Analysing Flue Gases
Using ECGA
29
Chemical Engineering
Professional
10/23/2015

Additional Chemical Engineering Flashcards

 


 

Cards

Term
E.C.G.A
Definition
Electronic COMBUSTION Gas Analyser
Term
Basic ECGA
Definition
Can measure O2 and CO
Can calculate CO2
Can measure ambient temp
And Flue Gas Temp
Term
Calibration of analyser
Definition
Check O2 level-s/b 20.9%+- 0/1%
(20.8-21% OK)
CO level s/b ZERO
Term
Difference between GROSS and NET
Definition
GROSS:Is based on Max c.v the gas will produce.
NET: Is based on GROSS-The latent heat of condensation for natural gas
Term
ECGA
Flueless Appliances
Definition
1.Bent probe with holes used for flueless gas fires.
2.Straight probe with holes used for testing cooker grills
Term
R.S.A without an internal test point
Definition
Position the Analyser,in the flue outlet duct outside
Term
ECGA
Open flued appliances
Definition
Position the probe up through the D.D.
In about 200mm
Term
ECGA
Mandatory
Definition
For commissioning of c.h boilers and servicing if A band condensing boilers
Term
ECGA
SENSORS
Definition
ECGA
Moving away from electrolytic sensors to IR sensors.
(Reduces maintenance and cost of calibration )
Term
ECGA.
Testing of other fuels
Definition
Change the fuel when testing combustion of other fuels
Or CO2 readings will be incorrect.
Term
Taper Plug Valve
Construction
Definition
Consists of a tapered brass or aluminium
barrel.
Term
Taper Plug Valve
Construction 2
Definition
2.Barrel is inserted into the body of the valve.Held in place by a spring or nut.
Term
Taper Plug Valve
Operation
Definition
Lubricated by graphite grease,this ensures ease of operation and remains gas tight
Term
Taper Plug Valve
operation 2
Definition
Valve is operated manually by means of handle/knob.
Commonly used to isolate appliances or installations.
Term
Open Flued Appliance COMPARTMENT Venting to OUTSIDE
Definition

High Level 5cm2/kW Low Level 10cm2/kW

In Room-NIL

[image]
Term
Open Flued Appliance
COMPARTMENT
Venting to ROOM
Definition
High Level 10cm2/kW
Low Level 20cm2/kW
Room Vent-Max Heat Input(net)-7kW x 5cm2[image]
Term
Open Flued Appliance
ROOM
Definition
Max Heat Input(Net)-7kW x 5cm2
Term
Room Sealed Appliance
COMPARTMENT
Venting to OUTSIDE
Definition
High Level-5cm2/kW
Low Level -5cm2/kW
In Room-NIL[image]
Term
Room Sealed Appliance
COMPARTMENT
Venting to ROOM
Definition
High Level 10cm2/kW
Low Level 10cm2/kW
In Room-NIL[image]
Term
Room Sealed Appliance
Room
Definition
No Vent Required[image]
Term
Ventilation
NET Heat Input Value
Definition
Divide the gross value by 1.1
Term
Adventitious Ventilation
Definition
Air that can leak into buildings through windows,doors,floorboards walls etc
Term
DFEF
Definition
No allowance can be made for adventitious ventilation
Term
Intumescent Air Vent
Definition
Specially designed to prevent spread of fire.
Normally an insert with metal framework,open latticework of heat sensitive material
Term
Design width of Vent grill
Definition
Permits entry of a ball of 5mm diameter
but prevents entry of a ball of 10mm diameter
Term
Installation of a vent in internal wall or door
Definition
No greater than
450mm from floor level
Term
Fluess appliance ventilation requirements
Definition
Consult M.Is
or table in BS5440-2
Any air vent required must be direct to outside
Term
Ventilation for flueless space heater in a ROOM
Definition
1.Convert kW to Watts by x the net heat input by 1000
2.Then DIVIDE by the volume of the room
Answer must be 45W/m3 or less
Term
Gas Fired Appliances
Minimum Flue Diameter is
Definition
125mm[image]