolts
Exam 1 Steam Boilers |
|
Definition
|
|
Term
In a water tube boiler, the heat and gases of combustion pass:
around the tubes
Exam 1 Steam Boilers |
|
Definition
|
|
Term
The ___________ boiler has a large volume of water in relation to horse power size.
fire tube
Exam 1 Steam Boilers
|
|
Definition
|
|
Term
The mudroom is the lowest part of the water side of a:
water tube boiler
Exam 1 Steam Boilers |
|
Definition
|
|
Term
Boiler plates and stay bolts are subject to:
tensile stress
Exam 1 Steam Boilers
|
|
Definition
|
|
Term
Safety valve connections must be approved by the:
Answer American society of mechanical engineers (ASME)
Exam 1 Steam Boilers
|
|
Definition
|
|
Term
The most important fitting on a boiler is the:
safety valve
Exam 2 Steam Boilers & Fittings
|
|
Definition
|
|
Term
To prevent failure from pressure over the MAWP, all steam boilers must be equipped with at least one:
safety valve
Exam 2 Steam Boilers & Fittings
|
|
Definition
|
|
Term
A safety valve will:
prevent the boiler from exceeding its MAWP
Exam 2 Steam Boilers & Fittings |
|
Definition
|
|
Term
Safety valves are designed to:
pop open
Exam 2 Steam Boilers & Fittings
|
|
Definition
|
|
Term
Super heater safety valves are set to open:
before the main safety valves are opened
Exam 2 Steam Boilers & Fittings |
|
Definition
|
|
Term
When testing a safety valve by hand, there must be:
at least 75% of the popping pressure
Exam 2 Steam Boilers & Fittings
|
|
Definition
|
|
Term
Any repairs to a safety valve should be done by the:
safety valve manufacturer or manufactures authorized representative
Exam 2 Steam Boilers & Fittings
|
|
Definition
|
|
Term
The setting or adjusting of a safety valve should only be done by the:
qualified person who is familiar with the construction and operation of a safety valve
Exam 2 Steam Boilers & Fittings |
|
Definition
|
|
Term
If it is necessary to test the relieving capacity of a safety valve:
an accumulation test is put on the boiler
Exam 2 Steam Boilers & Fittings
|
|
Definition
|
|
Term
The relieving capacity of a safety valve is measured in:
pounds of steam per hour capable of discharging under a given pressure
Exam 2 Steam Boilers & Fittings
|
|
Definition
|
|
Term
The main purpose of a water column is to:
reduce turbulence in the gauge glass and to get more accurate reading of the water level in the boiler
Exam 2 Steam Boilers & Fittings |
|
Definition
|
|
Term
Try cocks are:
a secondary means of determining water level in a boiler
Exam 2 Steam Boilers & Fittings
|
|
Definition
|
|
Term
The water column and gauge glass should usually be blown down:
once a shift
Exam 2 Steam Boilers & Fittings |
|
Definition
|
|
Term
A steam pressure gauge is calibrated in:
pounds per square inch (PSI)
Exam 2 Steam Boilers & Fittings |
|
Definition
|
|
Term
A siphon protects the steam pressure gauge from:
high temperature of steam
Exam 2 Steam Boilers & Fittings |
|
Definition
|
|
Term
The pressure at the base of a vertical foot of water is:
0.433 PSI
Exam 2 Steam Boilers & Fittings |
|
Definition
|
|
Term
The boiler vent is located at the:
highest part of the steam side of the boiler
Exam 2 Steam Boilers & Fittings
|
|
Definition
|
|
Term
The boiler vent is open when warming up a boiler until:
there is 10 to 15 psi of steam pressure on the boiler
Exam 2 Steam Boilers & Fittings
|
|
Definition
|
|
Term
Saturated steam is steam at:
its corresponding temperature and pressure
Exam 2 Steam Boilers & Fittings
|
|
Definition
|
|
Term
When steam is superheated the:
temperature increases with no increase in pressure
Exam 2 Steam Boilers & Fittings |
|
Definition
|
|
Term
Soot should be:
removed from boiler tubes for better heat transfer
Exam 2 Steam Boilers & Fittings |
|
Definition
|
|
Term
Boilers in battery equipped with manhole openings must have ___________ according to the ASME code.
