Term
Identify the three major objectives of electrical distribution protection systems |
|
Definition
- Rapidly disconnect fault from system
- Minimize system disruption
- Keep system component damage to a minimum
|
|
|
Term
Identify the types of molded case breakers used at LGS, and describe how they accomplish their function |
|
Definition
|
|
Term
How do you reset a tripped molded case breaker? |
|
Definition
From tripped/neutral position, take toggle switch to OFF then to ON |
|
|
Term
Function and Operation of MCC Bucket:
Control Power Transformer |
|
Definition
- Provides single phase 120VAC to control, auxiliary and indication circuits.
|
|
|
Term
Function and operation of MCC Bucket:
Contactors |
|
Definition
Contactors contain electromagnetic relays that close the contacts in the main power supply to the load when they are energized by the control circuit |
|
|
Term
Function and operation of MCC Bucket:
Thermal Overloads |
|
Definition
- Provide overcurrent protection for each phase of a motor
- Any one phase actuation will cause an open in the control circuit
- Can be reset when cooled
|
|
|
Term
What are the two types of thermal overload protection devices and how are they reset? |
|
Definition
- Eutectic (solder pots) - Reset by pushbutton on MCC door - does NOT require opening door. Eutectic devices are bring phased out and replaced with bi-metallic devices.
- Bi-metallic (dissimilar metals) - Pushbutton does not align with button on MCC door; therefore, door must be opened to reset.
|
|
|
Term
Function and operation of MCC Bucket:
Terminal Blocks |
|
Definition
- Terminal blocks provide connection points for contol, auxiliary and indication circuits
|
|
|
Term
Function and operation of MCC Bucket:
Seismic Clips |
|
Definition
- Provide rigid support for MCC bucket housing
- Safeguard buckets have 4 clips
- Non-safeguard buckets have 2 clips
|
|
|
Term
Function and operation of 480V Load Center Breaker:
Closing Springs |
|
Definition
- Discharged to close the breaker
- Charged by an AC motor, or manually when control power is unavailable
|
|
|
Term
Function and operation of 480V Load Center Breaker:
Arc Chutes |
|
Definition
- Contain metal arc barriers to elongate and cool the arc from the arcing contacts
|
|
|
Term
Function and operation of 480V Load Center Breaker:
Trip Buttons |
|
Definition
- Mechanical trip button opens breaker manually
|
|
|
Term
Function and operation of 480V Load Center Breaker:
Automatic Trip Indicator |
|
Definition
- Protrudes from front plate to indicate an overcurrent trip, can be reset by pushing back in
|
|
|
Term
Function and operation of 480V Load Center Breaker:
Automatic Trip Lockout |
|
Definition
- Mechanically prevents closing breaker after an overcurrent trip
- Can be reset by pushing in automatic trip indicator
|
|
|
Term
Function and operation of 480V Load Center Breaker:
Padlocking device |
|
Definition
- Provides a means for locking the breaker in the trip free position
- Maintains manual trip button in trip direction (inwards) when locking plate is held forward
- Push manual trip inward to push locking plate outward
|
|
|
Term
Function and operation of 480V Load Center Breaker:
Closing Spring Charge Indicator |
|
Definition
- Indicates whether spring is charged or discharged,
- Closing spring is automatically charged after tripping (closing) unless motor disconnect switch is in OFF
|
|
|
Term
Function and operation of 480V Load Center Breaker:
Motor disconnect switch |
|
Definition
- Toggle switch connected in series with charging motor,
- Used to disconnect motor from voltage source
|
|
|
Term
Function and operation of 480V Load Center Breaker:
Electrical Close Pushbutton |
|
Definition
- Used to electrically close breaker from the front panel,
- If breaker can be operated remotely this can only be performed in the TEST position
|
|
|
Term
Function and operation of 480V Load Center Breaker:
Manual Close Lever |
|
Definition
- Provides a means of manually closing the breaker without control power
|
|
|
Term
Function and operation of 480V Load Center Breaker:
Racking Mechanism |
|
Definition
- Used to move the circuit breaker to CONNECTED, TEST, or DISCONNECTED positions,
- Racking shutter interlocked with breaker contacts
- Contacts must be open for shutter to lift
- Breaker cannot be closed when shutter open
|
|
|
Term
Function and operation of 480V Load Center Breaker:
Emergency Charging Device |
|
Definition
A maintenance handle is used to charge the closing springs, the breaker can be closed manually once the springs are charged |
|
|
Term
Identify the 480 VAC load center breaker housing positions and functions available |
|
Definition
- CONNECTED
- Main breaker connections are connected
- All control contacts are connected
- TEST
- Main breaker connections are disengaged from bus
- Certain control contacts are connected to allow testing breaker operation
- DISCONNECTED
- Main breaker connections are disengaged from bus
- All control contacts are disengaged
|
|
|
Term
Identify the function and operation of 2.3/4.16/13.2 KV breaker:
Arcing contacts |
|
Definition
- Set of moving and stationary contacts that make connection before the main contacts