two main steam stop valves
Exam 2 Steam Boilers & Fittings |
|
Definition
|
|
Term
Main boiler stop valves must be:
os&y gate (outside stem & yoke)
Exam 2 Steam Boilers & Fittings
|
|
Definition
|
|
Term
The ASME Code will allow an automatic non-return valve to be used as a main steam stop valve. If one is used it must be:
installed as close to the shell of the boiler as practical on the main steam line
Exam 2 Steam Boilers & Fittings
|
|
Definition
|
|
Term
The main steam stop valve should be gate valves because they:
offer no restriction to the flow of steam
Exam 2 Steam Boilers & Fittings |
|
Definition
|
|
Term
When the boiler is equipped with hand operated, main steam stop valves, to cut the boiler in on the line, the steam pressure on the incoming boiler should be:
slightly lower than line pressure
Exam 2 Steam Boilers & Fittings
|
|
Definition
|
|
Term
When a boiler is being inspected, the two main steam stop valves are:
closed, locked, and tagged
Exam 2 Steam Boilers & Fittings
|
|
Definition
|
|
Term
During boiler warm-up, to remove any condensate trapped between the two boiler stop valves the:
free blowing drain should be open
Exam 2 Steam Boilers & Fittings
|
|
Definition
|
|
Term
According to the ASME code, boilers operating at 100 psi or over must have:
2 bottom blowdown valves
Exam 2 Steam Boilers & Fittings
|
|
Definition
|
|
Term
When blowing down a boiler equipped with a quick opening valve and a screw type valve, the quick opening valve is:
opened first and closed last
Exam 2 Steam Boilers & Fittings
|
|
Definition
|
|
Term
If a quick opening valve is used as a bottom blowdown valve, it must be located:
between the boiler and the slow opening (screw type) valve
Exam 2 Steam Boilers & Fittings |
|
Definition
|
|
Term
The maximum size of the bottom blowdown line and the surface blow down line is:
2.5"
Exam 2 Steam Boilers & Fittings |
|
Definition
|
|
Term
Bottom blowdown lines on a water tube boiler are located on the:
mud drum
Exam 2 Steam Boilers & Fittings |
|
Definition
|
|
Term
The most accurate means of deciding the frequency of blowdown of a boiler is determined by a:
boiler water analysis
Exam 2 Steam Boilers & Fittings
|
|
Definition
|
|
Term
Oxygen and other non-condensable gases are separated from the feed water:
in the open deaerator feed water heater
Exam 3 Boiler Room Systems
|
|
Definition
|
|
Term
The four systems required to operate a steam boiler are:
steam, feed water, fuel, & draft
Exam 3 Boiler Room Systems
|
|
Definition
|
|
Term
In order to produce 1 pound of steam, it is necessary to evaporate:
1 pound of water
Exam 3 Boiler Room Systems
|
|
Definition
|
|
Term
Steam that has lost its heat and has turned back into water is:
condensate
Exam 3 Boiler Room Systems
|
|
Definition
|
|
Term
A safe and efficient boiler plant should include __________ pumps.
one steam & one electric feed water
Exam 3 Boiler Room Systems
|
|
Definition
|
|
Term
On a boiler burning low pressure gas, the volume (amount) of gas burned is controlled by the:
volume of air passing through the Venturi tube
Exam 3 Boiler Room Systems
|
|
Definition
|
|
Term
On the fuel oil system, the purpose of the duplex strainers on the suction line between the tank and fuel pump is to:
allow the strainer to be cleaned without securing the boiler
Exam 3 Boiler Room Systems
|
|
Definition
|
|
Term
A draft fan located between the boiler and chimney is used in a:
induced draft system
Exam 3 Boiler Room Systems
|
|
Definition
|
|
Term
The open feed water heater is located:
above the feed water pumps
Exam 3 Boiler Room Systems
|
|
Definition
|
|
Term
Number ____ fuel oil must be heated in order to be pumped.
6
Exam 3 Boiler Room Systems
|
|
Definition
|
|
Term
Pulverized coal has the consistency of talcum powder so that it:
can come in closer contact with the oxygen for complete combustion
Exam 3 Boiler Room Systems
|
|
Definition
|
|
Term
Draft is defined as a difference in pressure that causes:
Air or gasses to flow
Exam 3 Boiler Room Systems
|
|
Definition
|
|
Term
Air is mixed inside the burner register in a:
high-pressure gas system
Exam 3 Boiler Room Systems
|
|
Definition
|
|
Term
Natural draft is produced by a:
difference in temperature of a column of gas inside the chimney from a column air outside the chimney
Exam 3 Boiler Room Systems
|
|
Definition
|
|
Term
Pulverized coal is burned in _______ in the furnace.
suspension
Exam 3 Boiler Room Systems
|
|
Definition
|
|
Term
Gas leaks should be located and repaired by a:
gas company representative
Exam 3 Boiler Room Systems
|
|
Definition
|
|
Term
If a boiler that was online is down because of low steam pressure, the cause is:
either a flame failure or low-water condition
Exam 3 Boiler Room Systems
|
|
Definition
|
|
Term
When performing a hydrostatic test the pressure on the boiler should be increased to:
1½ Times the safety valve setting
Exam 3 Boiler Room Systems
|
|
Definition
|
|
Term
A furnace explosion can be caused by:
an accumulation of combustible gases
Exam 3 Boiler Room Systems
|
|
Definition
|
|
Term
The ASME code requires that boilers be inspected internally and externally every:
year
Exam 3 Boiler Room Systems
|
|
Definition
|
|
Term
When someone finds an unsafe condition in a plant, that person should report it to:
The immediate supervisor
Exam 3 Boiler Room Systems
|
|
Definition
|
|
Term
A fire that is caused by oil, gas, grease, or paint would be classified as a class:
B fire
Exam 3 Boiler Room Systems
|
|
Definition
|
|
Term
The low-water fuel cut off control should be blown down:
once a shift
Exam 3 Boiler Room Systems
|
|
Definition
|
|
Term
The automatic city water make up valve found on an open feed water heater is used to:
maintain a water level in the feed water heater if there are insufficient condensate returns
Exam 4: Steam & Water Accessories
|
|
Definition
|
|
Term
The purpose of a feed water regulator is to:
maintain a consistent water level in the boiler
Exam 4: Steam & Water Accessories
|
|
Definition
|
|
Term
The sequence of three numbers found on the data plate attached to a reciprocating feed water pump indicates the:
diameter of steam piston, diameter of water piston, and length of pump stroke
Exam 4: Steam & Water Accessories
|
|
Definition
|
|
Term
A reciprocating feed water pump must have a safety relief valve located between the:
pump and the discharge valve
Exam 4: Steam & Water Accessories
|
|
Definition
|
|
Term
An economizer is used in large boiler plants to heat:
Feed water using gases of combustion
Exam 4: Steam & Water Accessories
|
|
Definition
|
|
Term
Centrifugal feed water pumps can be started with their discharge valves:
Open or closed
Exam 4: Steam & Water Accessories
|
|
Definition
|
|
Term
Water temperature that is too high in the open feed water heater could cause:
The feed water pump to become steam bound
Exam 4: Steam & Water Accessories
|
|
Definition
|
|
Term
Water temperature that is too low in the open feed water heater could cause:
oxygen pitting in the boiler
Exam 4: Steam & Water Accessories
|
|
Definition
|
|
Term
In a low pressure gas burner, a __________ shuts off the gas supply if a little water condition exists.
manual reset valve
Exam 5: Fuel Burning Equipment
|
|
Definition
|
|
Term
An indication of a dirty fuel oil strainer would be ________ across the strainer.
A large pressure drop
Exam 5: Fuel Burning Equipment
|
|
Definition
|
|
Term
Duplex strainers are found on ___________ of the fuel oil pump.
both the suction and discharge sides
Exam 5: Fuel Burning Equipment
|
|
Definition
|
|
Term
Fuel oil heaters must be used when burning number ____ fuel oil.