- Arcing contacts are replaceable, burning and pitting from arcing is normal for breaker operation
|
|
|
Term
Identify the function and operation of 2.3/4.16/13.2 KV breaker:
Main contacts |
|
Definition
- Consist of a set of moving and stationary contacts that supply power from the bus to the load when closed
|
|
|
Term
Identify the function and operation of 2.3/4.16/13.2 KV breaker:
Puffers |
|
Definition
- Cylindrical operated bellows, with a nozzle, that provide a blast of air to force the arc (generated during breaker opening) into the arc chute
|
|
|
Term
Identify the function and operation of 2.3/4.16/13.2 KV breaker:
Arc Chutes |
|
Definition
Ceramic enclosures that use plates to elongate and cool generated arcs |
|
|
Term
Identify the function and operation of 2.3/4.16/13.2 KV breaker:
Interphase barriers |
|
Definition
Act as insulators for each phase by surrounding the arc chutes |
|
|
Term
Identify the function and operation of 2.3/4.16/13.2 KV breaker:
Closing Coil |
|
Definition
A solenoid that releases the energy in the closing spring |
|
|
Term
Identify the function and operation of 2.3/4.16/13.2 KV breaker:
Closing Spring |
|
Definition
- A spring that forces the main and arcing contacts to close and charge the opening spring,
- Closing spring is charged by a DC motor at the end of a closing cycle or when the breaker is racked-in to the TEST position (aux contacts madeup in test)
|
|
|
Term
Identify the function and operation of 2.3/4.16/13.2 KV breaker:
Closing spring charging |
|
Definition
- Charged by a ratcheting mechanism connected to a DC motor,
- Charged after breaker is closed, or
- When breaker is racked-in to TEST
|
|
|
Term
Identify the function and operation of 2.3/4.16/13.2 KV breaker:
Trip Coil |
|
Definition
Breaker opening is accomplished by energizing a solenoid (trip coil) that will release the energy stored in the opening spring, to force the main and arcing contacts open.
Solenoid can be opened manually/mechanically with the trip pushbutton. |
|
|
Term
Identify the function and operation of 2.3/4.16/13.2 KV breaker:
Racking Device |
|
Definition
- Used to change breaker position (connected/test/disc) within the housing
- The release lever must be rotated to the left to turn the racking mechanism
- The release lever cannot be moved to the left when the breaker main contacts are closed, to prevent racking in or out a CLOSED breaker
|
|
|
Term
Identify the function and operation of 2.3/4.16/13.2 KV breaker:
Primary/Secondary disconnects
|
|
Definition
Primary disconnects - 6 disconnects used to connect the breaker to the line and bus terminals. They are connected to the bus and line when the breaker is in the CONNECTED position.
Secondary disconnect - Single (1) contact that connects control power to the breaker when in TEST or CONNECTED positions. |
|
|
Term
Identify the function and operation of 2.3/4.16/13.2 KV breaker:
Auxiliary Switches |
|
Definition
Operated by main contact position or breaker housing position depending on the application required. |
|
|
Term
Identify the function and operation of 2.3/4.16/13.2 KV breaker:
Safety shutter |
|
Definition
Automatically covers the bus and line ports when the breaker is removed from the compartment, to provide worker protection. |
|
|
Term
Identify the function and operation of 2.3/4.16/13.2 KV breaker:
Ground bus contacts and motor extension |
|
Definition
Ground bus contacts engage a ground bus extension to provide ground protection for the breaker.
Contacts are located in the bottom rear of the breaker.
Extension is located between the floor guides toward the front of the housing. |
|
|
Term
Identify the function of high voltage ground trucks |
|
Definition
Provide protection of equipment and workers by connecting electrical systems or components to ground,
Provide safe access to live terminals for bus/line phase-out testing,
Capable of connecting either the BUS or LINE side to ground |
|
|
Term
Function and operation of ground truck:
Selector switch |
|
Definition
Determines whether the BUS or LINE side will be connected to ground
Operated using a removable handle on the left side of the ground truck
Visual verification of selector switch position can be made at the rear of the ground truck and a position indicator is available on the front of the truck |
|
|
Term
Function and operation of ground truck:
Main contacts |
|
Definition
Operated remotely from a control station on the wall near the switchgear |
|
|
Term
Function and operation of ground truck:
Ground truck control station |
|
Definition
- Connected to ground truck control cable,
- Controls closing of ground truck main contacts
|
|
|
Term
Function and operation of ground truck:
Test Ports |
|
Definition
Allow access to terminals for checking/comparing voltages on the BUS and LINE |
|
|
Term
Function and operation of ground truck:
Key interlock system |
|
Definition
Provided to maximize operator safety during the ground truck operation by requiring certain conditions to be met for a key to be available to perform required actions |
|
|
Term
What position is the ground truck in when it is connected? |
|
Definition
TEST - The ground truck doesn't go in as far as the breaker does, it is connected at the TEST postion |
|
|