6
Exam 5: Fuel Burning Equipment
|
|
Definition
|
|
Term
A gas pressure regulator is used to control the:
desired pressure at the burner
Exam 5: Fuel Burning Equipment
|
|
Definition
|
|
Term
A solenoid valve is a direct acting valve in the gas system and is used:
as an automatic gas shut off valve
Exam 5: Fuel Burning Equipment
|
|
Definition
|
|
Term
Blowers are used in high-pressure gas system to:
supply air for combustion
Exam 5: Fuel Burning Equipment
|
|
Definition
|
|
Term
The air-to-gas ratio is maintained by a:
Air damper, butterfly valve, modulating motor and linkage
Exam 5: Fuel Burning Equipment
|
|
Definition
|
|
Term
The gas pressure reducing valve in the low pressure gas system produces the gas pressure to:
Zero PSI
Exam 5: Fuel Burning Equipment
|
|
Definition
|
|
Term
Boilers are equipped with a combination gas/fuel oil burner for:
more flexible operation
Exam 5: Fuel Burning Equipment
|
|
Definition
|
|
Term
Pulverized coal burns:
in suspension
Exam 5: Fuel Burning Equipment
|
|
Definition
|
|
Term
The volume of gas to the burner in a high-pressure gas system is controlled by a:
butterfly valve
Exam 5: Fuel Burning Equipment
|
|
Definition
|
|
Term
In order to burn 1 lb of fuel, approximately ______ lb of air is needed.
15
Exam 6: Draft
|
|
Definition
|
|
Term
Draft is measured in:
inches or tenths of an inch of a vertical water column
Exam 6: Draft
|
|
Definition
|
|
Term
To reduce the heat loss of flue gas going to the chimney, boilers are equipped with:
economizers and air heaters
Exam 6: Draft
|
|
Definition
|
|
Term
The amount of draft available in a natural draft system is dependent on the:
height of the chimney
Exam 6: Draft
|
|
Definition
|
|
Term
The gases of combustion leaving a boiler that has natural draft are controlled by:
outlet dampers
|
|
Definition
|
|
Term
Rank refers to the _______ of the coal.
degree of hardness
Exam 7: Combustion
|
|
Definition
|
|
Term
Bituminous coal has a high _______ content.
volatile
Exam 7: Combustion
|
|
Definition
|
|
Term
Anthracite coal has a high ________ content.
carbon
Exam 7: Combustion
|
|
Definition
|
|
Term
_______ coal is the type of coal most likely to have problems with spontaneous combustion when being stockpiled.
Bituminous
Exam 7: Combustion
|
|
Definition
|
|
Term
Air that controls the combustion efficiency is:
secondary air
Exam 7: Combustion
|
|
Definition
|
|
Term
Air supply to the burner that is more than the theoretical amount needed to burn fuel is:
excess air
Exam 7: Combustion
|
|
Definition
|
|
Term
Air needed for the combustion of fuel is made up of approximately ____% oxygen and ____% nitrogen.
21; 79
Exam 7: Combustion
|
|
Definition
|
|
Term
Number ____ fuel oil must be heated to reach the required temperature for combustion.
6
Exam 7: Combustion
|
|
Definition
|
|
Term
Higher numbered fuel oil's produce ______ lower number fuel oils.
more BTU per gallon then
Exam 7: Combustion
|
|
Definition
|
|
Term
The heating value of a fuel is expressed in:
British thermal units (BTU)
Exam 7: Combustion
|
|
Definition
|
|
Term
The on / off pressure control must be connected to the:
highest part of the steam side of the boiler
Exam 8: Combustion Controls
|
|
Definition
|
|
Term
A steam siphon ensures that ______ does not enter the boiler pressure control.
steam
Exam 8: Combustion Controls
|
|
Definition
|
|
Term
Mercury-tube pressure control will only be accurate when it is installed:
in a vertical position
Exam 8: Combustion Controls
|
|
Definition
|
|
Term
The two scales found on the boiler pressure control are used to:
set the operating steam pressure range of the boiler
Exam 8: Combustion Controls
|
|
Definition
|
|
Term
The purpose of the boiler modulating pressure control is to:
regulate the high and low firing rates of the burner
Exam 8: Combustion Controls
|
|
Definition
|
|
Term
To eliminate the danger of a furnace explosion deeming start up, the firing sequence must first allow for:
a pre-purge period
Exam 8: Combustion Controls
|
|
Definition
|
|
Term
The purpose of the scanner is to provide:
both the pilot & the main flame
Exam 8: Combustion Controls
|
|
Definition
|
|
Term
The positioning combustion control system used on older boilers cannot function without:
Air pressure
Exam 8: Combustion Controls
|
|
Definition
|
|
Term
The metering combustion control system is sensitive to changes in:
steam flow and pressure
Exam 8: Combustion Controls
|
|
Definition
|
|
Term
The positioning combustion control system is sensitive to changes in the:
steam header
Exam 8: Combustion Controls
|
|
Definition
|
|
Term
Absolute pressure is equal to:
gauge pressure plus atmospheric pressure
Exam 9: Instruments
|
|
Definition
|
|
Term
A boiler steam pressure gauge should have a range of:
1&1/2 to 2 times the safety valve setting
Exam 9: Instruments
|
|
Definition
|
|
Term
The boiler steam pressure gauge must be connected to the _______ of the boiler.
highest part of the steam side
Exam 9: Instruments
|
|
Definition
|
|
Term
The boiler steam pressure gauge is protected from high temperatures by:
A siphon
Exam 9: Instruments
|
|
Definition
|
|
Term
Liquids in a tank maybe measured from a remote location using a:
pneumercator
Exam 9: Instruments
|
|
Definition
|
|
Term
The rotameter flow meter consists of a:
float in a tapered tube
|
|
Definition
|
|
Term
Boiler water must be conditioned to prevent:
formation of scale, oxygen pitting, & carryover
Exam 10: Boiler Water Treatment
|
|
Definition
|
|
Term
Boiler water having high alkalinity could develop:
caustic embrittlement
Exam 10: Boiler Water Treatment
|
|
Definition
|
|
Term
Deposits of calcium and magnesium carbonate on the boiler heating surface cause:
scale
Exam 10: Boiler Water Treatment
|
|
Definition
|
|
Term
Cracking of the boiler metal along the seams and tube ends is caused by:
caustic embrittlement
Exam 10: Boiler Water Treatment
|
|
Definition
|
|
Term
Chemicals added to the boiler water change the scale-forming salts into:
A non-adhering sludge
Exam 10: Boiler Water Treatment
|
|
Definition
|
|
Term
Oxygen in the boiler will cause:
pitting of boiler metal
Exam 10: Boiler Water Treatment
|
|
Definition
|
|
Term
Oxygen present in the boiler water is removed by:
heating the feed water and using sodium sulfite
Exam 10: Boiler Water Treatment
|
|
Definition
|
|
Term
The frequency of blowing down a steam boiler is best ascertained by the:
daily testing of boiler water
Exam 10: Boiler Water Treatment
|
|
Definition
|
|
Term
Closer control of boiler water chemical concentrations is maintained by:
continuous blow downs
Exam 10: Boiler Water Treatment
|
|
Definition
|
|
Term
When taking over a shift, the boiler operator must first check:
The water level on all boilers that are on the line by blowing down the water column and gauge glass
Exam 11: Steam Boiler Operation
|
|
Definition
|
|
Term
The low water fuel cut off control can be tested:
by blowing down the low-water fuel cut off or allowing the water level in the boiler to drop
Exam 11: Steam Boiler Operation
|
|
Definition
|
|
Term
The purpose of a flame failure control is to protect the boiler from:
A possible furnace explosion
Exam 11: Steam Boiler Operation
|
|
Definition
|
|
Term
After establishing the proper boiler water level, the burner may be lit after:
purging the furnace
Exam 11: Steam Boiler Operation
|
|
Definition
|
|
Term
The automatic non-return valve on a boiler being cut in on a line should be open to when the steam pressure on the boiler reaches:
75% to 85% of the line pressure
Exam 11: Steam Boiler Operation
|
|
Definition
|
|
Term
It is good operating procedure to test the safety valve on an incoming boiler by hand:
before the boiler is cut in on the line
Exam 11: Steam Boiler Operation
|
|
Definition
|
|
Term
When cutting a boiler in on a line equipped with two hand operated steam stop valves, the pressure on the boiler should be ______ line pressure.
slightly lower than. (75% to 85%)
Exam 11: Steam Boiler Operation
|
|
Definition
|
|
Term
Boilers equipped with a superheater must be protected during warm-up by:
keeping the superheater drain valve open until the boiler is cut in on the line
Exam 11: Steam Boiler Operation
|
|
Definition
|
|
Term
Superheaters are prevented from overheating by the circulation of:
steam
Exam 11: Steam Boiler Operation
|
|
Definition
|
|
Term
When the steam pressure in the boiler has dropped to 10 psi or 15 psi the ______ should be opened.
boiler vent
Exam 11: Steam Boiler Operation
|
|
Definition
|
|
Term
After a boiler has had major repair work made on its steam or water side or has developed a low-water condition, it should be subjected to:
a hydrostatic test
Exam 11: Steam Boiler Operation
|
|
Definition
|
|
Term
Flame failure controls use a:
flame scanner
Exam 11: Steam Boiler Operation
|
|
Definition
|
|
Term
If there is a danger of the boiler freezing, the boiler should be laid up:
completely dry
Exam 11: Steam Boiler Operation
|
|
Definition
|
|
Term
A low water fuel cut off:
shuts off the fuel supply
Exam 11: Steam Boiler Operation
|
|
Definition
|
|
Term
A boiler that has experienced a low water condition should be:
Thoroughly examined for signs of overheating
& Hydrostatic tested
Exam 11: Steam Boiler Operation
|
|
Definition
|
|
Term
A high water level condition in the boiler can be corrected by using:
bottom blow down
Exam 11: Steam Boiler Operation
|
|
Definition
|
|
Term
High pressure steam boilers generally operate at pressures
Above 15 psi and over 6 boiler horsepower
Sample Test
|
|
Definition
|
|
Term
Pressure gauges should never have a range less than
1½ times the safety valve set pressure Sample Test
|
|
Definition
|
|
Term
After water is blown out of a siphon, why should live steam never be allowed to enter a Bourdin tube?
Live steam will damage the pressure gauge
Sample Test
|
|
Definition
|
|
Term
All of the following are essential to maintain the proper fuel oil pressure with fuel oil accessories EXCEPT
Obtaining the correct difference in pressure inside and outside the boiler.
Sample Test
|
|
Definition
|
|
Term
Which of the following could be dangerous to safe operation of a low pressure boiler?
Adding water to an operating boiler when the water level cannot be seen in the gauge glass tube
Sample Test
|
|
Definition
|
|
Term
Which of the following is best if a low-pressure boiler does not have an air vent?
Vent the boiler with the try cocks
Sample Test
|
|
Definition
|
|
Term
What is the purpose of an evaporation test on a low pressure boiler?
To test the low water cutoff control
Sample Test
|
|
Definition
|
|
Term
Following flame failure, controls must de-energize fuel and ignition circuits
Within 4 seconds
Sample Test
|
|
Definition
|
|
Term
How can an operator prevent damage to the tubes while using a cleaner to remove scale from boiler tubes?
Never allow the cleaner to stay in one place
Sample Test
|
|
Definition
|
|
Term
In a steam boiler, which of the following should never be placed between the safety relief valve and the boiler?
A shut-off valve
Sample Test
|
|
Definition
|
|
Term
Which of these should be used on live electrical fires?
Class C extinguishers
Sample Test
|
|
Definition
|
|
Term
If certain grades of fuel oil are not preheated properly, they may cause
Poor combustion and high fuel consumption
Sample Test
|
|